SE Relays Power Relays
Refer to Catalog 8501CT1003
199 Power Relays
199—SPST-NO-DM, 40 A; SPDT, 40 A; DPST-NO, 40 A; DPDT, 40 A
Standard Part Numbers
Rated Contact Current | Contact Configuration | Coil Voltage | Coil Resistance (Ω) | Special Features | Standard Part Number |
---|---|---|---|---|---|
40 A[1] | SPST-NO-DM | 120 Vac | 290 | ||
24 Vdc | 290 | Blowout Magnet | |||
48 Vdc | 1200 | Blowout Magnet | |||
SPDT | 120 Vac | 290 | |||
12 Vdc | 70 | ||||
24 Vdc | 290 | ||||
DPST-NO | 120 Vac | 290 | |||
240 Vac | 1200 | ||||
12 Vdc | 70 | ||||
24 Vdc | 290 | ||||
DPDT | 24 Vac | 12 | |||
120 Vac | 290 | Blowout Magnet | |||
240 Vac | 1200 | ||||
12 Vdc | 70 | ||||
24 Vdc | 290 | Blowout Magnet | |||
110 Vdc | 6000 | Blowout Magnet | |||
199 Specifications (UL 508)
Part Numbers | 199AX, 199X, 199ABX [2], 199BX [2] | 199ADX, 199DX, 199DYX, 199DBX [2] |
---|---|---|
Contact Characteristics |
||
Contact Configuration | SPST, SPDT, DPST, DPDT | SPST-DM, SPST-DB |
Contact Material | Silver alloy | |
Thermal (Carrying) Current | 40 A | |
Maximum Switching Voltage | 600 V(rms) | |
Rated Switching Current at Voltage | Resistive: 40 A at 300 Vac 50/60 Hz; 5 A at 480 Vac 50/60 Hz; 5 A at 600 Vac 50/60 Hz; 40 A at 28 Vdc |
Resistive: 40 A at 300 Vac 50/60 Hz; 12 A at 480 Vac 50/60 Hz; 10 A at 600 Vac 50/60 Hz; 40 A at 28 Vdc |
Motor: 2 hp at 120–600 Vac 50/60 Hz | ||
Tungsten: 15 A at 120 Vac 50/60 Hz | ||
Pilot Duty: A600 | ||
Minimum Switching Requirement | 1 A at 5 Vac/Vdc | |
Coil Characteristics |
||
Coil Voltage Range[3] | 6–600 Vac 50/60 Hz; 6–250 Vdc2 | |
Operating Range (% of Nominal) | 85%–110% (AC); 80%–110% (DC) | |
Average Consumption (Maximum) | 10 VA (AC); 4 W (DC) | |
Drop-Out Voltage Threshold | 10% (AC/DC) |
Additional DC Ratings with Blowout Magnet
Load Voltage | Contact Rating |
---|---|
110 Vdc | 20 A |
220 Vdc | 8 A |
325 Vdc | 4 A |
500 Vdc | 2 A |
Auxiliary Switch Ratings (Non-Standard Option)
Load Type | Contact Rating |
---|---|
Resistive Load 120/250 Vac (50/60 Hz) | 10 A |
Motor Load 125/250 Vac (50/60 Hz) | 0.25 hp |
Tungsten Load 125 Vac (50/60 Hz) | 3 A |
Contact Ratings and Electrical Endurance (per IEC 609471, 6094741)
Contact Ratings | Load Voltage | Frequency | Load Type | Estimated Electrical Endurance | See Note(s) |
---|---|---|---|---|---|
AC Load |
|||||
40 A | 300 V | 50/60 Hz | Resistive | 50,000 cycles | [4][5] |
2 hp | 120–600 V | Motor | 50,000 cycles | [6][5] | |
15 A | 120 V | Tungsten | 20,000 cycles | [5][7] | |
A600 | — | — | Pilot Duty | 100,000 cycles | [5] |
DC Load |
|||||
40 A | 28 V | DC | Resistive | 100,000 cycles | [5] |
20 A | 110 V | ||||
8 A | 220 V | ||||
4 A | 325 V | ||||
2 A | 500 V |
