Menu - Services
Services Menu
The Services menu contains the following sub-menus:
|
Level 1 |
Level 2 |
Level 3 |
|---|---|---|
|
Menu |
Services |
Date-Time setting |
|
HMI setting |
||
|
Network |
||
|
History |
||
|
Config |
||
|
Settings |
||
|
Product ID |
||
|
Self-test |
||
|
Clear |
The Services sub-menus are described below.
Date-Time Setting
The Date-Time setting sub-menu contains the following editable parameters:
|
Level 3 |
Level 4 |
Parameter Name |
|---|---|---|
|
Date-Time setting |
Year |
Date and time setting |
|
Month |
||
|
Day |
||
|
Hour |
||
|
Minutes |
||
|
Seconds |
HMI Setting
The HMI Setting sub-menu contains the following editable parameters:
|
Level 3 |
Level 4 |
Parameter Name |
|---|---|---|
|
HMI setting |
Language |
HMI language setting |
|
Contrast |
HMI display contrast setting |
|
|
Brightness |
HMI display brightness setting |
|
|
Run LED color |
HMI motor status LED color |
|
|
Degree unit |
Motor temperature sensor display degree CF |
|
Level 3 |
Level 4 |
Level 5 |
Parameter Name |
||
|---|---|---|---|---|---|
|
HMI setting (continued) |
Quick View |
Motor status |
HMI display motor status enable |
||
|
Date |
HMI display date enable |
||||
|
Time |
HMI display time enable |
||||
|
Last start |
HMI display start statistics enable |
||||
|
Thermal capacity |
HMI display thermal capacity level enable |
||||
|
Remain th cap |
HMI display thermal capacity remaining enable |
||||
|
Time to trip |
HMI display time to trip enable |
||||
|
Average voltage |
HMI display average voltage enable |
||||
|
L1-L2 voltage |
HMI display L1-L2 voltage enable |
||||
|
L2-L3 voltage |
HMI display L2-L3 voltage enable |
||||
|
L3-L1 voltage |
HMI display L3-L1 voltage enable |
||||
|
Voltage imbalance |
HMI display voltage phase imbalance enable |
||||
|
Average current |
HMI display average current enable |
||||
|
L1 current |
HMI display L1 current enable |
||||
|
L2 current |
HMI display L2 current enable |
||||
|
L3 current |
HMI display L3 current enable |
||||
|
Avg current in% |
HMI display average current ratio enable |
||||
|
L1 current in% |
HMI display L1 current ratio enable |
||||
|
L2 current in% |
HMI display L2 current ratio enable |
||||
|
L3 current in% |
HMI display L3 current ratio enable |
||||
|
Current imbalance |
HMI display current phase imbalance enable |
||||
|
Ground current |
HMI display ground current enable |
||||
|
Active power |
HMI Display active power enable |
||||
|
Reactive power |
HMI display reactive power enable |
||||
|
Power Wh |
HMI Display power consumption enable |
||||
|
Power factor |
HMI display power factor enable |
||||
|
Frequency |
HMI display frequency enable |
||||
|
Temp sensor |
HMI motor temperature sensor enable |
||||
|
Operating time |
HMI display operating time enable |
||||
|
Starts per hour |
HMI display starts per hour enable |
||||
|
I/O status |
HMI display I/O status enable |
||||
|
Control mode |
HMI display control mode enable |
||||
|
Level 3 |
Level 4 |
Level 5 |
Level 6 |
Parameter Name |
|
|---|---|---|---|---|---|
|
HMI Setting (continued) |
Password |
Change password
|
HMI keypad password |
||
|
HMI comm |
Baud rate |
HMI port baud rate setting |
|||
|
Parity |
HMI port parity setting |
||||
|
Comm Loss |
Trip enable |
HMI port trip enable |
|||
|
Alarm enable |
HMI port alarm enable |
||||
Network (Modbus, Profibus, CANopen, DeviceNet)
The Network sub-menu contains the following parameters:
|
Level 3 |
Level 4 |
Level 5 |
Level 6 |
Parameter Name |
|---|---|---|---|---|
|
Network |
Network settings |
