Maintenance and Diagnostic Data
Contact Wear
Address |
Register |
RW |
Unit |
Type |
Range |
Description |
---|---|---|---|---|---|---|
0x5DC0–0x5DC1 |
24001–24002 |
R |
– |
FLOAT32 |
– |
Rate of contact wear:
|
Load profile
Address |
Register |
RW |
Unit |
Type |
Range |
Description |
---|---|---|---|---|---|---|
0x5DCE–0x5DCF |
24015–24016 |
R |
s |
INT32U |
– |
Cumulated duration when current was lower than 49% of rated current In |
0x5DD0–0x5DD1 |
24017–24018 |
R |
s |
INT32U |
– |
Cumulated duration when current was between 50% and 79% of rated current In |
0x5DD2–0x5DD3 |
24019–24020 |
R |
s |
INT32U |
– |
Cumulated duration when current was between 80% and 89% of rated current In |
0x5DD4–0x5DD5 |
24021–24022 |
R |
s |
INT32U |
– |
Cumulated duration when current was higher than 90% of rated current In |
Maintenance Data
Address |
Register |
RW |
Unit |
Type |
Range |
Bit |
Description |
---|---|---|---|---|---|---|---|
0x7E66-0x7E72 |
32359-32371 |
R |
– |
INT16U |
– |
– |
Quality of each bit of registers 32384-32396:
|
0x7E73-0x7E76 |
32372-32375 |
R |
– |
INT16U |
– |
– |
|
0x7E77-0x7E7C |
32376-32381 |
R |
– |
INT16U |
– |
– |
|
0x7E7D-0x7E7E |
32382-32383 |
R |
– |
INT16U |
– |
– |
|
0x7E7F |
32384 |
R |
– |
INT16U |
– |
0 |
Protection settings changed by display enabled |
1 |
Protection settings changed by display |
||||||
2 |
Protection settings changed by Bluetooth/USB/IFE |
||||||
3 |
Communication lost with EIFE/IFE module |
||||||
4 |
Communication lost with IO1 module |
||||||
5 |
Communication lost with IO2 module |
||||||
6 |
Configuration mismatch between IO and control unit: dual settings or inhibit close order |
||||||
7 |
Communication lost with IFM module |
||||||
8–9 |
Reserved |
||||||
10 |
Configuration mismatch between IO and control unit: optional protection inhibit |
||||||
11 |
Configuration mismatch between IO and control unit: local/remote mode |
||||||
12–15 |
Reserved |
||||||
0x7E80 |
32385 |
R |
– |
INT16U |
– |
0–2 |
Reserved |
3 |
Control unit firmware update mode |
||||||
4 |
Digital module license expires in 30 days |
||||||
5 |
Digital module license expires in 20 days |
||||||
6 |
Digital module license expires in 10 days |
||||||
7 |
Control unit firmware update unsuccessful |
||||||
8 |
Digital module license installed |
||||||
9 |
Digital module license uninstalled |
||||||
10 |
Digital module license expired |
||||||
11 |
Digital module license rejected |
||||||
12–13 |
Reserved |
||||||
14 |
Date and time set |
||||||
15 |
Remote protection settings change enabled |
||||||
0x7E81 |
32386 |
R |
– |
INT16U |
– |
0 |
Connection on USB port |
1 |
Bluetooth communication enabled |
||||||
2 |
PowerTag communication enabled |
||||||
3 |
Connection on Bluetooth port |
||||||
4–5 |
Reserved |
||||||
6 |
Schedule basic maintenance within one month |
||||||
7 |
Schedule standard maintenance within one month |
||||||
8 |
Schedule manufacturer maintenance within three months |
||||||
9 |
Protection settings still set on factory default settings 6 months after commissioning |
||||||
10 |
Remaining service life of MicroLogic below alarm threshold |
||||||
11 |
MicroLogic control unit has reached the maximum service life |
||||||
12 |
Partial Internal Current Power Supply (CPS) sensors malfunction |
||||||
13 |
Partial Internal Current Power Supply (CPS) sensors major malfunction |
||||||
14–15 |
Reserved |
||||||
0x7E82 |
32387 |
R |
– |
INT16U |
– |
0 |
Control unit in test mode |
1 |
Injection test in progress |
||||||
2 |
Test aborted by user |
||||||
3 |
ZSI test in progress |
||||||
4 |
Ig protection configured in OFF mode |
||||||
5 |
Control unit self test major malfunction 1 |
||||||
6 |
Ig function inhibited for test purpose |
||||||
7 |
Internal current sensor disconnected |
||||||
8 |
External neutral current sensor disconnected |
||||||
9 |
Earth leakage sensor disconnected |
||||||
10 |
Internal Current Power Supply (CPS) sensors malfunction |
||||||
11 |
Protection settings reset to factory values |
||||||
12 |
Last modification of protection settings has not been completely applied |
||||||
13 |
Unable to read sensor plug |
||||||
14 |
Reserved |
||||||
15 |
Invalid control unit factory configuration 1 |