Dimensions, in, (mm)
SPDT—Short Base (shown with optional Auxiliary Switch) |
SPST-NO-DM |
DPDT—Long Base (shown with optional Auxiliary Switch) |
DPST-NO |
Wiring Diagrams
725 Power Relays
![]() |
![]() |
Plug-In Socket Mount with full-feature cover |
Panel/DIN Mount with blade terminals |
![]() |
|
Panel/DIN Mount with screw terminals |
725—SPST-NO, 30 A; DPST-NO, 25 A
Standard Coil Voltages
Rated Contact Current | Contact Configuration | Coil Voltage | Coil Resistance (Ω) | Mounting Style | Terminal Style | Standard Part Number |
---|---|---|---|---|---|---|
25 A | DPST-NO | 24 Vac | 275 | DIN and panel | Blade terminals | |
Screw terminals | ||||||
120 Vac | 5200 | DIN and panel | Blade terminals | |||
Screw terminals | ||||||
Plug-in (socket) | Blade terminals | |||||
240 Vac | 21000 | DIN and panel | Blade terminals | |||
Screw terminals | ||||||
12 Vdc | 75 | DIN and panel | Blade terminals | |||
Screw terminals | ||||||
24 Vdc | 300 | DIN and panel | Blade terminals | |||
Screw terminals | ||||||
Plug-in (socket) | Blade terminals | |||||
30 A | SPST-NO | 24 Vac | 275 | DIN and panel | Blade terminals | |
Screw terminals | ||||||
Plug-in (socket) | Blade terminals | |||||
120 Vac | 5200 | DIN and panel | Blade terminals | |||
Screw terminals | ||||||
Plug-in (socket) | Blade terminals | |||||
240 Vac | 21000 | DIN and panel | Blade terminals | |||
Screw terminals | ||||||
12 Vdc | 75 | DIN and panel | Blade terminals | |||
Screw terminals | ||||||
24 Vdc | 300 | DIN and panel | Blade terminals |
725 Specifications
Part Number |
725AXX |
725BXX |
---|---|---|
Contact Characteristics |
||
Contact Configuration | SPST-NO | DPST-NO |
Contact Material | Silver alloy | |
Thermal (Carrying) Current | 30 A | 25 A |
Maximum Switching Voltage | 300 V | |
Current Ratings at Voltage | Resistive: 30 A at 277 Vac 50/60 Hz, 6,000 cycles |
Resistive: 25 A at 277 Vac 50/60 Hz; 25 A at 30 Vdc, 6,000 cycles |
Motor: 1.5 hp at 120 Vac 50/60 Hz; 3.0 hp at 277 Vac 50/60 Hz, 6,000 cycles |
Motor: 1.0 hp at 120 Vac 50/60 Hz; 2.0 hp at 277 Vac 50/60 Hz, 6,000 cycles |
|
Tungsten: 1.5 kW at 120 Vac 50/60 Hz, 6,000 cycles |
Tungsten: 1.3 kW at 120 Vac 50/60 Hz, 6,000 cycles |
|
Minimum Switching Requirement | 100 mA at 5 Vdc (0.5 W) | |
Coil Characteristics |
||
Coil Voltage Range[8]Standard Coil Voltages | 6–240 Vac 50/60 Hz (All AC coils are rectified); 6–110 Vdc[8]Standard Coil Voltages | |
Operating Range (% of Nominal) | 75%–110% (AC/DC) | |
Average Consumption | 2.5 VA (AC); 1.9 W (DC) | |
Insulation System Per UL 508 | Class B (130°C) |
Dimensions, in, (mm)
Plug-in Socket Mount (Blade Terminals) | C3 – DIN/Panel Mount (Blade Terminals) |
C3 – DIN/Panel Mount (Screw Terminals) |
