DOCA0128EN-02

Power

Underpower

Parameters

Setting range

Factory setting

Underpower trip enable

  • Disable

  • Enable

Disable

Underpower trip threshold

20...800 % of Motor nominal power in increments of 1 %

20 % of Motor nominal power

Underpower trip timeout

1...100 s in increments of 1 s

60 s

Underpower alarm enable

  • Disable

  • Enable

Disable

Underpower alarm threshold

20...800 % of Motor nominal power in increments of 1 %

30 % of Motor nominal power

Overpower

Parameters

Setting range

Factory setting

Overpower trip enable

  • Disable

  • Enable

Disable

Overpower trip threshold

20...800 % of Motor nominal power in increments of 1 %

150 % of Motor nominal power

Overpower trip timeout

1...100 s in increments of 1 s

60 s

Overpower alarm enable

  • Disable

  • Enable

Disable

Overpower alarm threshold

20...800 % of Motor nominal power in increments of 1 %

150 % of Motor nominal power

Under Power Factor

Parameters

Setting range

Factory setting

Under power factor trip enable

  • Disable

  • Enable

Disable

Under power factor trip threshold

0...1 in increments of 0.01

0.6

Under power factor trip timeout

1...25 s in increments of 0.1 s

10 s

Under power factor alarm enable

  • Disable

  • Enable

Disable

Under power factor alarm threshold

0...1 in increments of 0.01

0.6

Over Power Factor

Parameters

Setting range

Factory setting

Over power factor trip enable

  • Disable

  • Enable

Disable

Over power factor trip threshold

0...1 in increments of 0.01

0.9

Under power factor trip timeout

1...25 s in increments of 0.1 s

10 s

Over power factor alarm enable

  • Disable

  • Enable

Disable

Over power factor alarm threshold

0...1 in increments of 0.01

0.9