Device List
Description
The device list is used for defining the list of devices connected to the Ethernet port or serial port.
The list of connected devices is defined manually by adding individual devices.
Master Mode Device List Setup
For
mode, the usage of the COM port is:-
Modbus RTU devices do not have to be defined in the
, but it helps you manage your system. -
PowerLogicTM protocol (SY/MAX) devices must be defined in the
.
If you selected
mode on the page, follow the steps to set up the device list:
Step |
Action |
Result |
---|---|---|
1. |
From the menu bar, click . |
Opens the menu. |
2. |
From the menu, in the submenu, click . |
Displays the Device List page. |
3. |
Select the number of viewable devices (16 to 128) and click . |
Based on the number of viewable devices selected, the number of rows in the device list page appears. NOTE: System communication degrades as the number of
devices grow.
|
4. |
Select the . |
Selects the protocol of the connected device. |
5. |
Enter the . |
Enters the name of the device. |
6. |
In the box, type the local ID (address) of the serial slave device. |
Enters the local address of the device. |
7. |
Repeat steps from 4 to 6 until all of the devices are entered. |
Enters all of the connected devices. |
8. |
Click . |
Updates the settings. |
Device List Parameters for Master Mode
Parameters |
Description |
Settings |
---|---|---|
|
The maximum number of viewable devices displayed on the webpage. |
16, 32, 48, 64, 80, 96, 112, or 128 |
|
Selects the protocol type. |
|
|
Denotes the name of the slave device. |
– NOTE: Device
Name must be a unique value.
|
|
The local address of the device connected to the Link150 gateway. |
For serial port: 1–247 and 255 NOTE: Local ID must be a unique value.
|
Slave Mode Device List Setup
Serial port slave mode allows the serial Modbus master devices to access information from serial slave devices across a TCP/IP network.
If you selected Slave mode on the
page, follow the steps below to set up the device list:
Step |
Action |
Result |
---|---|---|
1. |
From the menu bar, click . |
Opens the menu. |
2. |
From the menu, in the submenu, click . |
Displays the Device List page. |
3. |
Select the number of viewable devices (1 to 128), and click . |
Selects the number of viewable locations that can be used to define serial slave devices connected to the Link150 gateway. |
4. |
Select the |
Selects the Modbus TCP/IP address to associate with the remote ID. |
5. |
Enter the . |
Displays the name of the device. |
6. |
In the box, enter the local ID (address) of the serial slave device. |
Enters the address of the device that the local Modbus master device will use to access the remote device. |
7. |
In the box, enter the remote ID (address) of the serial slave device. |
Enters the serial slave address of the remotely connected device. |
8. |
Repeat steps 4 to 7 until all of the devices are entered. |
Enters all of the mapping information for the Link150 gateway to communicate to the remote devices. |
9. |
Click . |
Updates the settings |
Device List Parameters for Slave Mode
Parameters |
Description |
Settings |
---|---|---|
|
The maximum number of viewable devices displayed on the webpage. |
16, 32, 48, 64, 80, 96, 112, or 128 |
|
Selects the Modbus TCP/IP address to associate with the remote ID. |
The Remote Device IPs configured in the page. |
|
Denotes the name of the slave device. |
– NOTE: Device
Name must be a unique value.
|
|
The local address of the device connected to the Link150 gateway. |
For serial port: 1–247 NOTE: Local ID must be a unique value.
|
|
The remote ID (address) of the serial slave device that is remotely connected. |
1–247 and 255 NOTE: Remote ID must be a unique value for the same connection.
|