Protection for Motor-Feeders
Introduction
TeSys GV5 / GV6 devices:
-
Provide protection for direct-on-line motor-feeders and star-delta motor starters (direct-on-line starting is the most widely used type of motor-feeder).
-
Integrate the basic protections (overload, short-circuit, and phase unbalance) for the motor-feeder.
-
Allow protection and coordination of the motor-feeder components that comply with the requirements of IEC/EN 60947-2 and IEC/EN 60947-4-1 standards.
-
Are used to create motor-feeders with two devices.
Characteristics Defined by IEC/EN 60947-4-1 Standard
A motor-feeder must satisfy the general rules of IEC/EN 60947-4-1 standard, in particular the rules concerning the protection of contactors and motor-feeders.
In the matter of protection, this standard defines:
-
Coordination of motor-feeder protections
-
Trip class setting value
-
Insulation coordination
Coordination According to IEC/EN 60947-4-1 Standard
Two types of coordination are allowed: type 1 coordination or type 2 coordination.
-
In type 1 coordination, deterioration of the contactor and relay is accepted under the two following conditions:
-
The contactor or starter does not represent a danger to people or installations.
-
The starter can operate correctly when parts have been repaired or replaced.
-
-
In type 2 coordination, some slight welding of the contactor or starter contacts is allowed if, following type 2 coordination tests:
-
They are easy to separate.
-
The control and protection switchgear functions then work without the need for repair.
-
To ensure type 2 coordination, IEC/EN 60947-4-1 standard lays down three Id fault current tests intended to check that the equipment behaves correctly in overload and short-circuit conditions.