Cross References to Modbus Registers for ComPacT NS Circuit Breakers
General Description
The following table gives cross references to the Modbus registers used by the communication modules. The registers are listed in ascending order.
Cross References Table
Address |
Register |
Module |
Description |
Page |
---|---|---|---|---|
0x0095–0x009B |
150–156 |
BCM ULP module |
Trip history |
|
0x0202 |
515 |
BCM ULP module |
Product identification |
|
0x0215–0x021E |
534–543 |
BCM ULP module |
BCM ULP module identifier |
|
0x0229–0x022A |
554–555 |
BCM ULP module |
BCM ULP module counters |
|
0x0240 |
577 |
BCM ULP module |
Firmware version |
|
0x0243–0x0244 |
580–581 |
BCM ULP module |
Counter thresholds |
|
0x0289–0x028A |
650–651 |
BCM ULP module |
Tripping cause |
|
0x0291–0x0292 |
658–659 |
BCM ULP module |
Inhibit close order |
|
0x0293 |
660 |
BCM ULP module |
Local/remote mode |
|
0x0294 |
661 |
BCM ULP module |
Circuit breaker status |
|
0x0295–0x0298 |
662–665 |
BCM ULP module |
Circuit breaker operation counters |
|
0x029D |
670 |
BCM ULP module |
Auto/Manu mode |
|
0x029E–0x02A0 |
671–673 |
BCM ULP module |
Date of last actuation of MX auxiliary |
|
0x02A1 |
674 |
BCM ULP module |
MX actuation counter |
|
0x02A2 |
675 |
BCM ULP module |
Date of last actuation of XF auxiliary |
|
0x02A5 |
678 |
BCM ULP module |
XF actuation counter |
|
0x02A6–0x02A9 |
679–682 |
BCM ULP module |
Current date of BCM ULP module |
|
0x02AB–0x02BD |
684–702 |
BCM ULP module |
Date of last event |
|
0x031F |
800 |
BCM ULP module |
Legacy dataset activation |
|
0x0325 |
806 |
BCM ULP module |
Communication parameter |
|
0x0326–0x032B |
807–812 |
BCM ULP module |
Energy Reduction Maintenance Switch (ERMS) |
|
0x032C |
813 |
BCM ULP module |
Contact wear |
|
0x03E7–0x03F6 |
1000–1015 |
MicroLogic trip unit |
Voltage and voltage unbalance (real time-measurements) |
|
0x03F7–0x0407 |
1016–1032 |
MicroLogic trip unit |
Current and current unbalance (real time-measurements) |
|
0x0409–0x0414 |
1034–1045 |
MicroLogic trip unit |
Active, reactive, and apparent power (real time-measurements) |
|
0x0415–0x041C |
1046–1053 |
MicroLogic trip unit |
Power factor and fundamental power factor (real time-measurements) |
|
0x041D |
1054 |
MicroLogic trip unit |
Frequency (real time-measurements) |
|
0x0513–0x0522 |
1300–1315 |
MicroLogic trip unit |
Voltage (minimum of real-time measurement) |
|
0x0523–0x0533 |
1316–1332 |
MicroLogic trip unit |
Current (minimum of real-time measurement) |
|
0x0535–0x0540 |
1334–1345 |
MicroLogic trip unit |
Active, reactive, and apparent power (minimum of real-time measurement) |
|
0x0541–0x0548 |
1346–1353 |
MicroLogic trip unit |
Power factor (minimum of real-time measurement) |
|
0x0549–0x054A |
1354–1355 |
MicroLogic trip unit |
Frequency (minimum of real-time measurement) |
|
0x054B–0x0551 |
1356–1362 |
MicroLogic trip unit |
Fundamental voltage (minimum of real-time measurement) |
|
0x0557–0x055B |
1368–1372 |
MicroLogic trip unit |
Fundamental current (minimum of real-time measurement) |
|
0x055F–0x0562 |
1376–1379 |
MicroLogic trip unit |
Fundamental active power (minimum of real-time measurement) |
|
0x0563–0x0566 |
1380–1383 |
MicroLogic trip unit |
Fundamental reactive power (minimum of real-time measurement) |
|
0x0567–0x056A |
1384–1387 |
MicroLogic trip unit |
Fundamental apparent power (minimum of real-time measurement) |
