Panelboards
Refer to NQ Panelboards
NQ Panelboards
This page contains UL Tested and Certified series combination ratings for panelboards. These ratings apply to either an integral main located in the same enclosure or a remote main located in a separate enclosure.
NQ Series Connected Circuit Breaker Ratings (RMS Symmetrical)
Maximum System Voltage AC [1] |
Maximum Short Circuit Current Rating[2] |
Square D™ Brand Integral or Remote Main Circuit Breakers and Remote Main Fuses[3][4][5] |
Square D™
Brand Branch Circuit Breaker Catalog Designation and |
|||
---|---|---|---|---|---|---|
1 Pole |
2 Pole |
3 Pole |
||||
120/240
1P/3W |
18,000 |
LA / LH |
QO (B) |
15–30 A |
15–30 A |
— |
22,000 |
QO (B) VH, QOB-VH |
QO (B) |
15–70 A |
15–125 A |
— |
|
QO (B) GFI |
15–30 A |
15–60 A |
— |
|||
QO (B) EPD |
15–30 A |
15–60 A |
— |
|||
QO (B) PL |
15–30 A |
15–60 A |
— |
|||
QO (B) AFI |
15–20 A |
— |
— |
|||
QO (B) CAFI |
15–20 A |
15–20 A |
— |
|||
QO (B) DF |
15–20 A |
— |
— |
|||
25,000 |
QD |
QO (B) |
15–70 A |
15–125 A |
— |
|
QOB-VH |
— |
150 A |
— |
|||
QO (B) PL |
15–30 A |
15–60 A |
— |
|||
QO (B) GFI |
15–30 A |
15–60 A |
— |
|||
QO (B) EPD |
15–30 A |
15–60 A |
— |
|||
QO (B) AFI |
15–20 A |
— |
— |
|||
QO (B) CAFI |
15–20 A |
15–20 A |
— |
|||
QO (B) DF |
15–20 A |
— |
— |
|||
ED |
QO (B) |
15–70 A |
15–125 A |
— |
||
QO (B) GFI |
15–30 A |
15–60 A |
— |
|||
QO (B) EPD |
15–30 A |
15–60 A |
— |
|||
QO (B) AFI |
15–20 A |
— |
— |
|||
QO (B) CAFI |
15–20 A |
15–20 A |
— |
|||
QO (B) DF |
15–20 A |
— |
— |
|||
BD, HD, JD, LD |
QO (B) |
15–70 A |
15–125 A |
— |
||
QOB-VH |
— |
150 A |
— |
|||
QO (B) PL |
15–30 A |
15–60 A |
— |
|||
QO (B) GFI |
15–30 A |
15–60 A |
— |
|||
QO (B) EPD |
15–30 A |
15–60 A |
— |
|||
QO (B) AFI |
15–20 A |
— |
— |
|||
QO (B) CAFI |
15–20 A |
15–20 A |
— |
|||
QO (B) DF |
15–20 A |
— |
— |
|||
42,000 |
LA |
QO (B) |
15–30 A |
15–30 A |
— |
|
65,000 |
QG |
QO (B) |
15–70 A |
15–125 A |
— |
|
QO(B) VH |
15–70 A |
15–125 A |
— |
|||
QOB-VH |
— |
150 A |
— |
|||
QO (B) GFI |
15–30 A |
15–60 A |
— |
|||
QO (B) PL |
15–30 A |
15–60 A |
— |
|||
QO (B) AFI |
15–20 A |
— |
— |
|||
QO (B) CAFI |
15–20 A |
15–20 A |
— |
|||
QO (B) DF |
15–20 A |
— |
— |
|||
EG |
QO (B) |
15–70 A |
15–125 A |
— |
||
QO (B) GFI |
15–30 A |
15–60 A |
— |
|||
QO (B) EPD |
15–30 A |
15–60 A |
— |
|||
QO (B) EPE |
— |
— |
— |
|||
QO (B) AFI |
15–20 A |
— |
— |
|||
QO (B) CAFI |
15–20 A |
15–20 A |
— |
|||
