Panelboards

Refer to NQ Panelboards

NQ Panelboards

This page contains UL Tested and Certified series combination ratings for panelboards. These ratings apply to either an integral main located in the same enclosure or a remote main located in a separate enclosure.

NQ Series Connected Circuit Breaker Ratings (RMS Symmetrical)

Maximum System Voltage AC [1]

Maximum Short Circuit Current Rating[2]

Square D™ Brand Integral or Remote Main Circuit Breakers and Remote Main Fuses[3][4][5]

Square D™ Brand Branch Circuit Breaker Catalog Designation and
Allowable Ampere Ranges 

Type[6][7][8]

1 Pole

2 Pole

3 Pole

120/240 1P/3W
208Y/120 3P/4W
240/120 3P/4W

18,000

LA / LH

QO (B)

15–30 A

15–30 A

22,000

QO (B) VH, QOB-VH

QO (B)

15–70 A

15–125 A

QO (B) GFI

15–30 A

15–60 A

QO (B) EPD

15–30 A

15–60 A

QO (B) PL

15–30 A

15–60 A

QO (B) AFI

15–20 A

QO (B) CAFI

15–20 A

15–20 A

QO (B) DF

15–20 A

25,000

QD

QO (B)

15–70 A

15–125 A

QOB-VH

150 A

QO (B) PL

15–30 A

15–60 A

QO (B) GFI

15–30 A

15–60 A

QO (B) EPD

15–30 A

15–60 A

QO (B) AFI

15–20 A

QO (B) CAFI

15–20 A

15–20 A

QO (B) DF

15–20 A

ED

QO (B)

15–70 A

15–125 A

QO (B) GFI

15–30 A

15–60 A

QO (B) EPD

15–30 A

15–60 A

QO (B) AFI

15–20 A

QO (B) CAFI

15–20 A

15–20 A

QO (B) DF

15–20 A

BD, HD, JD, LD

QO (B)

15–70 A

15–125 A

QOB-VH

150 A

QO (B) PL

15–30 A

15–60 A

QO (B) GFI

15–30 A

15–60 A

QO (B) EPD

15–30 A

15–60 A

QO (B) AFI

15–20 A

QO (B) CAFI

15–20 A

15–20 A

QO (B) DF

15–20 A

42,000

LA

QO (B)

15–30 A

15–30 A

65,000

QG

QO (B)

15–70 A

15–125 A

QO(B) VH

15–70 A

15–125 A

QOB-VH

150 A

QO (B) GFI

15–30 A

15–60 A

QO (B) PL

15–30 A

15–60 A

QO (B) AFI

15–20 A

QO (B) CAFI

15–20 A

15–20 A

QO (B) DF

15–20 A

EG

QO (B)

15–70 A

15–125 A

QO (B) GFI

15–30 A

15–60 A

QO (B) EPD

15–30 A

15–60 A

QO (B) EPE

QO (B) AFI

15–20 A

QO (B) CAFI

15–20 A

15–20 A

QO (B) DF

15–20 A

BG, HG, JG, LG

QO (B)

15–70 A

15–125 A

QOB-VH

150 A

QO (B) PL

15–30 A

15–60 A

QO (B) GFI

15–30 A

15–60 A

QO (B) EPD

15–30 A

15–60 A

QO (B) AFI

15–20 A

QO (B) CAFI

15–20 A

15–20 A

QO (B) DF

15–20 A

100,000

QJ

QO (B)

15–70 A

15–125 A

QOB-VH

150 A

QO (B) PL

15–30 A

15–60 A

QO (B) GFI

15–30 A

15–60 A

QO (B) EPD

15–30 A

15–60 A

QO (B) AFI

15–20 A

QO (B) CAFI

15–20 A

15–20 A

QO (B) DF

15–20 A

EJ

QO (B)

15–70 A

15–125 A

QO (B) GFI

15–30 A

15–60 A

QO (B) EPD

15–30 A

15–60 A

QO (B) AFI

15–20 A

QO (B) CAFI

15–20 A

15–20 A

QO (B) DF

15–20 A

BJ, HJ, JJ

QO (B)

