Auto test overview
The device’s auto test function tests:
-
The product: indicator lights, internal electronics.
-
The measuring chain, the insulation alarm relay and the preventive insulation alarm relay.
The auto-test is triggered:
-
Manually at any time by pressing the T contextual menu button on one of the system insulation monitoring screens.
-
Automatically:
Whenever the device starts up (power-up or reset)
Every 5 hours (except when the device has detected an insulation fault, regardless of whether the alarm is active, has been acknowledged, or is transient).
When injection is activated again after exiting the inhibited injection state.