Specifications
Input Specifications
UPS rating | 10 kW | 20 kW |
---|---|---|
Voltage (V) | 200/208/220 | 480 |
Connections |
4-wire (L1, L2, L3, N, PE) WYE (single mains) |
4-wire (L1, L2, L3, N, PE) WYE (single mains) |
Input voltage range (V) |
200 V: 170-230 |
408-552 |
Frequency range (Hz) |
40-70 |
|
Nominal input current (A) |
31/30/28 |
25 |
Maximum input current (A) |
37/36/34 |
30 |
Input current limitation (A) |
39/37/35 |
31 |
Input power factor |
0.99 for load greater than 50% |
|
Total harmonic distortion (THDI) |
<3% at full linear load (symmetrical) |
|
Maximum short circuit rating |
65 kA RMS |
|
Protection |
Built-in backfeed protection and fuses |
|
Ramp-in |
Programmable and adaptive 1-40 seconds |
Bypass Specifications
UPS rating | 10 kW | 20 kW |
---|---|---|
Voltage (V) | 200/208/220 | 480 |
Connections |
4-wire (L1, L2, L3, N, PE) WYE |
4-wire (L1, L2, L3, N, PE) WYE |
Bypass voltage range (V) |
200 V: 180-220 |
432-528 |
Frequency range (Hz) |
50/60 ± 1, 50/60 ± 3, 50/60 ± 10 (user selectable) |
|
Nominal bypass current (A) |
29/28/27 |
24 |
Nominal neutral current (A) |
50/48/45 |
42 |
Maximum short circuit rating* |
65 kA RMS |
|
Protection |
Built-in backfeed protection and fuses |
Output Specifications
UPS rating | 10 kW | 20 kW |
---|---|---|
Voltage (V) | 200/208/220 | 480 |
Connections* |
4-wire (L1, L2, L3, N, PE) |
4-wire (L1, L2, L3, N, PE) |
Output voltage regulation |
Symmetrical load ± 1% |
|
Overload capacity |
150% for 1 minute (in normal operation) |
|
Dynamic load response |
± 5% after 2 milliseconds |
|
Output power factor | 1 | |
Nominal output current (A) |
29/28/26 |
24 |
Frequency regulation (Hz) |
50/60 Hz bypass synchronized – 50/60 Hz ± 0.1% free-running |
|
Synchronized slew rate (Hz/sec) |
Programmable to 0.25, 0.5, 1, 2, 4, 6 |
|
Total harmonic distortion (THDU) | <2% for linear load <5% for non-linear load |
<1% for linear load <3% for non-linear load |
Load crest factor |
2.5 |
|
Load power factor |
From 0.7 leading to 0.7 lagging without any derating |
Battery Specifications
All values are based on 40 battery blocks.
UPS rating | 10 kW | 20 kW |
---|---|---|
Voltage (V) | 200/208/220 | 480 |
Charging power in % of output power at 0-40% load |
80% |
|
Charging power in % of output power at 100% load |
20% |
|
Maximum charging power (at 0-40% load) (kW) |
8 |
16 |
Maximum charging power (at 100% load) (kW) |
2 |
4 |
Nominal battery voltage (VDC) |
480 |
|
Nominal float voltage (VDC) |
545 |
|
Maximum boost voltage (VDC) |
571 |
|
Temperature compensation (per cell) |
-3.3mV/°C, for T ≥ 25 °C – 0mV/°C, for T < 25 °C |
|
End of discharge voltage (full load) (VDC) |
384 |
|
Battery current at full load and nominal battery voltage (A) |
22 |
43 |
Battery current at full load and minimum battery voltage (A) |
27 |
54 |
Ripple current |
< 5% C20 (5 minute runtime) |
|
Battery test |
Manual/automatic (selectable) |
|
Maximum short circuit rating |
10 kA |
Recommended Upstream Protection
![]() |
---|
hazard of fire
Failure to follow these instructions can result in injury or equipment damage.
|
UPS rating | 10 kW | 20 kW | ||
---|---|---|---|---|
Voltage (V) | 200/208/220 | 480 | ||
Input | Bypass | Input | Bypass | |
Breaker type |
HJF36100U31X |
HJF36100U31X |
||
Ir setting |
50 |
40 |
40 |
35 |
Tr at 6 Ir setting |
0.5 |
0.5 |
||
li (x In) setting |
1.5 |
1.5 |
Recommended Cable Sizes for 200/208/220/480 V
![]() |
---|
hazard of electric shock, explosion, or arc flash
All wiring must comply with all applicable national and/or electrical codes. The maximum
allowable cable size is 4 AWG.
