Diagnostic codes
Diagnostic code |
PM3200 PM3250 |
PM3210 PM3255 |
Description |
Possible solution |
---|---|---|---|---|
— |
√ |
√ |
LCD display is not visible. |
Check and adjust LCD contrast/backlight settings. |
— |
√ |
√ |
Push buttons do not function. |
Restart the meter by power off and power on again. |
101, 102 |
√ |
√ |
Metering stops due to internal error. Total energy consumption is displayed. |
Enter the Configuration mode and implement Reset Config. |
201 |
√ |
√ |
Metering continues. Mismatch between frequency settings and frequency measurements. |
Correct frequency settings according to the nominal frequency of the network. |
202 |
√ |
√ |
Metering continues. Mismatch between wiring settings and wiring inputs. |
Correct wiring settings according to wiring inputs. |
203 |
√ |
√ |
Metering continues. Phase sequence reverses. |
Check wire connections or correct wiring settings. |
205 |
√ |
√ |
Metering continues. Date and time have been reset due to loss of power. |
Set Date and time. |
206 |
— |
√ |
Metering continues. Pulse is missing due to overload on energy pulse output. |
Check the energy pulse output settings and correct if needed. |
207 |
√ |
√ |
Metering continues. Abnormal internal clock function. |
Restart the meter by power off and power on again. |