DOCA0105EN-09

Protection Get Commands with Session

List of Commands

The following table lists the protection get commands with session, their corresponding command codes, and user profiles:

Command

Command code

User profile

Get long time over current protection settings Get Long Time Over Current Protection Settings

51584

No password required

Get short time over current protection settings Get Short Time Over Current Protection Settings

51585

No password required

Get instantaneous protection settings Get Instantaneous Protection Settings

51586

No password required

Get ground fault protection settings Get Ground Fault Protection Settings

51587

No password required

Get earth leakage protection settings Get Earth Leakage Protection Settings

51588

No password required

Get neutral protection settings Get Neutral Protection Settings

51589

No password required

Get Long Time Over Current Protection Settings

To get the long time over current protection settings, set the command registers in the following way:

Address

Register

Unit

Type

Range

Description

0x1F3F

8000

INT16U

51584

Requested command code

0x1F40

8001

INT16U

16

Number of parameters of the command

0x1F41

8002

INT16U

5377 (0x1501)

Destination of the command

0x1F42

8003

INT16U

0

Security type of the command

0x1F43-0x1F44

8004–8005

OCTET STRING

0

Password of the command = 0 (no password required)

0x1F45-0x1F46

8006–8007

INT32U

0–4294967294

Key for the protection get command with session

0x1F47

8008

INT16U

MSB: 0

LSB: Requested setting group

  • 0 = Current setting group

  • 1 = Setting group A

  • 2 = Setting group B

  • 3 = Setting group ERMS

The long time over current protection settings are returned to command registers in the following way:

Address

Register

Unit

Type

Range

Description

0x1F53

8020

INT16U

51584

Last command code

0x1F54

8021

INT16U

Command status:

0x1F55

8022

INT16U

56

Number of bytes returned

0x1F56-0x1F57

8023–8024

INT32U

0–4294967294

Key for the protection get command with session

0x1F58

8025

INT16U

MSB: Requested setting group

  • 0 = Current setting group

  • 1 = Setting group A

  • 2 = Setting group B

  • 3 = Setting group ERMS

LSB: Responded setting group

  • 1 = Setting group A

  • 2 = Setting group B

  • 3 = Setting group ERMS

  • 128 = Fallback setting

0x1F59

8026

INT16U

MSB: Long time over current protection mode

  • 0 = Off

  • 1 = On (tripping)

LSB: Long time over current protection supported

  • 0 = Not supported

  • 1 = Supported

0x1F5A-0x1F5D

8027–8030

DATETIME

Timestamp of last change of long time over current protection mode

0x1F5E

8031

INT16U

Timestamp quality of last change of long time over current protection mode

0x1F5F-0x1F62

8032–8035

DATETIME

Timestamp of last change of any parameter of the long time over current protection function

0x1F63

8036

INT16U

Timestamp quality of last change of any parameter of the long time over current protection function

0x1F64-0x1F65

8037–8038

FLOAT32

Long time over current protection threshold coefficient high limit

0x1F66-0x1F67

8039–8040

s

FLOAT32

Long time over current protection time delay high limit

0x1F68

8041

INT16U

1

MSB: 0

LSB: Long time over current protection curve

  • 1 = Inverse time (I2t = ON)

0x1F69-0x1F6A

8042–8043

A

FLOAT32

Long time over current protection threshold

0x1F6B-0x1F6C

8044–8045

s

FLOAT32

Long time over current protection time delay

0x1F6D-0x1F71

8046–8050

Reserved

Get Short Time Over Current Protection Settings

To get the short time over current protection settings, set the command registers in the following way:

Address

Register

Unit

Type

Range

Description

0x1F3F

8000

INT16U

51585

Requested command code

0x1F40

8001

INT16U

16

Number of parameters of the command

0x1F41

8002

INT16U

5377 (0x1501)

Destination of the command

0x1F42

8003

INT16U

0

Security type of the command

0x1F43-0x1F44

8004–8005

OCTET STRING

0

Password of the command = 0 (no password required)