|
0x056B–0x056E |
1388–1391 |
MicroLogic trip unit |
Distortion power (minimum of real-time measurement) |
|
0x056–0x0578 |
1392–1401 |
MicroLogic trip unit |
Total harmonic distortion in relation to the fundamental (THD) (minimum of real-time measurement) |
|
0x0579–0x0582 |
1402–1411 |
MicroLogic trip unit |
Total harmonic distortion in relation to the RMS Value (thd) (minimum of real-time measurement) |
|
0x0583–0x0585 |
1412–1414 |
MicroLogic trip unit |
Voltage to current phase shift (minimum of real-time measurement) |
|
0x0586–0x0589 |
1415–1418 |
MicroLogic trip unit |
K-Factor (minimum of real-time measurement) |
|
0x058A–0x0593 |
1419–1428 |
MicroLogic trip unit |
Peak factor (minimum of real-time measurement) |
|
0x0598–0x059A |
1433–1435 |
MicroLogic trip unit |
Voltage-to-voltage phase shift (minimum of real-time measurement) |
|
0x063F–0x064E |
1600–1615 |
MicroLogic trip unit |
Voltage (maximum of real-time measurement) |
|
0x064F–0x065F |
1616–1632 |
MicroLogic trip unit |
Current (maximum of real-time measurement) |
|
0x0661–0x066C |
1634–1645 |
MicroLogic trip unit |
Active, reactive, and apparent power (maximum of real-time measurement) |
|
0x066D–0x0674 |
1646–1653 |
MicroLogic trip unit |
Power factor (maximum of real-time measurement) |
|
0x0675–0x0676 |
1654–1655 |
MicroLogic trip unit |
Frequency (maximum of real-time measurement) |
|
0x0677–0x067D |
1656–1662 |
MicroLogic trip unit |
Fundamental voltage (maximum of real-time measurement) |
|
0x0683–0x0687 |
1668–1672 |
MicroLogic trip unit |
Fundamental current (maximum of real-time measurement) |
|
0x068B–0x068E |
1676–1679 |
MicroLogic trip unit |
Fundamental active power (maximum of real-time measurement) |
|
0x068F–0x0692 |
1680–1683 |
MicroLogic trip unit |
Fundamental reactive power (maximum of real-time measurement) |
|
0x0693–0x0696 |
1684–1687 |
MicroLogic trip unit |
Fundamental apparent power (maximum of real-time measurement) |
|
0x0697–0x069A |
1688–1691 |
MicroLogic trip unit |
Distortion power (maximum of real-time measurement) |
|
0x069B–0x06A4 |
1692–1701 |
MicroLogic trip unit |
Total harmonic distortion in relation to the fundamental (THD) (maximum of real-time measurement) |
|
0x06A5–0x06AE |
1702–1711 |
MicroLogic trip unit |
Total harmonic distortion in relation to the RMS Value (thd) (maximum of real-time measurement) |
|
0x06AF–0x06B1 |
1712–1714 |
MicroLogic trip unit |
Voltage to current phase shift (maximum of real-time measurement) |
|
0x06B2–0x06B5 |
1715–1718 |
MicroLogic trip unit |
K-Factor (maximum of real-time measurement) |
|
0x06B6–0x06BF |
1719–1728 |
MicroLogic trip unit |
Peak factor (maximum of real-time measurement) |
|
0x06C4–0x06C6 |
1733–1735 |
MicroLogic trip unit |
Voltage-to-voltage phase shift (maximum of real-time measurement) |
|
0x07CF–0x07EA |
2000–2027 |
MicroLogic trip unit |
Energy measurements |
|
0x0897–0x08C0 |
2200–2241 |
MicroLogic trip unit |
Demand measurements |
|
0x0BB7–0x0BF7 |
3000–3064 |
MicroLogic trip unit |
Time-stamped information |
|
0x0CE6–0x0CEF |
3303–3312 |
MicroLogic trip unit |
Identification of the metering manager |
|
0x0CF1 |
3314 |
MicroLogic trip unit |
System type |
|
0x0CF3 |
3316 |
MicroLogic trip unit |
Power flow sign |
|
0x0CF4 |
3317 |
MicroLogic trip unit |
Power reactive sign |
|
0x0CF5 |
3318 |
MicroLogic trip unit |
Power factor sign |
|
0x0CFB |
3324 |
