DOCA0131EN-03

Statistics Variables

Statistics Overview

Statistics variables are grouped as shown in the following table. Trip statistics are organized into main tables and extension tables.

Statistics Variable Groups

Registers

Global statistics

100 to 121

LTM monitoring statistics

122 to 149

Last trip statistics

and extension

150 to 179

300 to 309

Trip n-1 statistics

and extension

180 to 209

330 to 339

Trip n-2 statistics

and extension

210 to 239

360 to 369

Trip n-3 statistics

and extension

240 to 269

390 to 399

Trip n-4 statistics

and extension

270 to 299

420 to 429

Global Statistics

The global statistics are described in the following table:

Register

Variable Type

Read-only Variables

Note

100-101

(Not significant)

 

102

Ulnt

Ground current trips count

 

103

Ulnt

Thermal overload trips count

 

104

Ulnt

Long start trips count

 

105

Ulnt

Jam trips count

 

106

Ulnt

Current phase imbalance trips count

 

107

Ulnt

Undercurrent trips count

 

109

Ulnt

HMI port trips count

 

110

Ulnt

Controller internal trips count

 

111

Ulnt

Internal port trips count

 

112

Ulnt

(Not significant)

 

113

Ulnt

Network port config trips count

 

114

Ulnt

Network port trips count

 

115

Ulnt

Auto-resets count

 

116

Ulnt

Thermal overload alarms count

 

117-118

UDlnt

Motor starts count

 

119-120

UDlnt

Operating time (s)

 

121

lnt

Controller internal temperature max (°C)

 

LTM Monitoring Statistics

The LTM monitoring statistics are described in the following table:

Register

Variable type

Read-only variables

Note

122

Ulnt

Trips count

 

123

Ulnt

Alarms count

 

124-125

UDlnt

Motor LO1 closings count

 

126-127

UDlnt

Motor LO2 closings count

 

128

Ulnt

Diagnostic trips count

 

129

Ulnt

(Reserved)

 

130

Ulnt

Overcurrent trips count

 

131

Ulnt

Current phase loss trips count

 

132

Ulnt

Motor temperature sensor trips count

 

133

Ulnt

Voltage phase imbalance trips count

1

134

Ulnt

Voltage phase loss trips count

1

135

Ulnt

Wiring trips count

1

136

Ulnt

Undervoltage trips count

1

137

Ulnt

Overvoltage trips count

1

138

Ulnt

Underpower trips count

1

139

Ulnt

Overpower trips count

1

140

Ulnt

Under power factor trips count

1

141

Ulnt

Over power factor trips count

1

142

Ulnt

Load sheddings count

1

143-144

UDlnt

Active power consumption (kWh)

1

145-146

UDlnt

Reactive power consumption (kVARh)

1

147

Ulnt

Auto restart immediate count

148

Ulnt

Auto restart delayed count

149

Ulnt

Auto restart manual count

Last Trip (n-0) Statistics

The last trip statistics are completed by variables at addresses 300 to 310. See Last Trip (n-0) Statistics Extension.

Register

Variable type

Read-only variables

Note

150

Ulnt

Trip code n-0

 

151

Ulnt

Motor full load current ratio n-0 (% FLC max)

 

152

Ulnt

Thermal capacity level n-0 (% trip level)

 

153

Ulnt

Average current ratio n-0 (% FLC)

 

154

Ulnt

L1 current ratio n-0 (% FLC)

 

155

Ulnt

L2 current ratio n-0 (% FLC)

 

156

Ulnt

L3 current ratio n-0 (% FLC)

 

157

Ulnt

Ground current ratio n-0 (x 0.1 % FLC min)

 

158

Ulnt

Full load current max n-0 (x 0.1 A)

 

159

Ulnt

Current phase imbalance n-0 (%)

 

160

Ulnt

Frequency n-0 (x 0.1 Hz)

2

161

Ulnt

Motor temperature sensor n-0 (x 0.1 Ω)

 

162-165

Word[4]

Date and time n-0 DT_DateTime

 

166

Ulnt

Average voltage n-0 (V)

1

167

Ulnt

L3-L1 voltage n-0 (V)

1

168

Ulnt

L1-L2 voltage n-0 (V)

1

169

Ulnt

L2-L3 voltage n-0 (V)

1

170

Ulnt

Voltage phase imbalance n-0 (%)

1

171

Ulnt

Active power n-0 (x 0.1 kW)

1

172

Ulnt

Power factor n-0 (x 0.01)

1

173-179

(Not significant)

 

N-1 Trip Statistics

The n-1 trip statistics are completed by variables at addresses 330 to 340. See N-1 Trip Statistics Extension .

