QO Special Constructions, Single Phase
Class 1130 / Refer to Catalog 1100CT0501
QO Standard Load Center Main Lugs and Main Breaker, Fixed Mains
1Ø3W—120/240 Vac Special Applications—UL Listed
Low Amperage Fixed Main Lugs Indoor Load Centers (Accepts Only QO Plug-on Circuit Breakers - Not compatible with QO Plug-on Neutral Circuit Breakers)
Mains Rating |
Spaces |
Max. 1P Circuits [1] |
Max. Tandem Circuit Breakers |
Load Center Box and Interior |
Indoor Cover with Door |
Main Wire Size |
Bus Rating |
Equipment |
Box No. [2] |
|||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Flush |
Surface |
Al |
Cu |
|||||||||
I N D O O R |
Fixed Mains—Factory-Installed Main Lugs—10 kA Short Circuit Current Rating [3] |
|||||||||||
30 A |
2 |
2 |
0 |
Cover Included—Without Door |
12–10 |
14–10 |
30 |
1 |
||||
70 A |
2 |
4 |
2 |
Cover Included—Without Door |
12–3 |
14–4 |
70 |
2 |
||||
100 A |
6 |
12 |
6 |
QO612L100F / S [6] [8] |
Cover Included—Without Door |
8–1 |
100 |
4 |
||||
6 |
12 |
6 |
QO612L100DF / S [6] [8] |
Cover Included—With Door |
100 |
4 |
||||||
8 |
16 |
8 |
QO816L100F / S [6] [8] |
Cover Included—Without Door |
100 |
4 |
||||||
8 |
16 |
8 |
QO816L100DF / S [6] [8] |
Cover Included—With Door |
100 | |||||||
6 |
12 |
6 |
QO612L100DFCU OBS / |
Cover Included—With Door |
100 |
4 |
||||||
8 |
16 |
8 |
QO816L100DFCU OBS / |
Cover Included—With Door |
100 |
4 |
||||||
125 A |
4 |
8 |
4 |
QO148L125GF / S [6] [10] |
Cover Included—Without Door |
12–2/0 |
14–2/0 |
125 |
PK7GTA [11] |
21 |
||
OBS This product is obsolete. |
Low Amperage Fixed Mains Indoor Load Centers with Factory Installed Ground Bar (Accepts Only QO Plug-On Circuit Breakers - Not compatible with QO Plug-on Neutral Circuit Breakers)
Mains Rating |
Short |
Spaces |
Max. 1P Circuits [1] |
Max. Tandem Circuit Breakers |
Load Center [6] Box, Interior, and Cover |
Equipment Ground Bar Kit (Order Separately) |
Main Wire Size AWG/kcmil |
Bus Rating |
Box No. [2] |
||
---|---|---|---|---|---|---|---|---|---|---|---|
Al |
Cu |
||||||||||
I N D O O R |
Manufactured Housing: 1Ø2W 120 Vac—Main Lugs Only—CSA Certified |
||||||||||
30 A[12] |
10 kA |
2 |
2 |
0 |
Factory-installed |
12–10 |
14–10 |
30 |
1 |
||
50 A |
10 kA |
2 |
4 |
2 |
QO24L50TTS OBS[7] |
— |
14–6 |
70 |
2 |
||
1Ø2W 120 Vac—Main Circuit Breaker—CSA Certified |
|||||||||||
30 A |
10 kA |
3 |
5 |
2 |
QO35FM30TTF OBS / |
Factory-installed |
— |
3 |
|||
1Ø3W 120/240 Vac—Main Lugs Only—CSA Certified |
|||||||||||
70 A |
10 kA |
2 |
4 |
2 |
Factory |
12–3 |
14–4 |
70 |
2 |
||
100 A |
10 kA |
6 |
12 |
6 |
QO612L100TF OBS |
4–1 |
100 |
4 |
|||
6 |
12 |
6 |
QO612L100DTF / S OBS[15] |
100 |
4 |
||||||
8 |
16 |
8 |
QO816L100TF OBS / | 100 |
4 |
||||||
8 |
16 |
8 |
100 |
4 |
|||||||
OBS This product is obsolete. |
High Amperage Fixed Main Breaker and Main Lugs Indoor Load Centers (Accepts Only QO Plug-On Circuit Breakers - Not compatible with QO Plug-on Neutral Circuit Breakers)
Mains Rating |
Spaces |
Max. 1P |
Max. Tandem Circuit Breakers |
Load Center Box and Interior |
Indoor Cover with Door (Order Separately) |
