Wire Sizes for Homeline Circuit Breakers
|
Breaker Type |
Ampere Rating |
Wire Size (AWG/kcmil) [1] |
|
|---|---|---|---|
|
Aluminum |
Copper |
||
|
HOM 1P |
15–30 A |
14–8 AWG |
14–8 AWG or (2) 14–10 AWG |
|
40–50 A |
8–2 AWG |
8–2 AWG |
|
|
HOM 2P |
15–30 A |
14–8 AWG |
14–8 AWG or (2) 14–10 AWG |
|
35–70 A |
8–2 AWG |
8–2 AWG |
|
|
80–125 A |
4–2/0 AWG |
4–2/0 AWG |
|
|
150–200 A |
4 AWG–300 kcmil |
4 AWG–300 kcmil |
|
|
HOMT and Quad |
15–30 A |
14–8 AWG |
14–8 AWG |
|
Quad Only |
40–50 A |
6–12 AWG |
6–14 AWG |
|
HOM-GFI - 1P |
15–20 A |
14–10 AWG |
14–10 AWG |
|
HOM-GFI - 2P |
15–50 A |
12–4 AWG |
14–6 AWG |