Register

Variable type

Read-only variables

Note

180

Ulnt

Trip code n-1

 

181

Ulnt

Motor full load current ratio n-1 (% FLC max)

 

182

Ulnt

Thermal capacity level n-1 (% trip level)

 

183

Ulnt

Average current ratio n-1 (% FLC)

 

184

Ulnt

L1 current ratio n-1 (% FLC)

 

185

Ulnt

L2 current ratio n-1 (% FLC)

 

186

Ulnt

L3 current ratio n-1 (% FLC)

 

187

Ulnt

Ground current ratio n-1 (x 0.1 % FLC min)

 

188

Ulnt

Full load current max n-1 (x 0.1 A)

 

189

Ulnt

Current phase imbalance n-1 (%)

 

190

Ulnt

Frequency n-1 (x 0.1 Hz)

2

191

Ulnt

Motor temperature sensor n-1 (x 0.1 Ω)

 

192-195

Word[4]

Date and time n-1 DT_DateTime

 

196

Ulnt

Average voltage n-1 (V)

1

197

Ulnt

L3-L1 voltage n-1 (V)

1

198

Ulnt

L1-L2 voltage n-1 (V)

1

199

Ulnt

L2-L3 voltage n-1 (V)

1

200

Ulnt

Voltage phase imbalance n-1 (%)

1

201

Ulnt

Active power n-1 (x 0.1 kW)

1

202

Ulnt

Power factor n-1 (x 0.01)

1

203-209

Ulnt

(Not significant)

 

N-2 Trip Statistics

The n-2 trip statistics are completed by variables at addresses 360 to 370. See N-2 Trip Statistics Extension .

Register

Variable type

Read-only variables

Note

210

Ulnt

Trip code n-2

 

211

Ulnt

Motor full load current ratio n-2 (% FLC max)

 

212

Ulnt

Thermal capacity level n-2 (% trip level)

 

213

Ulnt

Average current ratio n-2 (% FLC)

 

214

Ulnt

L1 current ratio n-2 (% FLC)

 

215

Ulnt

L2 current ratio n-2 (% FLC)

 

216

Ulnt

L3 current ratio n-2 (% FLC)

 

217

Ulnt

Ground current ratio n-2 (x 0.1 % FLC min)

 

218

Ulnt

Full load current max n-2 (x 0.1 A)

 

219

Ulnt

Current phase imbalance n-2 (%)

 

220

Ulnt

Frequency n-2 (x 0.1 Hz)

2

221

Ulnt

Motor temperature sensor n-2 (x 0.1 Ω)

 

222-225

Word[4]

Date and time n-2 DT_DateTime

 

226

Ulnt

Average voltage n-2 (V)

1

227

Ulnt

L3-L1 voltage n-2 (V)

1

228

Ulnt

L1-L2 voltage n-2 (V)

1

229

Ulnt

L2-L3 voltage n-2 (V)

1

230

Ulnt

Voltage phase imbalance n-2 (%)

1

231

Ulnt

Active power n-2 (x 0.1 kW)

1

232

Ulnt

Power factor n-2 (x 0.01)

1

233-239

(Not significant)

 

N-3 Trip Statistics

The n-3 trip statistics are completed by variables at addresses 390 to 400. See N-3 Trip Statistics Extension .

Register

Variable type

Read-only variables

Note

240

Ulnt

Trip code n-3

 

241

Ulnt

Motor full load current ratio n-3 (% FLC max)

 

242

Ulnt

Thermal capacity level n-3 (% trip level)

 

243

Ulnt

Average current ratio n-3 (% FLC)

 

244

Ulnt

L1 current ratio n-3 (% FLC)

 

245

Ulnt

L2 current ratio n-3 (% FLC)

 

246

Ulnt

L3 current ratio n-3 (% FLC)

 

247

Ulnt

Ground current ratio n-3 (x 0.1 % FLC min)

 

248

Ulnt

Full load current max n-3 (0.1 A)

 

249

Ulnt

Current phase imbalance n-3 (%)

 

250

Ulnt

Frequency n-3 (x 0.1 Hz)

2

251

Ulnt

Motor temperature sensor n-3 (x 0.1 Ω)

 

252-255

Word[4]

Date and time n-3 DT_DateTime

 

256

Ulnt

Average voltage n-3 (V)

1

257

Ulnt

L3-L1 voltage n-3 (V)

1

258

Ulnt

L1-L2 voltage n-3 (V)

1

259

Ulnt

L2-L3 voltage n-3 (V)

1

260

Ulnt

Voltage phase imbalance n-3 (%)

1

261

Ulnt

Active power n-3 (x 0.1 kW)

1

262

Ulnt

Power factor n-3 (x 0.01)

1

263-269

(Not significant)

 

N-4 Trip Statistics

The n-4 trip statistics are completed by variables at addresses 420 to 430. See N-4 Trip Statistics Extension .

