TeSys GV5 / GV6 Devices
Description
TeSys GV5 / GV6 devices offer current ratings from 150 to 500 A, for AC power systems up to 690 Vac.
TeSys GV5 / GV6 devices are available in the following frame sizes:
-
TeSys GV5 for current ratings from 150 to 220 A
-
TeSys GV6 for current ratings from 320 to 500 A
TeSys GV5 / GV6 devices have the following features:
-
Direct rotary handle
-
3-pole devices
-
5, 10 and 20 trip classes
-
The following accessories are optional and installable on site:
-
Voltage trip releases
-
Auxiliary contacts
-
Insulation accessories
-
Device Identification
The commercial reference of each device provides information about:
-
The size of the device
-
The type of protection the device provides
-
The current rating of the device
-
The breaking capacity of the device
For example, the commercial reference of the GV5P 220H device contains the following information:
-
GV5: The device is a TeSys GV5 device.
-
P: The device offers protection against overloads and short-circuits.
-
220: The device has a current rating of 220 A.
-
H: The breaking capacity of the device is 70 kA at 415 Vac.
Breaking Capacity
The following table shows the breaking capacity (Ics = Icu) in kA rms for TeSys GV5 / GV6 devices:
AC power systems |
TeSys GV5P 150F |
TeSys GV5P 150H |
TeSys GV5P 220F |
TeSys GV5P 220H |
TeSys GV6P 320F |
TeSys GV6P 320H |
TeSys GV6P 500F |
TeSys GV6P 500H |
---|---|---|---|---|---|---|---|---|
230 Vac |
85 kA |
100 kA |
85 kA |
100 kA |
40 kA |
100 kA |
40 kA |
100 kA |
400/415 Vac |
36 kA |
70 kA |
36 kA |
70 kA |
36 kA |
70 kA |
36 kA |
70 kA |
440 Vac |
35 kA |
65 kA |
35 kA |
65 kA |
30 kA |
65 kA |
30 kA |
65 kA |
500 Vac |
30 kA |
50 kA |
30 kA |
50 kA |
25 kA |
50 kA |
25 kA |
50 kA |
660/690 Vac |
8 kA |
10 kA |
8 kA |
10 kA |
10 kA |
10 kA |
10 kA |
10 kA |
Standard Compliance
TeSys GV5 / GV6 devices are compliant with the following standards:
-
IEC/EN 60947-2 and IEC/EN 60947-4-1 for motor protection circuit breakers
-
UL 60947-4-1 for motor protection circuit breakers
-