990-5913B-001

Specifications

NOTICE
hazard of equipment damage
Refer to the UPS installation manual for detailed specifications for the UPS system.
Failure to follow these instructions can result in equipment damage.

Classic Battery Cabinet Specifications

DANGER
hazard of electric shock, explosion or arc flash
The classic battery cabinet must only be used with the Galaxy VS UPS.
Failure to follow these instructions will result in death or serious injury.
NOTE: Up to two classic battery cabinets can be connected to the Galaxy VS UPS.
Commercial reference Battery type Number of battery blocks
GVSCBC7A SWL750 48
GVSCBC7B SWL1100 44
GVSCBC7C XP12V1800 36
GVSCBC10A2 XP12V1800 48
GVSCBC10B2 XP12V3000 40

Trip Settings

Trip settings must be controlled during installation. Set the trip settings according to the relevant table below.

GVSCBC7A

UPS rating 20 kW 30 kW 40-50 kW 60 kW

Power factor

0.8

0.9

1

0.8

0.9

1

0.8

0.9

1

0.8

0.9

1

Breaker type NSX100SDC (LV438018) + TM80G (LV430080) NA
Ir setting 56 72 80 80
Im setting 250 (fixed)

GVSCBC7B

UPS rating 20-50 kW 60 kW 80 kW

Power factor

0.8

0.9

1

0.8

0.9

1

0.8

0.9

1

Breaker type NSX250SDC (LV438218) + TM200G (LV430088) NA
Ir setting 140 160 160
Im setting 530 (fixed)

GVSCBC7C

UPS rating 20-50 kW 60 kW 80 kW 100 kW

Power factor

0.8

0.9

1

0.8

0.9

1

0.8

0.9

1

0.8

0.9

1

Breaker type NSX250SDC (LV438218) + TM250G (LV430089) NA
Ir setting 175 200 250 250
Im setting 625 (fixed)

GVSCBC10A2

UPS rating 20-60 kW 80 kW 100 kW 120 kW 150 kW

Power factor

0.8

0.9

1

0.8

0.9

1

0.8

0.9

1

0.8

0.9

1

0.8

0.9

1

Breaker type NSX250SDC (LV438218) + TM250G (LV430089) NA
Ir setting 175 175 175 200 200 225 225 225 250 250 250
Im setting 625 (fixed)

GVSCBC10B2

UPS rating 20-80 kW 100 kW 120 kW 150 kW

Power factor

0.8

0.9

1

0.8

0.9

1

0.8

0.9

1

0.8

0.9

1

Breaker type NSX320S TM-DC (LV438276)
Ir setting 224 224 256 288 288 320 320
Im setting 800 (fixed)

Recommended Cable Sizes

DANGER
hazard of electric shock, explosion, or arc flash
All wiring must comply with all applicable national and/or electrical codes. The maximum allowable cable size is 95 mm2.
Failure to follow these instructions will result in death or serious injury.

Cable sizes in this manual are based on table B.52.3 (52–C2) of IEC 60364–5–52 with the following assertions:

  • 90 °C conductors

  • An ambient temperature of 30 °C

  • Use of copper conductors

  • Installation method C

Protective Earth (PE) cables are sized in accordance with table 54.3 of IEC 60364-4-54, Article 543.

If the ambient temperature is greater than 30 °C, larger conductors are to be selected in accordance with the correction factors of the IEC.

GVSCBC7A

UPS rating 20-30 kW 40-50 kW 60 kW

Power factor

0.8

0.9

1

0.8

0.9

1

0.8

0.9

1

DC+/DC- (mm2)

10 16 16 NA
DC PE (mm2) 10 10 10

GVSCBC7B

UPS rating 20-60 kW 80 kW

Power factor

0.8

0.9

1

0.8

0.9

1

DC+/DC- (mm2)

35 35 NA
DC PE (mm2) 16 16

GVSCBC7C

UPS rating 20-60 kW 80 kW 100 kW

Power factor

0.8

0.9

1

0.8

0.9

1

0.8

0.9

1

DC+/DC- (mm2)

50 70 70 NA
DC PE (mm2) 25 35 35

GVSCBC10A2

UPS rating 20-80 kW 100-120 kW 150 kW

Power factor

0.8

0.9

1

0.8

0.9

1

0.8

0.9

1

DC+/DC- (mm2)

50 70 70 NA
DC PE (mm2) 25 35 35

GVSCBC10B2

UPS rating 20-60 kW 80-100 kW 120-150 kW

Power factor

0.8

0.9

1

0.8

0.9

1

0.8

0.9

1

DC+/DC- (mm2)

50 70 95
DC PE (mm2) 25 35 50

Torque Specifications

Bolt size Torque
M4 1.7 Nm
M5 2.2 Nm
M6 5 Nm
M8 17.5 Nm
M10 30 Nm

Environment

  Operating Storage
Temperature 0 °C to 40 °C -15 °C to 40 °C
Relative humidity 0-95% non-condensing 10-80% non-condensing
Elevation 0-1000 m  
Protection class IP20
Color RAL 9003, gloss level 85%

Clearance

NOTE: Clearance dimensions are published for airflow and service access only. Consult with the local safety codes and standards for additional requirements in your local area.
NOTE: The room should be ventilated to prevent the concentration of the dihydrogen generated by the battery cabinet. Recommended minimum airflow: 2.41 m3/h.

Classic Battery Cabinet Weights and Dimensions

Commercial reference Weight kg Height mm Width mm Depth mm
GVSCBC7A 580

1900

710

845

GVSCBC7B 748

1900

710

845

GVSCBC7C 920

1900

710

845

GVSCBC10A2 1280

1900

1010

845

GVSCBC10B2 1512

1900

1010

845