Power
Underpower
|
Parameters |
Setting range |
Factory setting |
|---|---|---|
|
Underpower trip enable |
|
Disable |
|
Underpower trip threshold |
20...800 % of Motor nominal power in increments of 1 % |
20 % of Motor nominal power |
|
Underpower trip timeout |
1...100 s in increments of 1 s |
60 s |
|
Underpower alarm enable |
|
Disable |
|
Underpower alarm threshold |
20...800 % of Motor nominal power in increments of 1 % |
30 % of Motor nominal power |
Overpower
|
Parameters |
Setting range |
Factory setting |
|---|---|---|
|
Overpower trip enable |
|
Disable |
|
Overpower trip threshold |
20...800 % of Motor nominal power in increments of 1 % |
150 % of Motor nominal power |
|
Overpower trip timeout |
1...100 s in increments of 1 s |
60 s |
|
Overpower alarm enable |
|
Disable |
|
Overpower alarm threshold |
20...800 % of Motor nominal power in increments of 1 % |
150 % of Motor nominal power |
Under Power Factor
|
Parameters |
Setting range |
Factory setting |
|---|---|---|
|
Under power factor trip enable |
|
Disable |
|
Under power factor trip threshold |
0...1 in increments of 0.01 |
0.6 |
|
Under power factor trip timeout |
1...25 s in increments of 0.1 s |
10 s |
|
Under power factor alarm enable |
|
Disable |
|
Under power factor alarm threshold |
0...1 in increments of 0.01 |
0.6 |
Over Power Factor
|
Parameters |
Setting range |
Factory setting |
|---|---|---|
|
Over power factor trip enable |
|
Disable |
|
Over power factor trip threshold |
0...1 in increments of 0.01 |
0.9 |
|
Under power factor trip timeout |
1...25 s in increments of 0.1 s |
10 s |
|
Over power factor alarm enable |
|
Disable |
|
Over power factor alarm threshold |
0...1 in increments of 0.01 |
0.9 |