QO (B) DF |
15–20 A |
— |
— |
|||
BG, HG, JG, LG |
QO (B) |
15–70 A |
15–125 A |
— |
||
QOB-VH |
— |
150 A |
— |
|||
QO (B) PL |
15–30 A |
15–60 A |
— |
|||
QO (B) GFI |
15–30 A |
15–60 A |
— |
|||
QO (B) EPD |
15–30 A |
15–60 A |
— |
|||
QO (B) AFI |
15–20 A |
— |
— |
|||
QO (B) CAFI |
15–20 A |
15–20 A |
— |
|||
QO (B) DF |
15–20 A |
— |
— |
|||
100,000 |
QJ |
QO (B) |
15–70 A |
15–125 A |
— |
|
QOB-VH |
— |
150 A |
— |
|||
QO (B) PL |
15–30 A |
15–60 A |
— |
|||
QO (B) GFI |
15–30 A |
15–60 A |
— |
|||
QO (B) EPD |
15–30 A |
15–60 A |
— |
|||
QO (B) AFI |
15–20 A |
— |
— |
|||
QO (B) CAFI |
15–20 A |
15–20 A |
— |
|||
QO (B) DF |
15–20 A |
— |
— |
|||
EJ |
QO (B) |
15–70 A |
15–125 A |
— |
||
QO (B) GFI |
15–30 A |
15–60 A |
— |
|||
QO (B) EPD |
15–30 A |
15–60 A |
— |
|||
QO (B) AFI |
15–20 A |
— |
— |
|||
QO (B) CAFI |
15–20 A |
15–20 A |
— |
|||
QO (B) DF |
15–20 A |
— |
— |
|||
BJ, HJ, JJ |
QO (B) |
15–70 A |
15–125 A |
— |
||
QOB-VH |
— |
150 A |
— |
|||
QO (B) PL |
15–30 A |
15–60 A |
— |
|||
QO (B) GFI |
15–30 A |
15–60 A |
— |
|||
QO (B) EPD |
15–30 A |
15–60 A |
— |
|||
QO (B) AFI |
15–20 A |
— |
— |
|||
QO (B) CAFI |
15–20 A |
15–20 A |
— |
|||
QO (B) DF |
15–20 A |
— |
— |
|||
LJ |
QO (B) |
15–70 A |
15–125 A |
— |
||
QOB-VH |
— |
150 A |
— |
|||
QO (B) GFI |
— |
15–60 A |
— |
|||
QO (B) EPD |
— |
15–60 A |
— |
|||
QO (B) AFI |
15–20 A |
— |
— |
|||
QO (B) CAFI |
15–20 A |
15–20 A |
— |
|||
QO (B) DF |
15–20 A |
— |
— |
|||
125,000 |
HL, JL |
QO (B) |
15–70 A |
15–125 A |
— |
|
QOB-VH |
— |
150 A |
— |
|||
QO (B) PL |
15–30 A |
15–60 A |
— |
|||
QO (B) GFI |
15–30 A |
15–60 A |
— |
|||
QO (B) EPD |
15–30 A |
15–60 A |
— |
|||
QO (B) AFI |
15–20 A |
— |
— |
|||
QO (B) CAFI |
15–20 A |
15–20 A |
— |
|||
QO (B) DF |
15–20 A |
— |
— |
|||
200,000 |
HR, JR |
QO (B) |
15–70 A |
15–125 A |
— |
|
QO (B) GFI |
15–30 A |
15–60 A |
— |
|||
QO (B) EPD |
15–30 A |
15–60 A |
— |
|||
QO (B) AFI |
15–20 A |
— |
— |
|||
QO (B) CAFI |
15–20 A |
15–20 A |
— |
|||
QO (B) DF |
15–20 A |
— |
— |
|||
240 1P/2W |
25,000 |
QD, BD, HD, JD, LD |
QO (B) H |
— |
15–100 A |
— |
42,000 |
LA |
QDL |
— |
70–225 A |
— |
|
65,000 |
QG, BG, HG, JG, LG |
QO (B) H |
— |
15–100 A |
— |
|
100,000 |
BJ, HJ, JJ, LJ |
QO (B) H |
— |
15–100 A |
— |
|
125,000 |
HL, JL |
QO (B) H |
— |
15–100 A |
— |
|
208Y/120 3P/4W |
18,000 |
LA/LH |
QO (B) |
— |
— |
15–30 A |
22,000 | QO (B) VH, QOB-VH | QO (B) GFI |
— |
— |
15–50 A | |
25,000 |