0x1F45-0x1F46

8006–8007

INT32U

0–4294967294

Key for the protection get command with session

0x1F47

8008

INT16U

MSB: 0

LSB: Requested setting group

  • 0 = Current setting group

  • 1 = Setting group A

  • 2 = Setting group B

  • 3 = Setting group ERMS

The short time over current protection settings are returned to command registers in the following way:

Address

Register

Unit

Type

Range

Description

0x1F53

8020

INT16U

51585

Last command code

0x1F54

8021

INT16U

Command status:

0x1F55

8022

INT16U

56

Number of bytes returned

0x1F56-0x1F57

8023–8024

INT32U

0–4294967294

Key for the protection get command with session

0x1F58

8025

INT16U

MSB: Requested setting group

  • 0 = Current setting group

  • 1 = Setting group A

  • 2 = Setting group B

  • 3 = Setting group ERMS

LSB: Responded setting group

  • 1 = Setting group A

  • 2 = Setting group B

  • 3 = Setting group ERMS

  • 128 = Fallback setting

0x1F59

8026

INT16U

MSB: Short time over current protection mode

  • 0 = Off

  • 1 = On (tripping)

LSB: Short time over current protection supported

  • 0 = Not supported

  • 1 = Supported

0x1F5A-0x1F5D

8027–8030

DATETIME

Timestamp of last change of short time over current protection mode

0x1F5E

8031

INT16U

Timestamp quality of last change of short time over current protection mode

0x1F5F-0x1F62

8032–8035

DATETIME

Timestamp of last change of any parameter of the short time over current protection function

0x1F63

8036

INT16U

Timestamp quality of last change of any parameter of the short time over current protection function.

0x1F64-0x1F65

8037–8038

FLOAT32

Short time over current protection threshold coefficient high limit

0x1F66-0x1F67

8039–8040

s

FLOAT32

Short time over current protection time delay high limit

0x1F68

8041

INT16U

MSB: 0

LSB: Short time over current protection curve

  • 0 = Definite time (I2t = OFF)

  • 1 = Inverse time (I2t = ON)

0x1F69-0x1F6A

8042–8043

FLOAT32

Short time over current protection threshold coefficient

0x1F6B-0x1F6C

8044–8045

s

FLOAT32

Short time over current protection time delay

0x1F6D-0x1F71

8046–8050

Reserved

Get Instantaneous Protection Settings

To get the instantaneous protection settings, set the command registers in the following way:

Address

Register

Unit

Type

Range

Description

0x1F3F

8000

INT16U

51586

Requested command code

0x1F40

8001

INT16U

16

Number of parameters of the command

0x1F41

8002

INT16U

5377 (0x1501)

Destination of the command

0x1F42

8003

INT16U

0

Security type of the command

0x1F43-0x1F44

8004–8005

OCTET STRING

0

Password of the command = 0 (no password required)

0x1F45-0x1F46

8006–8007

INT32U

0–4294967294

Key for the protection get command with session

0x1F47

8008

INT16U

MSB: 0

LSB: Requested setting group

  • 0 = Current setting group

  • 1 = Setting group A

  • 2 = Setting group B

  • 3 = Setting group ERMS

The instantaneous protection settings are returned to command registers in the following way:

Address

Register

Unit

Type

Range

Description

0x1F53

8020

INT16U

51586

Last command code

0x1F54

8021

INT16U

Command status:

0x1F55

8022

INT16U

44

Number of bytes returned

0x1F56-0x1F57

8023–8024

INT32U

0–4294967294

Key for the protection get command with session

0x1F58

8025

INT16U

MSB: Requested setting group

  • 0 = Current setting group

  • 1 = Setting group A

  • 2 = Setting group B

  • 3 = Setting group ERMS

LSB: Responded setting group

  • 1 = Setting group A

  • 2 = Setting group B

  • 3 = Setting group ERMS

  • 128 = Fallback setting

0x1F59

8026

INT16U

MSB: Instantaneous over current protection mode

  • 0 = Off

  • 1 = On (tripping)

