MasterPacT NT/NW Trip Curves
MicroLogic 6.0 A/P/H Trip Units
MicroLogic 5.0/6.0 A/P/H Trip Units
MicroLogic 3.0A Trip Units
MicroLogic 2.0A Trip Unit
MasterPacT NT/NW MicroLogic Trip Unit Instantaneous Override Values
ANSI and UL MasterPacT NW/NT MicroLogic Trip Unit Instantaneous Override Values
ANSI CB Model No. |
Inst. Override |
ANSI CB Model No. |
Inst. Override |
UL CB Model No. |
Inst. Override |
UL CB Model No. |
Inst. Override |
---|---|---|---|---|---|---|---|
NW08N1* |
55 |
NW08HA |
None |
NW08N* |
55 |
NW08HF |
90 |
NW08N1 |
None |
NW16HA |
None |
NW08N |
90 |
NW12HF |
90 |
NW0816N1 |
None |
NW20HA |
None |
NW12N |
90 |
NW16HF |
90 |
NW08H1* |
55= |
NW32HA |
None |
NW16N |
90 |
NW20HF |
90 |
NW08H1 |
None |
NW40HA |
None |
NW20N |
90 |
NW25HF |
150 |
NW16H1 |
None |
NW50HA |
None |
NW08H* |
55 |
NW30HF |
150 |
NW20H1 |
None |
NW60HA |
None |
NW08H |
90 |
NW40HF |
170 |
NW32H1 |
None |
NW08HF |
190 |
NW12H |
90 |
NW50HF |
170 |
NW08H2* |
55 |
NW16HF |
190 |
NW16H |
90 |
NW60HF |
170 |
NW08H2 |
None |
NW20HF |
190 |
NW20H |
90 |
NW08HB |
80 |
NW16H2 |
None |
NW32HF |
190 |
NW25H |
150 |
NW12HB |
80 |
NW20H2 |
None |
NW40HF |
190 |
NW30H |
150 |
NW16HB |
80 |
NW32H2 |
None |
NW50HF |
190 |
NW40H |
170 |
NW20HB |
150 |
NW40H2 |
None |
NW60HF |
190 |
NW50H |
170 |
NW25HB |
150 |
NW50H2 |
None |
NW08HC |
80 |
NW60H |
170 |
NW30HB |
150 |
NW60H2 |
None |
NW16HC |
90 |
NW08L* |
55 |
NW40HB |
170 |
NW08H3* |
55 |
NW20HC |
90 |
NW08L |
80 |
NW50HB |
170 |
NW08H3 |
190 |
NW32HC |
270 |
NW08LF |
55 |
NW60HB |
170 |
NW16H3 |
190 |
NW40HC |
270 |
NW12L |
80 |
NT08N* |
55 |
NW20H3 |
190 |
NW50HC |
270 |
NW12LF |
55 |
NT08N |
90 |
NW32H3 |
190 |
NW60HC |
270 |
NW16L |
80 |
NT12N |
90 |
NW40H3 |
190 |
NT08N1* |
None |
NW16LF |
55 |
NT16N |
90 |
NW50H3 |
190 |
NT08N1 |
55 |
NW20L |
150 |
NT08L1 |
22 |
NW60H3 |
190 |
NT08H1* |
55 |
NW20LF |
55 |
NT12L1 |
22 |
NW08L1* |
55 |
NT08H1 |
None |
NW25L |
150 |
NT16L1 |
22 |
NW08L1 |
80 |
NT08L1F |
2 |
NW30L |
150 |
NT08L |
22 |
NW08L1F |
55 |
NT08NA |
None |
NW40L |
170 |
NT08LF |
22 |
NW16L1 |
80 |
NT08LHF |
90 |
NW50L |
170 |
NT12L |
22 |
NW16L1F |
55 |
NT12HF |
90 |
NW60L |
170 |
NT12LF |
22 |
NW20L1 |
80 |
NT16L |
22 |
||||
NW20L1F |
55 |
NOTE: Faults at or above instantaneous
override value will be cleared at 25 msec or less.
|
NT08L |
22 |
|||
NW32L1 |
270 |
NT08LF |
22 |
||||
NW40L1 |
270 |
NT12L |
22 |
||||
NW50L1 |
270 |
NT12LF |
22 |
||||
NW60L1 |
270 |
NT16L |
22 |
IEC MasterPacT NW/NT MicroLogic Trip Unit Instantaneous Override Values
IEC CB Model No. |
Inst. Override |
IEC CB Model No. |
Inst. Override |
IEC CB Model No. |
Inst. Override |
IEC CB Model No. |
Inst. Override |
---|---|---|---|---|---|---|---|
NW08N1 |
None |
NW08H2* |
55 |
NW08L1* |
55 |
NT08H1 |
None |
NW10N1 |
None |
NW08H2 |
190 |
NW08L1 |
80 |
NT10H1 |
None |
NW12N1 |
None |
NW10H2 |
190 |
NW10L1 |
80 |
NT12H1 |
None |
NW16N1 |
None |
NW16H2 |
190 |
NW12L1 |
80 |
NT16H1 |
None |
NW08H1 |
None |
NW20H2 |
190 |
NW16L1 |
80 |
NT08L1 |
22 |
NW10H1 |
None |
NW25H2 |
190 |
NW20L1 |
80 |
NT08H10 |
None |
NW12H1 |
None |
NW32H2 |
190 |
NW08H10 |
None |
NT10H10 |
None |
NW16H1 |
None |
NW40H2 |
190 |
NW10H10 |
None |
NT12H10 |
None |
NW20H1 |
None |
NW40bH2 |
190 |
NW12H10 |
None |
NT16H10 |
None |
NW25H1 |
None |
NW50H2 |
270 |
NW16H10 |
None |
NT08HA |
None |
NW32H1 |
None |
NW63H2 |
270 |
NW20H10 |
None |
NT10HA |
None |
NW40H1 |
None |
NW20H3 |
150 |
NW25H10 |
None |
NT12HA |
None |
NW40bH1 |
None |
NW25H3 |
150 |
NW32H10 |
None |
NT16HA |
None |
NW50H1 |
None |
NW32H3 |
150 |
NW40H10 |
None |
NT08HA10 |
None |
NW63H1 |
None |
NW40H3 |
150 |
NW08NA |
None |
NT10HA10 |
None |
NW08HF |
190 |
NW08HA10 |
None |
NW10NA |
None |
NT12HA10 |
None |
NW10HF |
190 |
NW10HA10 |
None |
NW16NA |
None |
NT16HA10 |
None |
NW12HF |
190 |
NW12HA10 |
None |
||||
NW16HF |
190 |
NW16HA10 |
None |
NOTE: Faults at or above instantaneous
override value will be cleared at 25 msec or less.
|
|||
NW20HF |
190 |
NW20HA10 |
None |
||||
NW25HF |
190 |
NW25HA10 |
None |
||||
NW32HF |
190 |
NW32HA10 |
None |
||||
NW40HF |
190 |
NW40HA10 |
None |