QD, ED, BD, HD, JD |
QO (B) GFI |
— |
— |
15–50 A |
|
LD |
QO (B) GFI |
— |
— |
15–30 A |
||
65,000 |
QG, EG, BG, HG, JG |
QO (B) GFI |
— |
— |
15–50 A |
|
LG |
QO (B) GFI |
— |
— |
15–30 A |
||
100,000 |
QJ |
QO (B) |
— |
— |
15–30 A |
|
QO (B) VH |
— |
— |
15–100 A |
|||
QOB-VH |
— |
— |
110–150 A |
|||
QO (B) PL |
— |
— |
15–30 A |
|||
QO (B) GFI |
— |
— |
15–50 A |
|||
QO (B) EPD |
— |
— |
15–50 A |
|||
QO (B) EPE |
— |
— |
15–50 A |
|||
EJ, BJ, HJ, JJ |
QO (B) GFI |
— |
— |
15–50 A |
||
240/120
3P/4W |
22,000 |
QO (B) VH |
QO (B) |
— |
— |
15–100 A |
QO (B) EPD |
— |
— |
15–50 A |
|||
QO (B) EPE |
— |
— |
15–50 A |
|||
25,000 |
QD |
QO (B) |
— |
— |
15–30 A |
|
QO (B) VH |
— |
— |
15–100 A |
|||
QOB-VH |
— |
— |
110–150 A |
|||
QO (B) PL |
— |
— |
15–30 A |
|||
QO (B) EPD |
— |
— |
15–50 A |
|||
QO (B) EPE |
— |
— |
15–50 A |
|||
ED |
QO (B) |
— |
— |
15–100 A |
||
QO (B) EPD |
— |
— |
15–50 A |
|||
QO (B) EPE |
— |
— |
15–50 A |
|||
BD, HD, JD |
QO (B) |
— |
— |
15–100 A |
||
QO (B) VH |
— |
— |
110–150 A |
|||
QO (B) PL |
— |
— |
15–30 A |
|||
QO (B) EPD |
— |
— |
15–50 A |
|||
QO (B) EPE |
— |
— |
15–50 A |
|||
LD |
QO (B) VH |
— |
— |
15–100 A |
||
QOB-VH |
— |
— |
110–150 A |
|||
QO (B) EPD |
— |
— |
15–30 A |
|||
QO (B) EPE |
— |
— |
15–30 A |
|||
42,000 |
LA |
QDL |
— |
— |
70–225 A |
|
QO (B) VH |
— |
— |
15–30 A |
|||
MG |
QOB-VH |
— |
— |
110-150A |
||
65,000 |
QG |
QO (B) |
— |
— |
15–30 A |
|
QO (B) VH |
— |
— |
15–100 A |
|||
QOB-VH |
— |
— |
110–150 A |
|||
QO (B) PL |
— |
— |
15–30 A |
|||
EG, FG |
QO (B) |
— |
— |
15–100 A |
||
QOB-VH |
— |
— |
110–125 A |
|||
QO (B) EPD |
— |
— |
15–50 A |
|||
QO (B) EPE |
— |
— |
15–50 A |
|||
BG, HG, JG |
QO (B) |
— |
— |
15–100 A |
||
QOB-VH |
— |
— |
110–150 A |
|||
QO (B) PL |
— |
— |
15–30 A |
|||
QO (B) EPD |
— |
— |
15–50 A |
|||
QO (B) EPE |
— |
— |
15–50 A |
|||
LG |
QO (B) VH |
— |
— |
15–100 A |
||
QOB-VH |
— |
— |
110–150 A |
|||
QO (B) EPD |
— |
— |
15–30 A |
|||
QO (B) EPE |
— |
— |
15–30 A |
|||
EJ |
QO (B) |
— |
— |
15–100 A |
||
QOB-VH |
— |
— |
110–125 A |
|||
QO (B) EPD |
— |
— |
15–50 A |
|||
QO (B) EPE |
— |
— |
15–50 A |
|||
BJ, HJ, JJ |
QO (B) |
— |
— |
15–100 A |
||
QOB-VH |
— |
— |
110–150 A |
|||
QO (B) PL |
— |
— |
15–30 A |
|||
QO (B) EPD |
— |
— |
15–50 A |
|||
QO (B) EPE |
— |
— |
15–50 A |
|||
LJ |
QO (B) VH |
— |
— |
15–100 A |
||
QOB-VH |
— |
— |
110-150A |
|||
125,000 |
HL, JL |
QO (B) |
— |
— |
15–100 A |