Register

Variable type

Read-only variables

Note

270

Ulnt

Trip code n-4

 

271

Ulnt

Motor full load current ratio n-4 (% FLC max)

 

272

Ulnt

Thermal capacity level n-4 (% trip level)

 

273

Ulnt

Average current ratio n-4 (% FLC)

 

274

Ulnt

L1 current ratio n-4 (% FLC)

 

275

Ulnt

L2 current ratio n-4 (% FLC)

 

276

Ulnt

L3 current ratio n-4 (% FLC)

 

277

Ulnt

Ground current ratio n-4 (x 0.1 % FLC min)

 

278

Ulnt

Full load current max n-4 (x 0.1 A)

 

279

Ulnt

Current phase imbalance n-4 (%)

 

280

Ulnt

Frequency n-4 (x 0.1 Hz)

2

281

Ulnt

Motor temperature sensor n-4 (x 0.1 Ω)

 

282-285

Word[4]

Date and time n-4 DT_DateTime

 

286

Ulnt

Average voltage n-4 (V)

1

287

Ulnt

L3-L1 voltage n-4 (V)

1

288

Ulnt

L1-L2 voltage n-4 (V)

1

289

Ulnt

L2-L3 voltage n-4 (V)

1

290

Ulnt

Voltage phase imbalance n-4 (%)

1

291

Ulnt

Active power n-4 (x 0.1 kW)

1

292

Ulnt

Power factor n-4 (x 0.01)

1

293-299

(Not significant)

 

Last Trip (n-0) Statistics Extension

The last trip main statistics are listed at addresses 150 to 179.

Register

Variable type

Read-only variables

Note

300-301

UDlnt

Average current n-0 (x 0.01 A)

 

302-303

UDlnt

L1 current n-0 (x 0.01 A)

 

304-305

UDlnt

L2 current n-0 (x 0.01 A)

 

306-307

UDlnt

L3 current n-0 (x 0.01 A)

 

308-309

UDlnt

Ground current n-0 (mA)

 

310

Ulnt

Motor temperature sensor degree n-0 (°C)

 

N-1 Trip Statistics Extension

The n-1 trip main statistics are listed at addresses 180 to 209.

Register

Variable type

Read-only variables

Note

330-331

UDlnt

Average current n-1 (x 0.01 A)

 

332-333

UDlnt

L1 current n-1 (x 0.01 A)

 

334-335

UDlnt

L2 current n-1 (x 0.01 A)

 

336-337

UDlnt

L3 current n-1 (x 0.01 A)

 

338-339

UDlnt

Ground current n-1 (mA)

 

340

Ulnt

Motor temperature sensor degree n-1 (°C)

 

N-2 Trip Statistics Extension

The n-2 trip main statistics are listed at addresses 210 to 239.

Register

Variable type

Read-only variables

Note

360-361

UDlnt

Average current n-2 (x 0.01 A)

 

362-363

UDlnt

L1 current n-2 (x 0.01 A)

 

364-365

UDlnt

L2 current n-2 (x 0.01 A)

 

366-367

UDlnt

L3 current n-2 (x 0.01 A)

 

368-369

UDlnt

Ground current n-2 (mA)

 

370

Ulnt

Motor temperature sensor degree n-2 (°C)

 

N-3 Trip Statistics Extension

The n-3 trip main statistics are listed at addresses 240 to 269.

Register

Variable type

Read-only variables

Note

390-391

UDlnt

Average current n-3 (x 0.01 A)

 

392-393

UDlnt

L1 current n-3 (x 0.01 A)

 

394-395

UDlnt

L2 current n-3 (x 0.01 A)

 

396-397

UDlnt

L3 current n-3 (x 0.01 A)

 

398-399

UDlnt

Ground current n-3 (mA)

 

400

Ulnt

Motor temperature sensor degree n-3 (°C)

 

N-4 Trip Statistics Extension

The n-4 trip main statistics are listed at addresses 270 to 299.

Register

Variable type

Read-only variables

Note

420-421

UDlnt

Average current n-4 (x 0.01 A)

 

422-423

UDlnt

L1 current n-4 (x 0.01 A)

 

424-425

UDlnt

L2 current n-4 (x 0.01 A)

 

426-427

UDlnt

L3 current n-4 (x 0.01 A)

 

428-429

UDlnt

Ground current n-4 (mA)

 

430

Ulnt

Motor temperature sensor degree n-4 (°C)

 