7EN02-0406-04

Insulation alarm relay (Ins. Al. Relay)

Applicable for IFL12MC, IFL12LMC, IFL12MCT, and IFL12LMCT.

You can set the insulation alarm relay mode depending on the status of insulation.

The allowed values for this parameter are FS and Std.. The default value is FS.

When the insulation alarm relay is configured in failsafe (FS) mode:

  • The insulation alarm relay is activated, that is, energized, in the following case:

    • No insulation fault is detected.

    • Transient fault is detected.

    • Insulation fault is detected and acknowledged (if Menu > Settings > I/O Config > Ack. Al. Relay is set to ON).

      NOTE: Applicable for IFL12MC, IFL12LMC, IFL12MCT, and IFL12LMCT.

  • The insulation alarm relay is deactivated, that is, de-energized, in the following cases:

    • Insulation fault is detected.

    • On first measurement after power cycle and on toroid disconnect.

    • The product is inoperative (detected by auto-test).

    • The auxiliary power supply is lost.

    • When you trigger an auto-test with relays, the relay toggles for 3 seconds. See Test with relays (Test w. Relays) and Auto test overview for more information.

      NOTE: Applicable for IFL12MC, IFL12LMC, IFL12MCT, and IFL12LMCT.
    • Insulation fault is detected and acknowledged (if Menu > Settings > I/O Config > Ack. Al. Relay is set to OFF).

      NOTE: Applicable for IFL12MC, IFL12LMC, IFL12MCT, and IFL12LMCT.

    • When the voltage signal is unavailable

      NOTE: Applicable for IFL12MC, IFL12LMC, IFL12MCT, and IFL12LMCT.
    • Channel failure

When the insulation alarm relay is configured in standard (Std.) mode:

  • The insulation alarm relay is activated, that is, energized, in the following cases:

    • Insulation fault is detected.

    • The product is inoperative (detected by auto-test).

    • When you trigger an auto-test with relays, the relay toggles for 3 seconds. See Test with relays (Test w. Relays) and Auto test overview for more information.

      NOTE: Applicable for IFL12MC, IFL12LMC, IFL12MCT, and IFL12LMCT.
    • Insulation fault is detected and acknowledged (if Menu > Settings > I/O Config > Ack. Al. Relay is set to OFF).

      NOTE: Applicable for IFL12MC, IFL12LMC, IFL12MCT, and IFL12LMCT.

    • Toroid disconnect

    • When the voltage signal is unavailable

      NOTE: Applicable for IFL12MC, IFL12LMC, IFL12MCT, and IFL12LMCT.
    • Channel failure

  • The insulation alarm relay is deactivated, that is, de-energized, in the following cases:

    • No insulation fault is detected.

    • On first measurement after power cycle

    • When you trigger an auto-test with relays, the relay toggles for 3 seconds. See Test with relays (Test w. Relays) and Auto test overview for more information.

      NOTE: Applicable for IFL12MC, IFL12LMC, IFL12MCT, and IFL12LMCT.
    • Insulation fault is detected and acknowledged (if Menu > Settings > I/O Config > Ack. Al. Relay is set to ON).

      NOTE: Applicable for IFL12MC, IFL12LMC, IFL12MCT, and IFL12LMCT.

    • The auxiliary power supply is lost.

    • Transient fault is detected.