Motor Operating States
Introduction
TeSys GV5 / GV6 devices consider the application to be operating as soon as the 10% of Ir pickup is crossed in a positive direction by the motor current.
Two operating states are considered:
-
Startup state
-
Steady state
Startup State
The application is considered to be in startup state according to the following criteria:
-
Start: As soon as 10% of Ir pickup is crossed in a positive direction by the motor current.
-
End: As soon as Id pickup equals 1.5 x Ir and the td time delay equals 10 s (non-adjustable parameters).
Exceeding the 10 s time delay does not result in tripping.
Steady State
The application is considered to be in steady state according to the following criteria:
-
Start: As soon as startup ends.
-
End: As soon as the 10% of Ir pickup is crossed in a negative direction by the motor current.
Operating Diagram
The following diagrams show the two cases of transition between startup and steady state:
A TeSys GV5 / GV6 devices status (green: ON position) B Contactor status (green: ON position) C Current in the motor D Operating state: startup state (green: active state) E Operating state: steady state (green: active state) |