|
QOB-VH |
— |
— |
110-150A |
|||
QO (B) PL |
— |
— |
15–30 A |
|||
QO (B) EPD |
— |
— |
15–50 A |
|||
QO (B) EPE |
— |
— |
15–50 A |
|||
200,000 |
HR, JR |
QO (B) |
— |
— |
15–100 A |
|
QOB-VH |
— |
— |
110-150A |
|||
120/240 1P/3W |
42,000 |
400 A Max. Class T3 Fuses |
QO (B) VH |
15–70 A |
15–125 A |
— |
65,000 |
400 A Max. Class J Fuses |
QO (B) VH |
15–70 A |
15–125 A |
— |
|
QO (B) AFI |
15–20 A |
— |
— |
|||
QO (B) CAFI |
15–20 A |
15–20 A |
— |
|||
QO (B) DF |
15–20 A |
— |
— |
|||
400 A Max. Class T6 Fuses |
QO (B) VH |
15–70 A |
15–125 A |
— |
||
QOB-VH |
— |
150 A |
— |
|||
QO (B) AFI |
15–20 A |
— |
— |
|||
QO (B) CAFI |
15–20 A |
15–20 A |
— |
|||
QO (B) DF |
15–20 A |
— |
— |
|||
100,000 |
200 A Max. Class T3 Fuses |
QO (B) |
15–70 A |
15–125 A |
— |
|
QO (B) GFI |
15–30 A |
15–60 A |
— |
|||
QO (B) EPD |
15–30 A |
15–60 A |
— |
|||
QO (B) AFI |
15–20 A |
— |
— |
|||
QO (B) CAFI |
15–20 A |
15–20 A |
— |
|||
QO (B) DF |
15–20 A |
— |
— |
|||
200,000 |
200 A Max. Class T6 or J Fuses |
QO (B) |
15–70 A |
15–125 A |
— |
|
QO (B) GFI |
15–30 A |
15–60 A |
— |
|||
QO (B) EPD |
15–30 A |
15–60 A |
— |
|||
400 A Max. Class T3 Fuses |
QO (B) |
15–70 A |
15–125 A |
— |
||
QO (B) GFI |
15–30 A |
15–60 A |
— |
|||
QO (B) EPD |
15–30 A |
15–60 A |
— |
|||
208Y/120 3P/4W |
65,000 |
400 A Max Class J |
QO (B) GFI |
— |
— |
15–50 A |
100,000 |
200 A Max Class T3 |
QO (B) GFI |
— |
— |
15–50 A |
|
200,000 |
200 A Max. Class T6 or J Fuses |
QO (B) GFI |
— |
— |
15–50 A |
|
400 A Max. Class T3 Fuses |
QO (B) GFI |
— |
— |
15–50 A |
||
240/120 3P/4W |
50,000 |
600 A Max. Class T3 Fuses |
QO (B) VH |
— |
— |
15–30 A |
65,000 |
400 A Max. Class J Fuses |
QO (B) VH |
— |
— |
15–100 A |
|
400 A Max. Class T6 Fuses |
QO (B) VH |
— |
— |
15–100 A |
||
QOB-VH |
— |
— |
110–150 A |
|||
100,000 |
200 A Max. Class T3 Fuses |
QO (B) |
— |
— |
15–100 A |
|
QO (B) EPD |
— |
— |
15–50 A |
|||
QO (B) EPE |
— |
— |
15–50 A |
|||
200,000 |
200 A Max. Class T6 or J Fuses |
QO (B) |
— |
— |
15–100 A |
|
QO (B) EPD |
— |
— |
15–50 A |
|||
QO (B) EPE |
— |
— |
15–50 A |
|||
400 A Max. Class T3 Fuses |
QO (B) |
— |
— |
15–100 A |
||
QO (B) EPD |
— |
— |
15–50 A |
|||
QO (B) EPE |
— |
— |
15–50 A |
NF Panelboards
This page contains UL Tested and Certified series combination ratings for panelboards. These ratings apply to either an integral main located in the same enclosure or a remote main located in a separate enclosure.