Failure to follow these instructions will result in death or serious injury.
|
Cable sizes in this manual are based on Table 310.15 (B)(16) of the National Electrical Code (NEC) with the following assertions:
-
90 °C (194 °F) conductors (75 °C (167 °F) termination)
-
An ambient temperature of 30 °C (86 °F)
-
Use of copper conductors
Equipment grounding conductors (PE in this manual) are sized in accordance with NEC Article 250.122 and Table 250.122.
If the ambient temperature is greater than 30 °C (86 °F), larger conductors are to be selected in accordance with the correction factors of the NEC.
UPS rating | 10 kW | 20 kW |
---|---|---|
Voltage (V) |
200/208/220 |
480 |
Input phases (AWG/kcmil) |
8 |
8 |
Input PE (AWG/kcmil) |
8 |
10 |
Bypass/output phases (AWG/kcmil) |
8 |
10 |
Bypass PE/output PE (AWG/kcmil) |
8 |
10 |
Neutral (AWG/kcmil)* |
6 |
6 |
Recommended Bolt and Lug Sizes
NOTICE |
---|
risk of equipment damage
Use only UL approved compression cable lugs.
Failure to follow these instructions can result in equipment damage.
|
Narrow One Hole Lugs for PE Cables
Narrow Insulated Ferrule for Phase Cables and N Cables
Bolt size | Insulated ferrule type | Crimping tool |
---|---|---|
10 AWG | FSD82-18-C | CT-1002, CT-1003, CT-1123 |
8 AWG | FSD83-18-C | CT-1003, CT-1004, CT-1104, CT-1123 |
6 AWG | FSD84-18-C | CT-1003, CT-1004, CT-1104 |
4 AWG | FSD85-18-L | CT-1005 |
Torque Specifications
Bolt size | Torque |
---|---|
M4 | 1.7 Nm (1.25 lb-ft / 15 lb-in) |
M5 | 2.2 Nm (1.62 lb-ft / 19.5 lb-in) |
M6 | 5 Nm (3.69 lb-ft / 44.3 lb-in) |
M8 | 17.5 Nm (12.91 lb-ft / 154.9 lb-in) |
M10 | 30 Nm (22 lb-ft / 194.7 lb-in) |
Environment
Operating | Storage | |
---|---|---|
Temperature |
0 °C to 40 °C (32 °F to 104 °F) |
-15 °C to 40 °C (5 °F to 104 °F) for systems with batteries. |
Relative humidity |
0 - 95% non-condensing |
10 - 80% non-condensing |
Elevation |
Designed for operation in 0-3000 m (0-10000 feet) elevation. |
|
Audible noise one meter (three feet) from unit |
480 V 20 kW and 208 V 10 kW: 49 dB at 70% load, 55 dB at 100% load |
|
Protection class |
IP20 |
|
Color |
RAL 9003, gloss level 85% |
Heat Dissipation
480 V UPS in BTU/hr
20 kW UPS | Normal operation | ECO mode | ECOnversion | Battery operation |
---|---|---|---|---|
25% load |
943 |
531 |
587 |
1009 |
50% load |
1305 |
587 |
654 |
1356 |
75% load |
1704 |
674 |
742 |
1903 |
100% load |
2225 |
794 |
841 |
2650 |
208 V UPS in BTU/hr
10 kW UPS | Normal operation | ECO mode | ||||
---|---|---|---|---|---|---|
Voltage (V) | 200 | 208 | 220 | 200 | 208 | 220 |
25% load |
735 |
609 |
701 |
473 |
466 |
465 |
50% load |
1137 |
965 |
1045 |
555 |
548 |
546 |
75% load |
1706 |
1438 |
1518 |
659 |
651 |
630 |
100% load |
2494 |
2031 |
2128 |
796 |
772 |
746 |
10 kW UPS | ECOnversion | Battery operation | ||||
---|---|---|---|---|---|---|
Voltage (V) | 200 | 208 | 220 | 200 | 208 | 220 |
25% load |
473 |
460 |
459 |
1032 |
902 |
1000 |
50% load |
556 |
552 |
538 |
1248 |
1167 |
1184 |
75% load |
659 |
641 |
629 |
1591 |
1511 |
1476 |
100% load |
787 |
763 |
731 |
2062 |
1935 |
1878 |