Thermal
Thermal Overload
|
Parameter |
Setting Range |
Factory Setting |
|---|---|---|
|
Thermal overload mode |
|
Inverse thermal |
|
Motor trip class |
|
Motor class 5 |
|
Thermal overload trip enable |
|
Enable |
|
Thermal overload trip reset threshold |
35...95 % in increments of 1 % |
75 % |
|
Thermal overload alarm enable |
|
Enable |
|
Thermal overload alarm threshold |
10...100 % in increments of 1 % |
85 % |
|
Long start trip timeout |
1...200 s in increments of 1 s |
10 s |
|
Thermal overload trip enable |
|
Enable |
|
Thermal overload trip definite timeout |
1...300 s in increments of 1 s |
10 s |
|
Thermal overload alarm enable |
|
Enable |
Motor Temperature
|
Parameters |
Setting range |
Factory setting |
|---|---|---|
|
Motor temperature sensor type |
|
None |
|
Motor temperature sensor trip enable |
|
Disable |
|
Motor temperature sensor trip threshold |
20...6,500 Ω |
20 Ω |
|
Motor temperature sensor trip threshold degree |
0...200 °C |
0 °C |
|
Motor temperature sensor alarm enable |
|
Disable |
|
Motor temperature sensor alarm threshold |
20...6,500 Ω |
20 Ω |
|
Motor temperature sensor alarm threshold degree |
0...200 °C |
0 °C |