LSB: Instantaneous over current protection function supported

  • 0 = Not supported

  • 1 = Supported

0x1F5A-0x1F5D

8027–8030

DATETIME

Timestamp of last change of instantaneous over current protection mode

0x1F5E

8031

INT16U

Timestamp quality of last change of instantaneous over current protection mode

0x1F5E-0x1F62

8032–8035

DATETIME

Timestamp of last change of any parameter of the instantaneous over current protection mode

0x1F63

8036

INT16U

Timestamp quality of last change of any parameter of the instantaneous over current protection function

0x1F64-0x1F65

8037–8038

FLOAT32

Instantaneous over current protection threshold coefficient high limit

0x1F66-0x1F67

8039–8040

FLOAT32

Instantaneous over current protection threshold coefficient

0x1F68

8041

INT16U

MSB: 0

LSB: Instantaneous over current protection time delay mode:

  • 0 = Standard

  • 1 = Fast

0x1F69-0x1F6B

8042–8044

Reserved

Get Ground Fault Protection Settings

To get the ground fault protection settings, set the command registers in the following way:

Address

Register

Unit

Type

Range

Description

0x1F3F

8000

INT16U

51587

Requested command code

0x1F40

8001

INT16U

16

Number of parameters of the command

0x1F41

8002

INT16U

5377 (0x1501)

Destination of the command

0x1F42

8003

INT16U

0

Security type of the command

0x1F43-0x1F44

8004–8005

OCTET STRING

0

Password of the command = 0 (no password required)

0x1F45-0x1F46

8006–8007

INT32U

0–4294967294

Key for the protection get command with session

0x1F47

8008

INT16U

MSB: 0

LSB: Requested setting group

  • 0 = Current setting group

  • 1 = Setting group A

  • 2 = Setting group B

  • 3 = Setting group ERMS

The ground fault protection settings are returned to command registers in the following way:

Address

Register

Unit

Type

Range

Description

0x1F53

8020

INT16U

51587

Last command code

0x1F54

8021

INT16U

Command status:

0x1F55

8022

INT16U

56

Number of bytes returned

0x1F56-0x1F57

8023–8024

INT32U

0–4294967294

Key for the protection get command with session

0x1F58

8025

INT16U

MSB: Requested setting group

  • 0 = Current setting group

  • 1 = Setting group A

  • 2 = Setting group B

  • 3 = Setting group ERMS

LSB: Responded setting group

  • 1 = Setting group A

  • 2 = Setting group B

  • 3 = Setting group ERMS

  • 128 = Fallback setting

0x1F59

8026

INT16U

MSB: Ground fault protection mode

  • 0 = Off

  • 1 = On (tripping)

LSB: Ground fault protection function supported

  • 0 = Not supported

  • 1 = Supported

0x1F5A-0x1F5D

8027–8030

DATETIME

Timestamp of last change of ground fault protection mode

0x1F5E

8031

INT16U

Timestamp quality of last change of ground fault protection mode

0x1F5F-0x1F62

8032–8035

DATETIME

Timestamp of last change of any parameter of the ground fault protection function

0x1F63

8036

INT16U

Timestamp quality of last change of any parameter of the ground fault protection function

0x1F64-0x1F65

8037–8038

FLOAT32

Ground fault protection threshold coefficient high limit

0x1F66-0x1F67

8039–8040

s

FLOAT32

Ground fault protection time delay high limit

0x1F68

8041

INT16U

MSB: 0

LSB: Ground fault protection curve

  • 0 = Definite time (I2t = OFF)

  • 1 = Inverse time (I2t = ON)

0x1F69-0x1F6A

8042–8043

A

FLOAT32

Ground fault protection threshold

0x1F6B-0x1F6C

8044–8045

s

FLOAT32

Ground fault protection time delay

0x1F6D-0x1F71

8046–8050

Reserved

Get Earth Leakage Protection Settings

To get the earth leakage protection settings, set the command registers in the following way:

