Setting up the digital input for external excitation

Follow the directions below to change the digital inputs’ setting to use an external power supply.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
  • Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E in the USA, CSA Z462 or applicable local standards.
  • Turn off all power supplying this device and the equipment in which it is installed before working on the device or equipment.
  • Always use a properly rated voltage sensing device to confirm that all power is off.
  • Components inside the meter are extremely sensitive to electrostatic discharge. Use anti-static precautions when working inside the unit.
Failure to follow these instructions will result in death or serious injury.
  1. Disconnect and lock out power. Use a properly rated voltage sensing device to confirm power is off.
  2. Remove any anti-tamper sealing devices located at the meter’s base.
  3. Rotate plastic cover ¼ turn counter-clockwise and pull cover off. The excitation pins and jumpers are in a recessed cavity on the bottom left of the meter.
  4. Remove both jumpers and place one jumper on pins 2 and 3 of the four-pin header. Keep the second jumper for future use.
  5. Replace the plastic cover and any anti-tamper sealing.

    Onboard digital input internal excitation is now disabled; an external supply can be used for external contacts. See the specifications table, “Onboard I/O” for details.