NF Series Connected Circuit Breaker Ratings (RMS Symmetrical)
Maximum System Voltage, AC [9] |
Max. Short Circuit |
Square D™
Brand Integral or Remote |
Square D™
Brand Branch Circuit Breaker Catalog |
|||
---|---|---|---|---|---|---|
Circuit Breaker Abbreviation[11] |
1 Pole |
2 Pole |
3 Pole |
|||
120 120/240 240 |
65,000 |
EG, BG, HG, JG, LG, LH |
EDB |
15–70 |
15–125 |
15–125 |
EG |
ECB-G3 |
15–30 |
15–30 |
15–30 |
||
100,000 |
EJ, BJ, HJ, JJ, LJ |
EDB, EGB |
15–70 |
15–125 |
15–125 |
|
EJ, BJ, HJ, JJ |
ECB-G3 |
15–30 |
15–30 |
15–30 |
||
125,000 |
HL, JL |
EDB, EGB, EJB |
15–70 |
15–125 |
15–125 |
|
HL, JL |
ECB-G3 |
15–30 |
15–30 |
15–30 |
||
200,000 |
HR, JR, LR |
EDB, EGB, EJB |
15–70 |
15–125 |
15–125 |
|
HR, JR |
ECB-G3 |
15–30 |
15–30 |
15–30 |
||
Class J or T (600 V) 200 A Max Fuses |
ECB-G3 |
15–30 |
15–30 |
15–30 |
||
277 |
35,000 |
EG, BG, HG, JG, LG, LH |
EDB |
15–70 |
15–125 |
15–125 |
EG, BG, HG, JG, LG, LH |
EDB-EPD |
15–50 |
— |
— |
||
EG, BG, HG, JG |
ECB-G3 |
15–30 |
15–30 |
15–20 |
||
65,000 |
EJ, BJ, HJ, JJ, LJ |
EDB, EPD |
15–70 |
15–125 |
15–125 |
|
EJ, BJ, HJ, JJ, LJ, LL |
EDB-EPD, EGB-EPD |
15–50 |
— |
— |
||
EJ, BJ, HJ, JJ |
ECB-G3 |
15–30 |
15–30 |
15–20 |
||
100,000 |
HL, JL, LL |
EDB, EGB, EJB |
15–70 |
15–125 |
15–125 |
|
HL, JL, LL |
EDB-EPD, EGB-EPD, EJB-EPD |
15–50 |
— |
— |
||
Class J or T (600 V) 400 A Max Fuses |
EDB, EGB, EJB |
15–70 |
15–125 |
15–125 |
||
Class J or T (600 V) 400 A Max Fuses |
EDB-EPD, EGB-EPD, EJB-EPD |
15–50 |
— |
— |
||
200,000 |
HR, JR, LR |
EDB, EGB, EJB |
15–70 |
15–125 |
15–125 |
|
HR, JR, LR |
EDB-EPD, EGB-EPD, EJB-EPD |
15–50 |
— |
— |
||
HR, JR |
ECB-G3 |
15–30 |
15–30 |
15–20 |
||
Class J or T (600 V) 200 A Max Fuses |
EDB, EGB, EJB |
15–70 |
15–125 |
15–125 |
||
Class J or T (600 V) 200 A Max Fuses |
EDB-EPD, EGB-EPD, EJB-EPD |
15–50 |
— |
— |
||
Class J or T (600 V) 200 A Max Fuses |
ECB-G3 |
15–30 |
15–30 |
15–20 |
||
347 |
18,000 |
HG, BG, JG, LG |
EDB |
15–70 |
15–100 |
15–100 |
25,000 |
EJ, BJ, HJ, JJ, LJ, LH |
EDB, EGB |
15–70 |
15–100 |
15–100 |
|
50,000 |
HL, JL, LL |
EDB, EGB, EJB |
15–70 |
15–100 |
15–100 |
|
65,000 |
HR, JR |
EDB, EGB, EJB |
15–70 |
15–100 |
15–100 |
|
LR |
EJB |
15–70 |
15–100 |
15–100 |
||
200,000 |
Class J or T (600 V) 200 A Max Fuses |
EDB, EGB, EJB |
15–70 |
15–100 |
15–100 |