Address |
Network port address setting |
|
|
Baud rate(1) |
Network port baud rate setting |
|||
|
Parity(2) |
Network port parity setting |
|||
|
Endian |
Network port endian setting |
|||
|
Comm loss |
Trip enable |
Network port trip enable |
||
|
Alarm enable |
Network port alarm enable |
|||
|
Network timeout(1) |
Network port comm loss timeout |
|||
|
Device Status |
Baud rate(1) |
Network port baud rate |
||
|
Parity(2) |
Network port parity |
|||
|
Address |
Network port address setting |
|||
|
(1) Except for LTM R Profibus (2) LTM R Modbus only |
||||
Network (Ethernet TCP/IP)
The Network sub-menu contains the following parameters:
|
Level 3 |
Level 4 |
Level 5 |
Level 6 |
Parameter Name |
|---|---|---|---|---|
|
Network |
Network settings |
IP address |
Ethernet IP address setting |
|
|
Subnet mask |
Ethernet subnet mask setting |
|||
|
Gateway |
Ethernet gateway address setting |
|||
|
Endian |
Network port endian setting |
|||
|
Frame type |
Network port frame type setting |
|||
|
Network protocol |
Communication protocol status |
|||
|
FDR |
FDR disable |
Network port FDR disable |
||
|
Auto backup |
Network port FDR auto backup enable |
|||
|
Backup period |
Network port FDR auto backup period setting |
|||
|
Comm loss |
Primary IP address |
Ethernet primary IP address setting |
||
|
Trip enable |
Network port trip enable |
|||
|
Alarm enable |
Network port alarm enable |
|||
|
Network timeout |
Network port comm loss timeout |
|||
|
Device Status |
Address |
Device name |
Ethernet device name |
|
|
MAC address |
Ethernet MAC address |
|||
|
IP address |
Ethernet IP address |
|||
|
Subnet mask |
Ethernet subnet mask |
|||
|
Gateway |
Ethernet gateway address |
|||
|
FDR status |
Network port FDR status |
|||
History
The History sub-menu contains the following sub-menus:
|
Level 1 |
Level 2 |
Level 3 |
Level 4 |
|---|---|---|---|
|
Menu |
Services |
History |
5 trips history |
|
Counters |
|||
|
Motor history |
|||
|
LTMR History |
The 5 trips history sub-menu contains the following sub-menus:
|
Level 4 |
Level 5 |
|---|---|
|
5 trips history |
Trip n-0 |
|
Trip n-1 |
|
|
Trip n-2 |
|
|
Trip n-3 |
|
|
Trip n-4 |
The Trip n-0 sub-menu contains the following read only parameters:
|
Level 3 |
Level 4 |
Level 5 |
Level 6 |
Parameter Name |
|---|---|---|---|---|
|
History |
5 trips history |
Trip n-0 |
Trip name |
Trip code n-0 |
|
Date |
Date and time n-0 |
|||
|
Time |
||||
|
FLC setting in % |
Motor full load current ratio n-0 |
|||
|
FLCmax |
Full load current max n-0 |
|||
|
Thermal capacity |
Thermal capacity level n-0 |
|||
|
Temp sensor |
Motor temperature sensor n-0 |
|||
|
Frequency |
Frequency n-0 |
|||
|
Average current |
Average current n-0 |
|||
|
L1 current |
L1 current n-0 |
|||
|
L2 current |
L2 current n-0 |
|||
|
L3 current |
L3 current n-0 |
|||
|
Ground current |
Ground current n-0 |
|||
|
Avg current in % |
Average current ratio n-0 |
|||
|
L1 current in % |
L1 current ratio n-0 |
|||
|
L2 current in % |
L2 current ratio n-0 |
|||
|
L3 current in % |
L3 current ratio n-0 |
|||
|
Gnd current in % |
Ground current ratio n-0 |
|||
|
Current imbalance |
Current phase imbalance n-0 |
|||
|
Average voltage |
Average voltage n-0 |
|||
|
L1-L2 voltage |
L1-L2 voltage n-0 |
|||
|
L2-L3 voltage |
L2-L3 voltage n-0 |
|||
|
L3-L1 voltage |
L3-L1 voltage n-0 |
|||
|
Voltage imbalance |
Voltage phase imbalance n-0 |
|||
|
Active power |
Active power n-0 |
|||
|
Power factor |
Power factor n-0 |
The Trip n-1 to Trip n-4 sub-menus contain identical n-1 to n-4 read only parameters.
