Control
Operating Mode
Parameter |
Setting Range |
Factory Setting |
---|---|---|
Control direct transition |
On / Off |
Off |
Motor transition timeout |
0...999.9 s |
1 s |
Motor Step 1 to 2 threshold |
20...800 % FLC in increments of 1 % |
150 % FLC |
Motor Step 1 to 2 timeout |
0.1...999.9 s |
5 s |
Inputs/Outputs
Parameter |
Setting Range |
Factory Setting |
---|---|---|
Controller AC logic inputs configuration |
|
Unknown |
Logic input 3 external ready enable |
|
Disable |
Rapid Cycle
Parameter |
Setting Range |
Factory Setting |
---|---|---|
Rapid cycle lockout timeout |
0...9999 s in increments of 1 s |
0 s |
Local/Remote Control
Parameter |
Setting Range |
Factory Setting |
---|---|---|
Control remote channel setting |
|
Network |
Control local channel setting |
|
Terminal strip |
Control transfer mode |
|
Bump |
Control remote local buttons enable |
|
Disable |
Control remote local default mode |
|
Remote |
Stop HMI disable |
|
Disable |
Stop terminal strip disable |
|
Disable |
Diagnostic
Parameter |
Setting Range |
Factory Setting |
---|---|---|
Diagnostic trip enable |
|
Enable |
Diagnostic alarm enable |
|
Enable |
Wiring trip enable |
|
Enable |
Motor phases sequence |
|
A B C |
Trip and Alarm
Parameter |
Setting Range |
Factory Setting |
---|---|---|
Trip reset mode |
|
Manual or HMI |
Auto-reset attempts group 1 setting |
0 = manual, 1, 2, 3, 4, 5 = unlimited number of reset attempts |
5 |
Auto-reset group 1 timeout |
0...9,999 s in increments of 1 s |
480 s |
Auto-reset attempts group 2 setting |
0 = manual, 1, 2, 3, 4, 5 = unlimited number of reset attempts |
0 |
Auto-reset group 2 timeout |
0...9999 s in increments of 1 s |
1,200 s |
Auto-reset attempts group 3 setting |
0 = manual, 1, 2, 3, 4, 5 = unlimited number of reset attempts |
0 |
Auto-reset group 3 timeout |
0...9999 s in increments of 1 s |
60 s |