Main Wire Size |
Equipment |
Box No. [2] |
|||
---|---|---|---|---|---|---|---|---|---|---|---|
Flush |
Surface |
Al |
Cu |
||||||||
I N D O O R |
300 A |
42 |
42 |
0 |
QONQ42MS300 (Int) [16] |
(1) 4–500 |
or |
16 |
|||
or (2) 4–3/0 |
|||||||||||
400 A |
42 |
42 |
0 |
QONQ42MS400 (Int) [16] |
(1) 4–500 |
16 |
|||||
or (2) 4–3/0 |
|||||||||||
Fixed Mains—Factory-Installed Main Lugs—65 kA Short Circuit Current Rating [3] [19] |
|||||||||||
400 A |
30 |
30 |
0 |
QONQ30LS400 (Int) [16] |
(1) 1/0–750 or (2) 1/0–300 |
or |
15 |
||||
42 |
42 |
0 |
QONQ42LS400 (Int) [16] |
15 |
|||||||
Above listings through 200 A mains rating meet Federal Specification W-P-115C as Type 1, Class 2. |
QO Standard Load Center Main Lugs, Fixed Mains
1Ø3W—120/240 Vac Rainproof—UL Listed
Fixed Main Lugs Rainproof Load Centers (Accepts Only QO Plug-on Circuit Breakers - Not compatible with QO Plug-on Neutral Circuit Breakers)
Mains Rating |
Spaces |
Max. Circuits [1] |
Max. Tandem Circuit Breakers |
Load Center Box and Interior |
Main Wire Size AWG/kcmil |
Bus Rating |
Equipment Ground Bar Kit (Order Separately) |
Box No. [20] |
||
---|---|---|---|---|---|---|---|---|---|---|
Al |
Cu |
|||||||||
R I N P R O O F |
Non-Metallic Enclosure Fixed Mains—Factory-installed Main Lugs—10 kA Short Circuit Current Rating |
|||||||||
60 A |
2 |
4 |
2 |
14–4 |
14–4 |
60 |
Factory-installed |
1NM |
||
Metallic Enclosure Fixed Mains—Factory-installed Main Lugs—10 kA Short Circuit Current Rating |
||||||||||
40 A |
2 |
2 |
0 |
12–6 |
14–6 |
40 |
1R |
|||
70 A |
2 |
4 |
2 |
12–3 |
14–4 |
70 |
1R |
|||
100 A |
6 |
12 |
6 |
8–1 |
100 |
2R |
||||
6 |
12 |
6 |
100 |
Factory-installed |
2R |
|||||
8 |
16 |
8 |
100 |
2R |
||||||
6 |
12 |
6 |
100 |
2R |
||||||
8 |
16 |
8 |
100 |
2R |
||||||
125 A |
4 |
8 |
4 |
12–2/0 |
14–2/0 |
125 |
PK7GTA Factory-included |
15R |
Standard Load Center Main Breaker, Convertible Mains
1Ø3W—120/240 Vac Rainproof—UL Listed
Convertible Main Breaker Load Centers (Accepts Only QO Plug-on Circuit Breakers - Not compatible with QO Plug-on Neutral Circuit Breakers)
Mains Rating |
Spaces |
Max. Circuits [1] |
Max. Tandem Circuit Breakers |
Load Center Box and Interior |
Al |
Cu |
Equipment Ground Bar Kit (Order Separately) |
Bus Rating |
Box No. [20] |
|
---|---|---|---|---|---|---|---|---|---|---|
R A I N P R O O F |
Convertible Mains —Factory-installed Main Circuit Breaker with Feed-thru Lugs, 22 kA Short Circuit Current Rating Convertible to Main
Lugs (See 1Ø, Field-Installed
Mains Kits or Lower Amperage Main Circuit Breaker (See QO Standard Plug-On
Circuit Breakers) [22], [23] |
|||||||||
125 A |
6 |
12 |
6 |
4–2/0 |
125 | 3R |
||||
150 A |
8 |
16 |
8 |
4–250 |
200 | 4R |
||||
200 A |
8 |
16 |
8 |
4–250 |
200 | 4R |
||||
Above listings through 200 A mains rating meet Federal Specification W-P-115C as Type 1, Class 2. |
QO Riser Panels
1Ø3W—120/240 Vac Special Applications—UL Listed
Riser Panels for Offset Interior for Wide Gutter—30
A Maximum Branch Circuit Breaker on Left Side of Interior [3] , [19]