MicroLogic trip unit |
Energy accumulation mode |
|
0x0D16–0x0D1A |
3351–3355 |
MicroLogic trip unit |
Demand time |
|
0x0EE7 |
3816 |
MicroLogic trip unit |
Product identification (with metering manager) |
|
0x21FB–0x21FE |
8700–8703 |
MicroLogic trip unit |
Serial number |
|
0x2204 |
8709 |
MicroLogic trip unit |
Hardware version |
|
0x2205 |
8710 |
MicroLogic trip unit |
Firmware version |
|
0x220B |
8716 |
MicroLogic trip unit |
Product identification (with protection manager) |
|
0x2223 |
8740 |
MicroLogic trip unit |
Protection type |
|
0x2224 |
8741 |
MicroLogic trip unit |
Metering type (A, E, P) |
|
0x2225 |
8742 |
MicroLogic trip unit |
Long-time rating plug |
|
0x222D |
8750 |
MicroLogic trip unit |
Nominal current |
|
0x2230 |
8753 |
MicroLogic trip unit |
Neutral protection parameters |
|
0x2231–0x223A |
8754–8763 |
MicroLogic trip unit |
Long-time protection |
|
0x223B–0x2244 |
8764–8773 |
MicroLogic trip unit |
Short-time protection |
|
0x2245–0x224E |
8774–8783 |
MicroLogic trip unit |
Instantaneous protection |
|
0x224F–0x2258 |
8784–8793 |
MicroLogic trip unit |
Ground-fault protection |
|
0x2259–0x2262 |
8794–8803 |
MicroLogic trip unit |
Earth-leakage (Vigi) protection |
|
0x2263–0x2289 |
8804–8842 |
MicroLogic trip unit |
Protection manager measurements |
|
0x228A |
8843 |
MicroLogic trip unit |
Battery status |
|
0x229D–0x229F |
8862–8864 |
MicroLogic trip unit |
Protection status |
|
0x22A0–0x22A1 |
8865–8866 |
MicroLogic trip unit |
Time remaining until long-time tripping |
|
0x22A7 |
8872 |
MicroLogic trip unit |
Phase rotation |
|
0x2327–0x2372 |
9000–9075 |
MicroLogic trip unit |
Time-stamped information |
|
0x238B–0x2452 |
9100–9299 |
MicroLogic trip unit |
Trip history |
|
0x2583–0x258C |
9604–9613 |
MicroLogic trip unit |
Identification (of the protection manager) |
|
0x258D |
9614 |
MicroLogic trip unit |
Language |
|
0x258E |
9615 |
MicroLogic trip unit |
Nominal frequency |
|
0x258F–0x2590 |
9616–9617 |
MicroLogic trip unit |
Nominal voltage Vn |
|
0x2591 |
9618 |
MicroLogic trip unit |
Circuit breaker type |
|
0x259C–0x25A5 |
9629–9638 |
MicroLogic trip unit |
Ground-fault alarm |
|
0x25A6–0x25AF |
9639–9648 |
MicroLogic trip unit |
Earth-leakage alarm |
|
0x25B0–0x25B9 |
9649–9658 |
MicroLogic trip unit |
Current unbalance protection |
|
0x25BA–0x25C3 |
9659–9668 |
MicroLogic trip unit |
Maximum current protection on phase 1 |
|
0x25C4–0x25CD |
9669–9678 |
MicroLogic trip unit |
Maximum current protection on phase 2 |
|
0x25CE–0x25D7 |
9679–9688 |
MicroLogic trip unit |
Maximum current protection on phase 3 |
|
0x25D8–0x25E1 |
9689–9698 |
MicroLogic trip unit |
Maximum current protection on neutral |
|
0x25E2–0x25EB |
9699–9708 |
MicroLogic trip unit |
Minimum voltage protection |
|
0x25EC–0x25F5 |
9709–9718 |
MicroLogic trip unit |
Maximum voltage protection |
|
0x25F6–0x25FF |
9719–9728 |
MicroLogic trip unit |
Voltage unbalance protection |
|
0x260A–0x2613 |
9739–9748 |
MicroLogic trip unit |
Reverse power protection |
|
0x2614–0x261D |
9749–9758 |
MicroLogic trip unit |
Minimum frequency protection |
|
0x261E–0x2627 |
9759–9768 |
MicroLogic trip unit |
Maximum frequency protection |
|
0x2628–0x2631 |
9769–9778 |
MicroLogic trip unit |
Phase rotation alarm |
|
0x2632–0x263B |
9779–9788 |
MicroLogic trip unit |
Load shedding and reconnection based on current |
|
0x263C–0x2645 |
9789–9798 |
