DOCA0128EN-02

Current

Ground Current

Parameters

Setting range

Factory setting

Ground current disable while motor starting

  • No

  • Yes

No

Ground current trip enable

  • Disable

  • Enable

Enable

Internal ground current trip threshold

20...500 % FLCmin in increments of 1 %

30 % FLCmin

Internal ground current trip timeout

0.5...25 s in increments of 0.1 s

1 s

External ground current trip threshold

0.02...20 A in increments of 0.01 A

1 A

External ground current trip timeout

0.1...25 s in increments of 0.01 s

0.5 s

Ground Current alarm enable

  • Disable

  • Enable

Enable

Internal ground current alarm threshold

50...500 % FLCmin in increments of 1 %

50 % FLCmin

External ground current alarm threshold

0.02...20 A in increments of 0.01 A

1 A

Phases

Parameters

Setting range

Factory setting

Current phase imbalance trip enable

  • Disable

  • Enable

Enable

Current phase imbalance trip threshold

10...70 % in increments of 1 %

10 %

Current phase imbalance trip timeout starting

0.2...20 s in increments of 0.1 s

0.7 s

Current phase imbalance trip timeout running

0.2...20 s in increments of 0.1 s

5 s

Current phase imbalance alarm enable

  • Disable

  • Enable

Disable

Current phase imbalance alarm threshold

10...70 % in increments of 1 %

10 %

Current phase loss trip enable

  • Disable

  • Enable

Enable

Current phase loss timeout

0.1...30 s in increments of 0.1 s

3 s

Current phase loss alarm enable

  • Disable

  • Enable

Enable

Current phase reversal trip enable

  • Disable

  • Enable

Disable

Long Start

Parameters

Setting range

Factory setting

Long start trip enable

  • Disable

  • Enable

Enable

Long start trip threshold

100...800 % FLC in increments of 1 %

100 % FLC

Long start trip timeout

1...200 s in increments of 1 s

10 s

Jam

Parameters

Setting range

Factory setting

Jam trip enable

  • Disable

  • Enable

Enable

Jam trip threshold

100...800 % FLC in increments of 1 %

200 % FLC

Jam trip timeout

1...30 s in increments of 1 s

5 s

Jam alarm enable

  • Disable

  • Enable

Disable

Jam alarm threshold

100...800 % FLC in increments of 1 %

200 % FLC

Undercurrent

Parameters

Setting range

Factory setting

Undercurrent Trip Enable

  • Disable

  • Enable

Disable

Undercurrent Trip Threshold

30...100 % FLC in increments of 1 %

50 % FLC

Undercurrent Trip Timeout

1...200 s in increments of 1 s

10 s

Undercurrent Alarm Enable

  • Disable

  • Enable

Disable

Undercurrent Alarm Threshold

30...100 % FLC in increments of 1 %

50 % FLC

Overcurrent

Parameters

Setting range

Factory setting

Overcurrent trip enable

  • Disable

  • Enable

Disable

Overcurrent Trip Threshold

20...800 % FLC in increments of 1 %

200 % FLC

Overcurrent trip timeout

1...250 s in increments of 1 s

10 s

Overcurrent alarm enable

  • Disable

  • Enable

Disable

Overcurrent alarm threshold

20...800 % FLC in increments of 1 %

200 % FLC