990-6161A-001

Connect the Signal Cables

  1. Assign an ID to each modular battery cabinet with the switch below the battery breaker. Set the IDs according to numbering on the installation overview images in Installation Procedure for UPS with Internal Batteries or Installation Procedure for UPS for External Batteries.

    Front View of the Modular Battery Cabinet

  2. Connect the provided signal cables between all the modular battery cabinets:
    1. Connect the provided signal cable 0W12908 from J8008 to J8007 on board 640-7572 between the modular battery cabinets.
    2. Connect the provided signal cable 0W76627 from J8011 to J8014 on board 640-7572 between the modular battery cabinets.
    3. Mount a termination plug (T) in the unused J8007 connector in the last modular battery cabinet.
    Modular Battery Cabinet 3 Modular Battery Cabinet 2 Modular Battery Cabinet 1

    Front View of Two Modular Battery Cabinets

  3. For installation with adjacent UPS:
    1. Connect the signal cable 0W12908 to J8008 on board 640-7572 in modular battery cabinet 1, route through the right side, and follow the UPS installation manual to connect the signal cables in the UPS.
    2. Connect the provided signal cable 0W76627 to J8011 on board 640-7572 in modular battery cabinet 1, route through the right side, and follow the UPS installation manual to connect the signal cables in the UPS.
  4. For installation with remote UPS:
    1. Connect signal cables to J8008 on board 640-7572 in modular battery cabinet 1, route up along the right side and out through the top of the modular battery cabinet, and follow the UPS installation manual to connect the signal cables in the UPS.
      NOTE: The provided signal cable 0W12908 is not long enough for a remote UPS installation. A 5 meter signal cable (0J-0W4527) or 50 meter signal cable (0J-0W3758) can be ordered from Schneider Electric. For other signal cable lengths, please contact Schneider Electric. This signal cable is classified as Class 2/SELV.
    2. Connect signal cables to J8011 on board 640-7572 in modular battery cabinet 1, route up along the left side and out through the top of the modular battery cabinet, and follow the UPS installation manual to connect the signal cables in the UPS.
      NOTE: The provided signal cable 0W76627 is not long enough for a remote UPS installation. Reuse the connectors from the provided signal cable 0W76627 to make new signal cables in the correct length. This signal cable is classified as non-Class 2/non-SELV.

      Signal Cable for UPS with Internal Batteries

      Signal Cable for UPS for External Batteries

    Front View of Modular Battery Cabinet 1 for Installation with Remote UPS

QR Code is a registered trademark of DENSO WAVE INCORPORATED in Japan and other countries.