MicroLogic trip unit |
Load shedding and reconnection based on power |
|
0x2675–0x267C |
9846–9853 |
MicroLogic trip unit |
Circuit breaker characteristics |
|
0x27FF–0x2826 |
10240–10279 |
IFE interface |
IP network parameters |
|
0x2DFF–0x2E06 |
11776–11783 |
IFM interface |
Firmware version |
|
0x2DFF–0x2E06 |
11776–11783 |
IFE interface |
Firmware version |
|
0x2E07–0x2E0C |
11784–11789 |
IFM interface |
Serial number |
|
0x2E07–0x2E0C |
11784–11789 |
IFE interface |
Hardware version |
|
0x2E18–0x2E2E |
11801–11823 |
IFM interface |
IMU name |
|
0x2E18–0x2E2E |
11801–11823 |
IFE interface |
IMU name |
|
0x2E45–0x2E5B |
11846–11868 |
IFM interface |
IMU location |
|
0x2E45–0x2E5B |
11846–11868 |
IFE interface |
IMU location |
|
0x2E72 |
11891 |
IFM interface |
Modbus locking pad position |
|
0x2E72 |
11891 |
IFE interface |
Locking pad position |
|
0x2E73–0x2E7A |
11892–11899 |
IFE interface |
Current date and time |
|
0x2E7C |
11901 |
IFM interface |
Product identification |
|
0x2E7C |
11901 |
IFE interface |
Product identification |
|
0x2E7D–0x02E7F |
11902–11904 |
IFE interface |
IFE interface MAC address |
|
0x2E89–0x2E8C |
11914–11917 |
IFE interface |
Manufacturing date and time |
|
0x2E91–0x02E96 |
11922–11931 |
IFE interface |
Serial number |
|
0x2EDF–0x2F84 |
12000–12165 |
IFM interface |
Legacy dataset |
|
0x2EDF–0x2F84 |
12000–12165 |
IFE interface |
Legacy dataset |
|
0x306E |
12399 |
IFM interface |
Auto-Speed sensing state |
|
0x306F |
12400 |
IFM interface |
IFM interface Modbus address |
|
0x306F–0x3072 |
12400–12403 |
IFE interface |
IFE interface Modbus parameters |
|
0x3070 |
12401 |
IFM interface |
Modbus parity |
|
0x3071 |
12402 |
IFM interface |
Modbus Baud rate |
|
0x3072 |
12403 |
IFM interface |
Number of stop bits |
|
0x35FF–0x3668 |
13824–13929 |
IO module |
Analog input of IO 1 |
|
0x3669–0x3848 |
13930–14409 |
IO module |
Digital input of IO 1 |
|
0x3849–0x38FC |
14410–14589 |
IO module |
Digital output of IO 1 |
|
0x38FD–0x3902 |
14590–14595 |
IO module |
Hardware setting of IO 1 |
|
0x3905–0x3908 |
14598–14601 |
IO module |
Digital input and output status of IO 1 |
|
0x392F–0x3982 |
14640–14723 |
IO module |
IO 1 identification |
|
0x3989–0x39A4 |
14730–14759 |
IO module |
Alarm status of IO 1 |
|
0x3BC3–0x3BE0 |
15300–15329 |
IO module |
Cradle management of IO 1 |
|
0x3BE1–0x3BFE |
15330–15359 |
IO module |
Drawer management of IO 1 |
|
0x3C27–3C30 |
15400–15409 |
IO module |
Light control of IO 1 |
|
0x3C31–3EEC |
15410–16109 |
IO module |
Load control of IO 1 |
|
0x41B8–0x4220 |
16824–16929 |
IO module |
Analog input of IO 2 |
|
0x4221–0x4400 |
16930–17409 |
IO module |
Digital input of IO 2 |
|
0x4401–0x44B4 |
17410–17589 |
IO module |
Digital output of IO 2 |
|
0x44B5–0x44BA |
17590–17595 |
IO module |
Hardware setting of IO 2 |
|
0x44BD–0x44C0 |
17598–17601 |
IO module |
Digital input and output status of IO 2 |
|
0x44E7–0x453A |
17640–17723 |
IO module |
IO 2 identification |
|
0x4541–0x455E |
17730–17759 |
IO module |
Alarm status of IO 2 |
|
0x477B–0x4798 |
18300–18329 |
IO module |
Cradle management of IO 2 |
|
0x4799–0x47B6 |
18330–18359 |
IO module |
Drawer management of IO 2 |
|
0x749C |
29853 |
MicroLogic trip unit |
Rate of wear counter |
|
0x74B7–0x74BE |
29880–29887 |
MicroLogic trip unit |
Load profile counters |
|
0x7CFF–0x7E4E |
32000–32341 |
IFE interface |
Standard dataset |