Address

Register

Unit

Type

Range

Description

0x1F3F

8000

INT16U

51588

Requested command code

0x1F40

8001

INT16U

16

Number of parameters of the command

0x1F41

8002

INT16U

5377 (0x1501)

Destination of the command

0x1F42

8003

INT16U

0

Security type of the command

0x1F43-0x1F44

8004–8005

OCTET STRING

0

Password of the command = 0 (no password required)

0x1F45-0x1F46

8006–8007

INT32U

0–4294967294

Key for the protection get command with session

0x1F47

8008

0xFFFF

Reserved

The earth leakage protection settings are returned to command registers in the following way:

Address

Register

Unit

Type

Range

Description

0x1F53

8020

INT16U

51588

Last command code

0x1F54

8021

INT16U

Command status:

0x1F55

8022

INT16U

52

Number of bytes returned

0x1F56-0x1F57

8023–8024

INT32U

0–4294967294

Key for the protection get command with session

0x1F58

8025

0xFFFF

Reserved

0x1F59

8026

INT16U

MSB: Earth leakage protection mode

  • 0 = Off

  • 1 = On

LSB: Earth leakage function supported

  • 0 = Not supported

  • 1 = Supported

0x1F5A-0x1F5D

8027–8030

DATETIME

Timestamp of last change of earth leakage protection mode

0x1F5E

8031

INT16U

Timestamp quality of last change of earth leakage protection mode

0x1F5F-0x1F62

8032–8035

DATETIME

Timestamp of last change of any parameter of the earth leakage protection function

0x1F63

8036

INT16U

Timestamp quality of last change of any parameter of the earth leakage protection function

0x1F64-0x1F65

8037–8038

FLOAT32

Earth leakage protection threshold coefficient high limit

0x1F66-0x1F67

8039–8040

s

FLOAT32

Earth leakage protection time delay high limit

0x1F68-0x1F69

8041–8042

A

FLOAT32

Earth leakage protection threshold

0x1F6A-0x1F6B

8043–8044

s

FLOAT32

0.06, 0.15, 0.23, 0.35, 0.80

Earth leakage protection time delay

0x1F6C-0x1F6F

8045–8048

Reserved

Get Neutral Protection Settings

To get the neutral protection settings, set the command registers in the following way:

Address

Register

Unit

Type

Range

Description

0x1F3F

8000

INT16U

51589

Requested command code

0x1F40

8001

INT16U

14

Number of parameters of the command

0x1F41

8002

INT16U

5377 (0x1501)

Destination of the command

0x1F42

8003

INT16U

0

Security type of the command

0x1F43-0x1F44

8004–8005

OCTET STRING

0

Password of the command = 0 (no password required)

0x1F45-0x1F46

8006–8007

INT32U

0–4294967294

Key for the protection get command with session

The neutral protection settings are returned to command registers in the following way:

Address

Register

Unit

Type

Range

Description

0x1F53

8020

INT16U

51589

Last command code

0x1F54

8021

INT16U

Command status:

0x1F55

8022

INT16U

32

Number of bytes returned

0x1F56-0x1F57

8023–8024

INT32U

0–4294967294

Key for the protection get command with session

0x1F58

8025

INT16U

MSB: Neutral protection mode

  • 0 = Off

  • 1 = On

LSB: Neutral protection function supported

  • 0 = Not supported

  • 1 = Supported

0x1F59-0x1F5C

8026–8029

DATETIME

Timestamp of last change of neutral protection mode

0x1F5D

8030

INT16U

Timestamp quality of last change of neutral protection mode

0x1F5E-0x1F61

8031–8034

DATETIME

Timestamp of last change of any parameter of the neutral protection function

0x1F62

8035

INT16U

Timestamp quality of last change of any parameter of the neutral protection function

0x1F63

8036

INT16U

0–3

MSB: 0

LSB: Neutral protection type

  • 0 = OFF

  • 1 = 0.5

  • 2 = 1.0

  • 3 = Oversized

0x1F64-0x1F65

8037–8038

A

FLOAT32

Long time over current protection threshold