Power
Underpower
Parameters |
Setting range |
Factory setting |
---|---|---|
Underpower trip enable |
|
Disable |
Underpower trip threshold |
20...800 % of Motor nominal power in increments of 1 % |
20 % of Motor nominal power |
Underpower trip timeout |
1...100 s in increments of 1 s |
60 s |
Underpower alarm enable |
|
Disable |
Underpower alarm threshold |
20...800 % of Motor nominal power in increments of 1 % |
30 % of Motor nominal power |
Overpower
Parameters |
Setting range |
Factory setting |
---|---|---|
Overpower trip enable |
|
Disable |
Overpower trip threshold |
20...800 % of Motor nominal power in increments of 1 % |
150 % of Motor nominal power |
Overpower trip timeout |
1...100 s in increments of 1 s |
60 s |
Overpower alarm enable |
|
Disable |
Overpower alarm threshold |
20...800 % of Motor nominal power in increments of 1 % |
150 % of Motor nominal power |
Under Power Factor
Parameters |
Setting range |
Factory setting |
---|---|---|
Under power factor trip enable |
|
Disable |
Under power factor trip threshold |
0...1 in increments of 0.01 |
0.6 |
Under power factor trip timeout |
1...25 s in increments of 0.1 s |
10 s |
Under power factor alarm enable |
|
Disable |
Under power factor alarm threshold |
0...1 in increments of 0.01 |
0.6 |
Over Power Factor
Parameters |
Setting range |
Factory setting |
---|---|---|
Over power factor trip enable |
|
Disable |
Over power factor trip threshold |
0...1 in increments of 0.01 |
0.9 |
Under power factor trip timeout |
1...25 s in increments of 0.1 s |
10 s |
Over power factor alarm enable |
|
Disable |
Over power factor alarm threshold |
0...1 in increments of 0.01 |
0.9 |