15–70 A

15–125 A

QOB-VH

150 A

QO (B) PL

15–30 A

15–60 A

QO (B) GFI

15–30 A

15–60 A

QO (B) EPD

15–30 A

15–60 A

QO (B) AFI

15–20 A

QO (B) CAFI

15–20 A

15–20 A

QO (B) DF

15–20 A

LJ

QO (B)

15–70 A

15–125 A

QOB-VH

150 A

QO (B) GFI

15–60 A

QO (B) EPD

15–60 A

QO (B) AFI

15–20 A

QO (B) CAFI

15–20 A

15–20 A

QO (B) DF

15–20 A

125,000

HL, JL

QO (B)

15–70 A

15–125 A

QOB-VH

150 A

QO (B) PL

15–30 A

15–60 A

QO (B) GFI

15–30 A

15–60 A

QO (B) EPD

15–30 A

15–60 A

QO (B) AFI

15–20 A

QO (B) CAFI

15–20 A

15–20 A

QO (B) DF

15–20 A

200,000

HR, JR

QO (B)

15–70 A

15–125 A

QO (B) GFI

15–30 A

15–60 A

QO (B) EPD

15–30 A

15–60 A

QO (B) AFI

15–20 A

QO (B) CAFI

15–20 A

15–20 A

QO (B) DF

15–20 A

240 1P/2W

25,000

QD, BD, HD, JD, LD

QO (B) H

15–100 A

42,000

LA

QDL

70–225 A

65,000

QG, BG, HG, JG, LG

QO (B) H

15–100 A

100,000

BJ, HJ, JJ, LJ

QO (B) H

15–100 A

125,000

HL, JL

QO (B) H

15–100 A

208Y/120 3P/4W

18,000

LA/LH

QO (B)

15–30 A

22,000 QO (B) VH, QOB-VH QO (B) GFI

15–50 A

25,000

QD, ED, BD, HD, JD

QO (B) GFI

15–50 A

LD

QO (B) GFI

15–30 A

65,000

QG, EG, BG, HG, JG

QO (B) GFI

15–50 A

LG

QO (B) GFI

15–30 A

100,000

QJ

QO (B)

15–30 A

QO (B) VH

15–100 A

QOB-VH

110–150 A

QO (B) PL

15–30 A

QO (B) GFI

15–50 A

QO (B) EPD

15–50 A

QO (B) EPE

15–50 A

EJ, BJ, HJ, JJ

QO (B) GFI

15–50 A

240/120 3P/4W
240 3P/3W

22,000

QO (B) VH

QO (B)

15–100 A

QO (B) EPD

15–50 A

QO (B) EPE

15–50 A

25,000

QD

QO (B)

15–30 A

QO (B) VH

15–100 A

QOB-VH

110–150 A

QO (B) PL

15–30 A

QO (B) EPD

15–50 A

QO (B) EPE

15–50 A

ED

QO (B)

15–100 A

QO (B) EPD

15–50 A

QO (B) EPE

15–50 A

BD, HD, JD

QO (B)

15–100 A

QO (B) VH

110–150 A

QO (B) PL

15–30 A

QO (B) EPD

15–50 A

QO (B) EPE

15–50 A

LD

QO (B) VH

15–100 A

QOB-VH

110–150 A

QO (B) EPD

15–30 A

QO (B) EPE

15–30 A

42,000

LA

QDL

70–225 A

QO (B) VH

15–30 A

MG

QOB-VH

110-150A

65,000

QG

QO (B)

15–30 A

QO (B) VH

15–100 A

QOB-VH

110–150 A

QO (B) PL

15–30 A

EG, FG

QO (B)

15–100 A

QOB-VH

110–125 A

QO (B) EPD

15–50 A

QO (B) EPE

15–50 A

BG, HG, JG

QO (B)

15–100 A

QOB-VH

110–150 A

QO (B) PL

15–30 A

QO (B) EPD

15–50 A

QO (B) EPE

15–50 A

LG

QO (B) VH

15–100 A

QOB-VH

110–150 A

QO (B) EPD

15–30 A

QO (B) EPE

15–30 A

EJ

QO (B)

