Current
Ground Current
Parameters |
Setting range |
Factory setting |
---|---|---|
Ground current disable while motor starting |
|
No |
Ground current trip enable |
|
Enable |
Internal ground current trip threshold |
20...500 % FLCmin in increments of 1 % |
30 % FLCmin |
Internal ground current trip timeout |
0.5...25 s in increments of 0.1 s |
1 s |
External ground current trip threshold |
0.02...20 A in increments of 0.01 A |
1 A |
External ground current trip timeout |
0.1...25 s in increments of 0.01 s |
0.5 s |
Ground Current alarm enable |
|
Enable |
Internal ground current alarm threshold |
50...500 % FLCmin in increments of 1 % |
50 % FLCmin |
External ground current alarm threshold |
0.02...20 A in increments of 0.01 A |
1 A |
Phases
Parameters |
Setting range |
Factory setting |
---|---|---|
Current phase imbalance trip enable |
|
Enable |
Current phase imbalance trip threshold |
10...70 % in increments of 1 % |
10 % |
Current phase imbalance trip timeout starting |
0.2...20 s in increments of 0.1 s |
0.7 s |
Current phase imbalance trip timeout running |
0.2...20 s in increments of 0.1 s |
5 s |
Current phase imbalance alarm enable |
|
Disable |
Current phase imbalance alarm threshold |
10...70 % in increments of 1 % |
10 % |
Current phase loss trip enable |
|
Enable |
Current phase loss timeout |
0.1...30 s in increments of 0.1 s |
3 s |
Current phase loss alarm enable |
|
Enable |
Current phase reversal trip enable |
|
Disable |
Long Start
Parameters |
Setting range |
Factory setting |
---|---|---|
Long start trip enable |
|
Enable |
Long start trip threshold |
100...800 % FLC in increments of 1 % |
100 % FLC |
Long start trip timeout |
1...200 s in increments of 1 s |
10 s |
Jam
Parameters |
Setting range |
Factory setting |
---|---|---|
Jam trip enable |
|
Enable |
Jam trip threshold |
100...800 % FLC in increments of 1 % |
200 % FLC |
Jam trip timeout |
1...30 s in increments of 1 s |
5 s |
Jam alarm enable |
|
Disable |
Jam alarm threshold |
100...800 % FLC in increments of 1 % |
200 % FLC |
Undercurrent
Parameters |
Setting range |
Factory setting |
---|---|---|
Undercurrent Trip Enable |
|
Disable |
Undercurrent Trip Threshold |
30...100 % FLC in increments of 1 % |
50 % FLC |
Undercurrent Trip Timeout |
1...200 s in increments of 1 s |
10 s |
Undercurrent Alarm Enable |
|
Disable |
Undercurrent Alarm Threshold |
30...100 % FLC in increments of 1 % |
50 % FLC |
Overcurrent
Parameters |
Setting range |
Factory setting |
---|---|---|
Overcurrent trip enable |
|
Disable |
Overcurrent Trip Threshold |
20...800 % FLC in increments of 1 % |
200 % FLC |
Overcurrent trip timeout |
1...250 s in increments of 1 s |
10 s |
Overcurrent alarm enable |
|
Disable |
Overcurrent alarm threshold |
20...800 % FLC in increments of 1 % |
200 % FLC |