Wiring Diagrams
389F Power Relays
389F—SPST, 30 A; DPDT, 20–25 A; SPDT, 25–30 A; 3PDT, 20 A
Standard Part Numbers
Rated Contact Current | Contact Configuration | Coil Voltage | Coil Resistance (Ω) | Cover Style | Standard Part Number |
---|---|---|---|---|---|
20 A | 3PDT | 120 Vac | 1700 | Plug-in (socket) | |
Side flange | |||||
Side flange | |||||
12 Vdc | 100 | Side flange | |||
24 Vdc | 400 | Plug-in (socket) | |||
Side flange | |||||
25 A | DPDT | 24 Vac | 72 | Plug-in (socket) | |
Side flange | |||||
120 Vac | 1700 | Plug-in (socket) | |||
Side flange | |||||
240 Vac | 7200 | Side flange | |||
12 Vdc | 100 | Plug-in (socket) | |||
Side flange | |||||
24 Vdc | 400 | Plug-in (socket) | |||
Side flange | |||||
SPDT | 24 Vac | 72 | Side flange | ||
12 Vdc | 100 | Side flange | |||
30 A | SPDT-DM-DB | 24 Vdc | 400 | Side flange | |
SPST-NO-DM | 24 Vdc | 400 | Side flange |
389F Specifications
Part Number |
389FXAX 389FXBX |
389FXCX |
389FXHX 389FHXX |
---|---|---|---|
Contact Characteristics |
|||
Contact Configuration | SPDT; DPDT | 3PDT | SPSTNODM; SPDTDMDB |
Contact Material | Silver alloy | ||
Thermal (Carrying) Current | 25 A | 20 A | 30 A |
Maximum Switching Voltage | 600 V | 300 V | 600 V |
Rated Switching Current at Voltage (Conforming to IEC AC-1 and DC-1) |
NO and NC: 25 A at 250 Vac NO and NC: 15 A at 28 Vdc |
NO and NC: 20 A at 250 Vac NO and NC: 15 A at 28 Vdc |
NO and NC: 30 A at 250 Vac NO and NC: 30 A at 28 Vdc |
Current Ratings at Voltage (Conforming to UL) |
Resistive: 25 A at 300 Vac 50/60 Hz; 5 A at 600 Vac 50/60 Hz; 13 A at 28 Vdc, 100,000 cycles Motor: 1.5 hp at 200–240 Vac 50/60 Hz; 1 hp at 120–200 and 480–600 Vac[9] 50/60 Hz, 6,000 cycles Pilot Duty: B600, 6,000 cycles FLA/LRA: 22/98 A at 120 Vac, 6,000 cycles Ballast: 20 A, 277 Vac 50/60 Hz, 6,000 cycles |
Resistive: 20 A at 150 Vac 50/60 Hz, 15 A at 250 Vac, 50/60 Hz 13 A at 28 Vdc, 50,000 cycles Motor: 0.5 hp at 120–240 Vac 50/60 Hz; 6,000 cycles Pilot Duty: B300, 6,000 cycles Ballast: 20 A, 150 Vac 50/60 Hz 6.67 A at 277 Vac 6,000 cycles |
Resistive: 30 A at 300 Vac 50/60 Hz 10 A at 600 Vac 50/60 Hz 30 A at 28 Vdc, 100,000 cycles Motor: 1.5 hp at 200–600 Vac 50/60 Hz; 1 hp at 120–200 Vac 50/60 Hz, 6,000 cycles Pilot Duty: A600, 6,000 cycles FLA/LRA: 22/98 A at 120 Vac, 6,000 cycles; 17/60 A at 300 Vac, 6,000 cycles[9] Ballast: 25 A, 277 Vac 50/60 Hz, 6,000 cycles |
Minimum Switching Requirement | 100 mA at 5 Vdc | ||
Coil Characteristics |
|||
Coil Voltage Range[8]Standard Part Numbers | 12–240 Vac 50/60 Hz; 12–24 Vdc[8]Standard Part Numbers | ||
Operating Range (% of Nominal) | 85%–110% (AC); 80%–110% (DC) | ||
Average Consumption | 2 VA (AC); 1.5 W (DC) | ||