||||||
0x7E83 |
32388 |
R |
– |
INT16U |
– |
0 |
Replace internal battery |
1 |
NFC invalid communication 1 |
||||||
2 |
NFC invalid communication 2 |
||||||
3 |
NFC invalid communication 3 |
||||||
4 |
Internal battery not detected |
||||||
5 |
Internal Current Power Supply (CPS) sensors malfunction. Tsd forced to 0. |
||||||
6 |
Invalid display screen or wireless communication 1 |
||||||
7 |
Reserved |
||||||
8 |
Invalid display screen or wireless communication 3 |
||||||
9 |
Invalid PowerTag communication |
||||||
10 |
Loss of Bluetooth communication |
||||||
11 |
Reserved |
||||||
12 |
Self diagnostic test - firmware |
||||||
13 |
Reserved |
||||||
14 |
Control unit alarm reset |
||||||
15 |
Reserved |
||||||
0x7E84 |
32389 |
R |
– |
INT16U |
– |
0 |
IΔn/Ig test - no trip |
1 |
IΔn/Ig test button pressed |
||||||
2 |
Protection settings not accessible 1 |
||||||
3 |
Protection settings not accessible 2 |
||||||
4 |
Protection settings not accessible 3 |
||||||
5 |
Protection settings not accessible 4 |
||||||
6 |
Reserved |
||||||
7 |
Control unit self test 1 |
||||||
8 |
Control unit self test 2 |
||||||
9 |
Control unit self test 3 |
||||||
10 |
Control unit self test 4 |
||||||
11 |
Control unit self test 5 |
||||||
12 |
Invalid measurement and optional protection 1 |
||||||
13 |
Invalid measurement and optional protection 2 |
||||||
14 |
Invalid measurement and optional protection 3 |
||||||
15 |
Invalid optional protection self test |
||||||
0x7E85 |
32390 |
R |
– |
INT16U |
– |
0 |
Critical hardware module discrepancy |
1 |
Critical firmware module discrepancy |
||||||
2 |
Non-critical hardware module discrepancy |
||||||
3 |
Non-critical firmware module discrepancy |
||||||
4 |
Address conflict between modules |
||||||
5 |
Firmware discrepancy within control unit |
||||||
6 |
Discrepancy between Display and MicroLogic |
||||||
7 |
Main voltage loss and circuit breaker is closed |
||||||
8 |
Invalid self test - MX2 shunt trip |
||||||
9 |
MX2 shunt trip not detected |
||||||
10 |
Presence of external 24 V power supply |
||||||
11 |
Events in history log have been erased |
||||||
12 |
Control unit self test major malfunction 2 |
||||||
13 |
Control unit self test major malfunction 3 |
||||||
14 |
Control unit self test major malfunction 4 |
||||||
15 |
Control unit self test major malfunction 5 |
||||||
0x7E86 |
32391 |
R |
– |
INT16U |
– |
0 |
Contact wear is above 60%. Check contacts. |
1 |
Contact wear is above 95%. Plan for replacement. |
||||||
2 |
Contacts 100% worn out. CB needs to be replaced. |
||||||
3 |
Remaining service life of circuit breaker is below the alarm threshold. |
||||||
4 |
Circuit breaker has reached the max number of operations. |
||||||
5 |
Invalid self test - MX1 shunt trip. |
||||||
6 |
MX1 shunt trip not detected. |
||||||
7 |
Invalid self test - XF shunt close. |
||||||
8 |
XF shunt close not detected. |
||||||
9 |
Invalid self test - MN undervoltage release |
||||||
10 |
MN undervoltage release not detected. |
||||||
11 |
MCH charging operation counter is above alarm threshold |
||||||
12 |
MCH has reached the max number of operations |
||||||
13 |
Voltage loss on MN undervoltage release. |
||||||
14 |
Communication loss on MN undervoltage release. |
||||||
15 |
Reserved |
||||||
0x7E87 |
32392 |
R |
– |
INT16U |
– |
0 |
Reset min/max currents |
1 |
Reset min/max voltages |
||||||
2 |
Reset min/max power |
||||||
3 |
Reset min/max frequency |
||||||
4 |
Reset min/max harmonics |
||||||
5 |
Reset min/max power factor |
||||||
6 |
Reset min/max current demand |
||||||
7 |
Reset min/max power demand |
||||||
8 |
Reset energy counters |
||||||
9–15 |
Reserved |
||||||
0x7E88–0x7EB0 |
32393–32433 |
– |
– |
– |
– |
– |
Reserved |
Diagnostic Data
Address |
Register |
RW |
Unit |
Type |
Range |
Description |
---|---|---|---|---|---|---|
0x8980 |
35201 |
R |
– |
INT16U |
– |
MSB: Overall system health state:
LSB: Reserved |
0x8981–0x8982 |
35202–35203 |
R |
– |
FLOAT32 |
– |
Breaker remaining service life ratio:
|
0x8983–0x8984 |
35204–35205 |
R |
– |
INT32U |
– |
Total number of operations (opening operation counter) |
0x8985–0x8986 |
35206–35207 |
R |
– |
INT32U |
– |
Number of total trips in operation |