The Counters, Motor history and LTMR history sub-menus contain the following parameters:
|
Level 3 |
Level 4 |
Level 5 |
Parameter Name |
|---|---|---|---|
|
History |
Counters |
All trips |
Trips count |
|
All alarms |
Alarms count |
||
|
Auto reset |
Auto-resets count |
||
|
Th overld T |
Thermal overload trips count |
||
|
Th overld W |
Thermal overload alarms count |
||
|
Temp sens T |
Motor temperature sensor trips count |
||
|
Cur imbal T |
Current phase imbalance trips count |
||
|
Cur ph loss T |
Current phase loss trips count |
||
|
Long start T |
Long start trips count |
||
|
Jam T |
Jam trips count |
||
|
Undercur T |
Undercurrent trips count |
||
|
Overcur T |
Overcurrent trips count |
||
|
Gnd cur T |
Ground current trips count |
||
|
Volt imbal T |
Voltage phase imbalance trips count |
||
|
V ph loss T |
Voltage phase loss trips count |
||
|
Undervolt T |
Undervoltage trips count |
||
|
Overvolt T |
Overvoltage trips count |
||
|
Load shedd |
Load sheddings count |
||
|
Rstart imm |
Auto restart immediate count |
||
|
Rstart delay |
Auto restart delayed count |
||
|
Rstart manu |
Auto restart manual count |
||
|
UnderPw T |
Underpower trips count |
||
|
OverPw T |
Overpower trips count |
||
|
Under Pfact T |
Under power factor trips count |
||
|
Over Pfact T |
Over power factor trips count |
||
|
HMI loss T |
HMI port trips count |
||
|
History (continued) |
Counters |
Net cfg T |
Network port config trips count |
|
Network T |
Network port trips count |
||
|
Diagnostic T |
Diagnostic trips count |
||
|
Wiring detected error |
Wiring trips count |
||
|
Internal T |
Controller internal trips count |
||
|
Int link T |
Internal port trips count |
||
|
Motor history |
Operating time |
Operating time |
|
|
Motor Starts |
Motor starts count |
||
|
Last start dur |
Motor last start duration |
||
|
Last start current |
Motor last start current ratio |
||
|
Power Wh |
Active power consumption |
||
|
Power VARh |
Reactive power consumption |
||
|
LTMR History |
LTMR max temp |
Controller internal temperature max |
|
|
LO1 closings |
Motor LO1 closings count |
||
|
LO2 closings |
Motor LO2 closings count |
Config
The Config sub-menu contains the following parameters:
|
Level 3 |
Level 4 |
Parameter Name |
|---|---|---|
|
Config |
Enter config |
Controller system config required |
|
End config |
Settings
The Settings sub-menu contains the following parameters:
|
Level 3 |
Level 4 |
Parameter Name |
|---|---|---|
|
Settings |
FDR backup now |
FDR data backup command |
|
FDR restore now |
FDR data restore command |
|
|
Channels |
Config via HMI keypad enable |
|
|
Config via HMI engineering tool enable |
||
|
Config via network port enable |
Product ID
The Product ID sub-menu contains the following read-only parameters:
|
Level 3 |
Level 4 |
Parameter Name |
|---|---|---|
|
Product ID |
LTMR |
Controller commercial reference |
|
LTME |
Expansion commercial reference |
Self-Test
The Self test sub-menu contains the following read-only parameters:
|
Level 3 |
Level 4 |
Parameter Name |
|---|---|---|
|
Self test |
Trip enable |
Test trip enable |
|
Self test now |
Self test command |
Clear
The Clear sub-menu contains the following editable parameters:
|
Level 3 |
Level 4 |
Parameter Name |
|
|---|---|---|---|
|
Clear |
Clear all |
Clear all command |
|
|
Controller setting |
Clear controller settings command |
||
|
Network setting |
Clear network port settings command |
||
|
Statistics |
Clear statistics command |
||
|
Thermal capacity |
Clear thermal capacity level command |
||