(Compatible with QO Plug-on Circuit Breakers
and QO Plug-on Neutral Circuit Breakers)
Mains Rating |
Spaces |
Max. Single Pole Circuits [1] |
Max. Tandem Circuit Breakers |
Load Center Box and Interior |
Load Center Cover |
Equipment Ground Bar Kit (Order Separately) |
Main Wire Size AWG/kcmil |
Bus Ratings |
Box No. [25] |
|||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Flush |
Mono-Flat |
Al |
Cu |
|||||||||
I N D O O R |
Convertible Mains—Factory-Installed Main Lugs, 65 kA Short Circuit Current Rating Convertible to QOM1 22 kA Short Circuit Current Rating Main Circuit Breaker (See Indoor, 1Ø, Main Lugs) when used with QOC cover below—Copper Bus |
|||||||||||
125 A |
12 |
24 |
12 |
QO112L125PWG OBS |
6–2/0 |
125 |
14 |
|||||
20 |
24 |
4 |
125 |
14 |
||||||||
Convertible Mains-Factory—Installed Main Lugs, 65 kA Short Circuit Current Rating Convertible to QOM2 22 kA Short Circuit Current Rating Main Circuit Breaker (See Indoor, 1Ø, Main Circuit Breaker) when used with QOC cover below—Copper Bus |
||||||||||||
200 A |
30 |
40 |
10 |
4–250 |
225 |
23 |
||||||
Convertible
Mains—Factory-Installed Main Circuit Breaker, 22 kA Short Circuit
Current Rating Convertible to Main Lugs (See Indoor, 1Ø, Main Lugs) |
||||||||||||
200 A |
24 |
36 |
12 |
4–250 |
225 |
23 |
||||||
Above listings through 200 A mains rating meet Federal Specification W-P-115c as Type 1, Class 2. OBS This product is obsolete. |
Panelboard-style Covers for Riser Panels
Mains Rating of Load Center |
Cat. No. |
---|---|
125 A |
NQC20FWG OBS |
200 A |
NQC30FWG OBS |
OBS This product is obsolete. |
Mono-Flat™ Front available for riser panels as an alternative to standard load center cover listed above. Provides a low-profile, aesthetically pleasing solution for high-traffic areas in upscale multi-family applications. Deadfront included. Lock kit not provided. Cover NQC30FWG CANNOT be used when panel has been converted to a main circuit breaker panel. [28]
Auxiliary Gutter
Cat. No. |
Cover |
Conduit Riser Size |
Width |
Height |
Depth |
---|---|---|---|---|---|
UL Listed for use with standard 1Ø and 3Ø load centers for riser applications [29]. For auxiliary gutter-load center compatibility, see catalog number 1100CT0501 |
|||||
Flush |
1-3/4, 2, 2-1/2 or [30] 3 |
13.50 |
26.12 |
3.75 |
Tap Kits for Use with Auxiliary Gutter
Cat. N0. |
Use with Auxiliary Gutter Cat. No. |
Riser Wire |
Tap Off Wire |
||
---|---|---|---|---|---|
Lug Type |
Al/Cu Wire Size |
Lug Type |
Al/Cu Wire Size |
||
SDAG26 |
Mechanical (Included) |
(2) 6 AWG–300 kcmil |
Mechanical (Included) |
(1) 6–2/0 AWG |
|
SDAG26 |
Mechanical (Included) |
(2) 6 AWG–300 kcmil |
Mechanical (Included) |
(1) 6 AWG–300 kcmil |
|
SDAG26 |
Anderson VCEL030516H1 (Not included) |
(2) 4 AWG–300 kcmil |
Anderson VCEL02114S1 (Not Included) |
(1) 8–1/0 AWG |
|
SDGT300C300C OBS |
SDAG26 |
Anderson VCEL030516H1 (Not included) |
(2) 4 AWG–300 kcmil |
Anderson VCEL030516H1 (Not included) |
(1) 4 AWG–300 kcmil |
QOGL20 |
SDAG26 |
Mechanical (Included) |
(2) 6–2/0 AWG |
— |
— |
OBS This product is obsolete. |