15–100 A

QOB-VH

110–125 A

QO (B) EPD

15–50 A

QO (B) EPE

15–50 A

BJ, HJ, JJ

QO (B)

15–100 A

QOB-VH

110–150 A

QO (B) PL

15–30 A

QO (B) EPD

15–50 A

QO (B) EPE

15–50 A

LJ

QO (B) VH

15–100 A

QOB-VH

110-150A

125,000

HL, JL

QO (B)

15–100 A

QOB-VH

110-150A

QO (B) PL

15–30 A

QO (B) EPD

15–50 A

QO (B) EPE

15–50 A

200,000

HR, JR

QO (B)

15–100 A

QOB-VH

110-150A

120/240 1P/3W
208Y/120 3P/4W
240/120 3P/4W

42,000

400 A Max. Class T3 Fuses

QO (B) VH

15–70 A

15–125 A

65,000

400 A Max. Class J Fuses

QO (B) VH

15–70 A

15–125 A

QO (B) AFI

15–20 A

QO (B) CAFI

15–20 A

15–20 A

QO (B) DF

15–20 A

400 A Max. Class T6 Fuses

QO (B) VH

15–70 A

15–125 A

QOB-VH

150 A

QO (B) AFI

15–20 A

QO (B) CAFI

15–20 A

15–20 A

QO (B) DF

15–20 A

100,000

200 A Max. Class T3 Fuses

QO (B)

15–70 A

15–125 A

QO (B) GFI

15–30 A

15–60 A

QO (B) EPD

15–30 A

15–60 A

QO (B) AFI

15–20 A

QO (B) CAFI

15–20 A

15–20 A

QO (B) DF

15–20 A

200,000

200 A Max. Class T6 or J Fuses

QO (B)

15–70 A

15–125 A

QO (B) GFI

15–30 A

15–60 A

QO (B) EPD

15–30 A

15–60 A

400 A Max. Class T3 Fuses

QO (B)

15–70 A

15–125 A

QO (B) GFI

15–30 A

15–60 A

QO (B) EPD

15–30 A

15–60 A

208Y/120 3P/4W

65,000

400 A Max Class J

QO (B) GFI

15–50 A

100,000

200 A Max Class T3

QO (B) GFI

15–50 A

200,000

200 A Max. Class T6 or J Fuses

QO (B) GFI

15–50 A

400 A Max. Class T3 Fuses

QO (B) GFI

15–50 A

240/120 3P/4W
240 3P/3W

50,000

600 A Max. Class T3 Fuses

QO (B) VH

15–30 A

65,000

400 A Max. Class J Fuses

QO (B) VH

15–100 A

400 A Max. Class T6 Fuses

QO (B) VH

15–100 A

QOB-VH

110–150 A

100,000

200 A Max. Class T3 Fuses

QO (B)

15–100 A

QO (B) EPD

15–50 A

QO (B) EPE

15–50 A

200,000

200 A Max. Class T6 or J Fuses

QO (B)

15–100 A

QO (B) EPD

15–50 A

QO (B) EPE

15–50 A

400 A Max. Class T3 Fuses

QO (B)

15–100 A

QO (B) EPD

15–50 A

QO (B) EPE

15–50 A



NF Panelboards

This page contains UL Tested and Certified series combination ratings for panelboards. These ratings apply to either an integral main located in the same enclosure or a remote main located in a separate enclosure.

