Setting up demand calculations
Demand is a measure of average consumption over a fixed time interval.
- Navigate to .
- Enter the setup password (default is “0”), then press OK.
- Navigate to .
- Move the cursor to select Power Demand or Current Demand.
- 
               Move the cursor to point to the parameter you want to modify,
                  then press Edit.
               
               Values Description Method Timed Sliding Block Timed Block Timed Rolling Block Cmd Sync Block Cmd Sync Roll Block Clock Sync Block Clock Sync Roll Block Input Sync Block Input Sync Roll Block Thermal Select the appropriate demand calculation method for your needs Interval 0 - 60 Set the demand interval, in minutes. Subinterval 0 - 60 Applies only to rolling block methods. Define how many subintervals the demand interval should be equally divided into. Select Dig Output None Digital Output D1 Digital Output D2 Select which digital output the end of demand interval pulse should be sent to. Select Dig Input None Digital Input S1 Digital Input S2 Applies only to input sync methods. Select which digital input is used to sync the demand. Clock Sync Time 0 - 2359 Applies only to clock sync methods (these synchronize the demand interval to the meter’s internal clock). Define what time of day you want to synchronize the demand, from the start of the day. For example, set this setting to 0730 to synchronize demand at 7:30 AM. 
- Modify the parameter as required, then press OK.
- Move the cursor to point to the next parameter you want to modify, press Edit, make your changes, then press OK.
- Press Yes to save your changes.