Drop-out Voltage Threshold | 10% minimum (AC/DC) | ||
General Characteristics |
|||
Electrical Life at Rated Load[10] | 100,000 operations for IEC AC-1, 50,000 operations for IEC DC-1 | ||
Mechanical Life at No Load (Unpowered) | 5,000,000 operations | ||
Operate Time at Nominal Coil Voltage | 20 ms (maximum) | ||
Dielectric Strength | Between coil and contact: 2200 Vac; between poles: 2200 Vac; between contacts: 1600 Vac | ||
Operating Temperature Range | -30 to +55°C (-22 to +131°F) | ||
Storage Temperature Range | -30 to +85°C (-22 to +185°F) | ||
Weight (Average) | 84 g (3.0 oz) | ||
Product Certifications | UL (E164862), CE (per IEC 60947), CSA (File: 044087 Class: 3211-07), RoHS |
Dimensions, in, (mm)
Wiring Diagrams
300 Power Relays
300—DPDT, 30 A
Standard Part Numbers
Rated Contact Current | Contact Configuration | Coil Voltage | Coil Resistance (Ω) | Cover Style | Standard Part Number |
---|---|---|---|---|---|
30 A | DPDT | 24 Vac | 54 | Side flange mount | |
120 Vac | 1270 | Side flange mount | |||
240 Vac | 5400 | Side flange mount | |||
12 Vdc | 57 | Side flange mount | |||
24 Vdc | 300 | Side flange mount |
300 Specifications
Part Number | [11] |
---|---|
Contact Characteristics |
|
Contact Configuration | DPDT |
Contact Material | Silver alloy |
Thermal (Carrying) Current | 30 A |
Maximum Switching Voltage | 600 V |
Current Ratings at Voltage[11] | Resistive: 30 A at 300 Vac 50/60 Hz; 30 A at 28 Vdc; 15 A at
600 Vac 50/60 Hz Motor: 1 hp at 120 Vac 50/60 Hz; 6,000 cycles; 2 hp at 208–600 Vac 50/60 Hz[12], 6,000 cycles Pilot Duty: 5.5 A at 120 Vac 50/60 Hz, 6,000 cycles; 1.2 A at 600 Vac 50/60 Hz, 6,000 cycles |
Minimum Switching Requirement | 500 mA at 5 Vdc |
Coil Characteristics |
|
Coil Voltage Range[3] | 12–240 Vac 50/60 Hz; 12–24 Vdc |
Operating Range (% of Nominal) | 85%–110% (AC); 80%–110% (DC) |
Average Consumption | 3.4 VA (AC at 60 Hz); 2.3 W (DC) |
Drop-out Voltage Threshold | 15% (AC); 10% (DC) |
General Characteristics |
|
Electrical Life at Rated Load | 6,000 operations |
Mechanical Life at No Load (Unpowered) | 5,000,000 operations |
Operate Time at Nominal Coil Voltage | 20 ms |
Dielectric Strength | Between coil and contact: 4000 Vac; Between poles: 2500 Vac; Between contacts: 2500 Vac |
Operating Temperature Range | −40 to +55°C (−40 to +131°F) |
Storage Temperature Range | −40 to +85°C (−40 to +185°F) |
Weight (Average) | without blowout magnet: 85 g (3.0 oz) with blowout magnet: 95 g (3.4 oz) |
Product Certifications | UL (E164862), CSA (File: 044087 Class: 3211-07), RoHS |
Additional DC Ratings with Blowout Magnet
Load Voltage |
Contact Reading |
---|---|
150 Vdc | 5 A |
Dimensions, in, (mm)
Wiring Diagrams