Power and Energy Meters — Selection
Power and Energy Meter Selection
Features [1] | PM5600 | PM5500 | PM5340 | PM5330 | PM5110 | PM2x30 | PM2x20 | PM2x10 | EM3500 | PM3000 | iEM3000 |
---|---|---|---|---|---|---|---|---|---|---|---|
Inputs, outputs and control power |
|||||||||||
3-phase / single-phase | • / • | • / • | • / • | • / • | • / • | • / • | • / • | • / • | • / • | • / • | • / • |
Digital in and out / analog in and out | 6 / 0 | 6 / 0 | 4 / 0 | 4 / 0 | 1 / 0 | option | option | option | 2 or 3 / 0 | up to 2/2 | up to 1/1 |
Power supply options | AC/DC | AC/DC/LVDC | AC/DC | AC/DC | AC/DC | AC/DC | AC/DC | AC/DC | AC/DC | AC/DC | AC |
Power and energy measurements |
|||||||||||
Voltage, current, frequency, power factor | • | • | • | • | • | • | • | • | • | • | • |
Power / Demand | • / • | • / • | • / • | • / • | • / • | • / • | • / • | • / • | • / • | • / • | • / - |
Energy / time-of-use (energy per shift) | • / • | • / • | • / • | • / • | • / - | • / • | • / • | • / • | - / - | • / • | • / • |
IEC / ANSI energy accuracy class (% of reading) | 0.2 | 0.2 | 0.5 | 0.5 | 0.5 | 0.5 | 1.0 | 1.0 | 0.2 | 0.5 | 0.5 |
Loss compensation | - | - | - | - | - | - | - | - | - | - | - |
Power quality analysis |
|||||||||||
EN50160 compliance reporting / IEC 61000-4-30 Class A or S | - / - | - / - | - / - | - / - | - / - | - / - | - / - | - / - | - / - | - / - | - / - |
Flicker measurement | - | - | - | - | - | - | - | - | - | - | - |
Transient detection duration | - | - | - | - | - | - | - | - | - | - | - |
Sag and swell monitoring / disturbance direction detection | • / - | - / - | - / - | - / - | - / - | - / - | - / - | - / - | - / - | - / - | - / - |
Harmonic distortion: total/ individual / inter | • / • / - | • / • / - | • / • / - | • / • / - | • / • / - | • / • / - | • / • / - | • / - / - | - / - / - | • / - / - | - / - / - |
Waveform capture | yes | - | - | - | - | - | - | - | - | - | - |
On-board data and event logging |
|||||||||||
Trending / forecasting / billing | - / - / - | - / - / - | - / - / - | - / - / - | - / - / - | - / - / - | - / - / - | - / - / - | - / - / - | - / - / - | - / - / - |
Minimum and maximum | • | • | • | • | • | • | - | - | - | • | - |
Events and alarms with timestamps | • | • | • | • | - | • | - | - | - | • | - |
Timestamp resolution (seconds) | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | - |
Time sync: Network / GPS / IRIG-B / DCF77-B | - / - / - / - | - / - / - / - | - / - / - / - | - / - / - / - | - / - / - / - | - / - / - / - | - / - / - / - | - / - / - / - | - / - / - / - | - / - / - / - | - / - / - / - |
Setpoints, alarms and control |
|||||||||||
Log alarm conditions / call out on alarm | • / • | • / • | • / • | • / - | • / - | • / - | • / - | • / - | - / - | • / - | - / - |
Trigger data logging / waveform capture | - / - | - / - | - / - | - / - | - / - | - / - | - / - | - / - | - / - | - / - | - / - |
Trigger relay or digital output | • | • | • | • | - | • | • | • | - | • | • |
Special features |
|||||||||||
Custom programming | - | - | - | - | - | - | - | - | - | - | - |
Downloadable firmware | • | • | • | • | • | • | • | • | • | • | • |
Communications |
|||||||||||
Ports: | |||||||||||
Ethernet: Copper / Fiber | 2/ - | 2/ - | 1 / - | - / - | - / - | - / - | - / - | - / - | - / - | - / - | - / - |
Ethernet-to-serial gateway | • | • | - | - | - | - | - | - | - | - | - |
Telephone modem | - | - | - | - | - | - | - | - | - | - | - |
Modem-to-serial gateway | - | - | - | - | - | - | - | - | - | - | - |
Infrared port | - | - | - | - | - | - | - | - | - | - | - |
RS485/RS232 | • / - | • / - | - / - | • / - | • / - | • / - | • / - | - / - | • / - | • / - | • / - |
Misc: Web server / Email / SNMP / XML | • / • / • / - | • / • / • / - | - / - / - / - | - / - / - / - | - / - / - / - | - / - / - / - | - / - / - / - | - / - / - / - | - / - / - / - | - / - / - / - | - / - / - / - |
Protocols: Modbus / DNP / MV-90 / DLMS | • / - / - / - | • / - / - / - | • / - / - / - | • / - / - / - | • / - / - / - | • / - / - / - | • / - / - / - | - / - / - / - | • / - / - / - | • / - / - / - | • / - / - / - |
Protocols: IEC61850 / Jbus / M-Bus / LON / BACnet | - / - / - / - / • | - / - / - / - / • | - / - / - / - / • | - / - / - / - / - | - / - / - / - / - | - / - / - / - / - | - / - / - / - / - | - / - / - / - / - | - / - / - / - / • | - / - / - / - / - | - / - / • / • / • |