NF Series Connected Circuit Breaker Ratings (RMS Symmetrical)

Maximum System

Voltage, AC [9]

Max. Short Circuit
Current Rating

Square D™ Brand Integral or Remote
Main Circuit Breakers and Remote Main Fuses[10]

Square D™ Brand Branch Circuit Breaker Catalog
Designation and Allowable Ampere Ranges

Circuit Breaker Abbreviation[11]

1 Pole

2 Pole

3 Pole

120

120/240

240

65,000

EG, BG, HG, JG, LG, LH

EDB

15–70

15–125

15–125

EG

ECB-G3

15–30

15–30

15–30

100,000

EJ, BJ, HJ, JJ, LJ

EDB, EGB

15–70

15–125

15–125

EJ, BJ, HJ, JJ

ECB-G3

15–30

15–30

15–30

125,000

HL, JL

EDB, EGB, EJB

15–70

15–125

15–125

HL, JL

ECB-G3

15–30

15–30

15–30

200,000

HR, JR, LR

EDB, EGB, EJB

15–70

15–125

15–125

HR, JR

ECB-G3

15–30

15–30

15–30

Class J or T (600 V) 200 A Max Fuses

ECB-G3

15–30

15–30

15–30

277
480Y/277

35,000

EG, BG, HG, JG, LG, LH

EDB

15–70

15–125

15–125

EG, BG, HG, JG, LG, LH

EDB-EPD

15–50

EG, BG, HG, JG

ECB-G3

15–30

15–30

15–20

65,000

EJ, BJ, HJ, JJ, LJ

EDB, EPD

15–70

15–125

15–125

EJ, BJ, HJ, JJ, LJ, LL

EDB-EPD, EGB-EPD

15–50

EJ, BJ, HJ, JJ

ECB-G3

15–30

15–30

15–20

100,000

HL, JL, LL

EDB, EGB, EJB

15–70

15–125

15–125

HL, JL, LL

EDB-EPD, EGB-EPD, EJB-EPD

15–50

Class J or T (600 V) 400 A Max Fuses

EDB, EGB, EJB

15–70

15–125

15–125

Class J or T (600 V) 400 A Max Fuses

EDB-EPD, EGB-EPD, EJB-EPD

15–50

200,000

HR, JR, LR

EDB, EGB, EJB

15–70

15–125

15–125

HR, JR, LR

EDB-EPD, EGB-EPD, EJB-EPD

15–50

HR, JR

ECB-G3

15–30

15–30

15–20

Class J or T (600 V) 200 A Max Fuses

EDB, EGB, EJB

15–70

15–125

15–125

Class J or T (600 V) 200 A Max Fuses

EDB-EPD, EGB-EPD, EJB-EPD

15–50

Class J or T (600 V) 200 A Max Fuses

ECB-G3

15–30

15–30

15–20

347
600Y/347

18,000

HG, BG, JG, LG

EDB

15–70

15–100

15–100

25,000

EJ, BJ, HJ, JJ, LJ, LH

EDB, EGB

15–70

15–100

15–100

50,000

HL, JL, LL

EDB, EGB, EJB

15–70

15–100

15–100

65,000

HR, JR

EDB, EGB, EJB

15–70

15–100

15–100

LR

EJB

15–70

15–100

15–100

200,000

Class J or T (600 V) 200 A Max Fuses

EDB, EGB, EJB

15–70

15–100

15–100

Footnotes

  1. Series Ratings listed at higher system voltages apply to lower system voltages (Example: 240 3P/3W covers 208Y/120 3P/4W).
  2. Short Circuit tests are conducted at 100–105% of the maximum rated voltage of the panelboard.
  3. Please consult the NQ/NQM Panelboards Information Manual (80043-712-06) for additional information, including series ratings with obsolete circuit breakers.
  4. Where LG is shown, LJ and LL can be used.
  5. Unless otherwise noted, main breakers can be applied at the maximum available amperage rating.
  6. Suffixes HID, SWD, and SWN may also be applied to the applicable branch circuit breakers shown above.
  7. Where QO(B) circuit breakers are shown above, QO(B)H, QO(B)VH, and QH(B) circuit breakers may also be used.
  8. Two-pole CAFI circuit breakers cannot be used on 208Y/120V systems.
  9. Short circuit tests are conducted at 100–105% of the maximum rated voltage of the panelboard.
  10. Please consult the NF/NFOM Panelboards Information Manual (80043-741-03) for additional information, including series ratings with obsolete circuit breakers.
  11. EDB-EPD, EGB-EPD & EJB-EPD suitable for 480Y/277Vac or 277Vac ONLY.

Was this helpful?