Homeline Circuit Breaker Wire Sizes

Homeline Circuit Breaker Wire Sizes

Wire Sizes for Homeline Circuit Breakers

Breaker Type

Ampere Rating

Wire Size (AWG/kcmil) [1]

Aluminum

Copper

HOM

1P

15–30 A

14–8 AWG

14–8 AWG or

(2) 14–10 AWG

40–50 A

8–2 AWG

8–2 AWG

HOM

2P

15–30 A

14–8 AWG

14–8 AWG or

(2) 14–10 AWG

35–70 A

8–2 AWG

8–2 AWG

 80–125 A

4–2/0 AWG

4–2/0 AWG

150–200 A

4 AWG–300 kcmil

4 AWG–300 kcmil

HOMT and Quad

15–30 A

14–8 AWG

14–8 AWG

Quad Only

40–50 A

6–12 AWG

6–14 AWG

HOM-GFI - 1P

15–20 A

14–10 AWG

14–10 AWG

HOM-GFI - 2P

15–50 A

12–4 AWG

14–6 AWG

Footnotes

  1. 15–30 A circuit breakers are suitable for use with 60°C or 75°C conductors. 40–125 A circuit breakers are suitable for use with 75°C conductors.
Feedback