GEX2563900-02

Mechanical Interlocks

Interlock

Function of interlock

Between truck and low voltage connector

The truck cannot be actuated, unless the low voltage plug is inserted.

The low voltage plug cannot be removed, when the truck is not in disconnected/test position.

Between circuit breaker and truck

Circuit breaker cannot be racked in or out while it is switched ON.

Circuit breaker cannot be switched ON, unless the truck is completely in its test or in-service position. CB can be ON/OFF in test / service position.

Between truck and cubicle

If the truck front frame is not locked in the cubicle, the truck cannot be actuated.

If the truck has left its test position, the truck front frame cannot be unlocked in the cubicle.

Between truck and front door

If the front door is opened, the truck cannot be moved into the service position.

Door cannot be opened, if the truck has left its test position.

Feedback