电气辅助装置概述
电气辅助装置
下表给出了可以增设到 ComPact NSX 断路器的电气辅助装置。有关更多信息,请参阅 LVPED217032EN ComPact NSX & NSXm 目录。
电气辅助装置 |
NSX100 |
NSX160 |
NSX250 |
NSX400 |
NSX630 |
|||||
---|---|---|---|---|---|---|---|---|---|---|
1P |
2P |
3P/4P |
1P |
2P |
3P/4P |
1P |
3P/4P |
3P/4P |
3P/4P |
|
OF 或 SD 辅助触点 |
– |
✔ |
✔ |
– |
✔ |
✔ |
– |
✔ |
✔ |
✔ |
SDE 辅助触点 |
– |
– |
✔ |
– |
– |
✔ |
– |
✔ |
✔ |
✔ |
SDx 模块 |
– |
– |
✔ |
– |
– |
✔ |
– |
✔ |
✔ |
✔ |
SDTAM 模块 |
– |
– |
✔ |
– |
– |
✔ |
– |
✔ |
✔ |
✔ |
无线指示辅助装置 |
– |
✔ |
✔ |
– |
✔ |
✔ |
– |
✔ |
✔ |
✔ |
MN 欠压脱扣线圈 |
– |
✔ |
✔ |
– |
✔ |
✔ |
– |
✔ |
✔ |
✔ |
MX 分励脱扣线圈 |
– |
✔ |
✔ |
– |
✔ |
✔ |
– |
✔ |
✔ |
✔ |
BSCM 断路器状态控制模块 |
– |
– |
✔ |
– |
– |
✔ |
– |
✔ |
✔ |
✔ |
NSX 线缆 |
– |
– |
✔ |
– |
– |
✔ |
– |
✔ |
✔ |
✔ |
24 Vdc 电源连接器(1) |
– |
– |
✔ |
– |
– |
✔ |
– |
✔ |
✔ |
✔ |
(1) 带有 MicroLogic 5、6 和 7 脱扣单元 |
电气辅助装置安装演示视频
如要访问与 ComPact NSX100-250 3P 断路器中的电气辅助装置安装有关的演示视频,请单击以下链接:https://youtu.be/zDqRyZHBWr4,将此链接复制粘贴至 Web 浏览器,或者扫描二维码。
ComPact NSX100/160 2P 断路器上电气辅助装置的插槽
名称 |
插槽 |
||
---|---|---|---|
A |
B |
C |
|
OF1(有线或无线) |
✔ |
– |
– |
SD(有线或无线) |
– |
✔ |
– |
MN |
– |
– |
✔ |
MX |
– |
– |
✔ |
ComPact NSX100-250 3P/4P 断路器上电气辅助装置的插槽
下图显示了电气辅助装置安装在盒体中时可使用的插槽。每个插槽只能安装一个辅助装置。有关更多信息,请参阅 LVPED217032EN ComPact NSX & NSXm 目录。
名称 |
插槽 |
备注 |
|||||
---|---|---|---|---|---|---|---|
A |
B |
C |
D |
E |
F |
||
标准远程指示和控制辅件 |
|||||||
OF1(有线或无线) |
✔ |
– |
– |
– |
– |
– |
适用于所有脱扣单元类型和控制类型(拨动手柄、旋转手柄或电动机构)。 |
OF2(有线或无线) |
– |
– |
– |
✔ |
– |
– |
|
SD(有线或无线) |
– |
✔ |
– |
– |
– |
– |
|
SDE(有线或无线) |
– |
– |
✔ |
– |
– |
– |
|
SDV(仅有线) |
– |
– |
– |
– |
– |
✔ |
VigiPacT Add-on 中的指示触点 |
MN |
– |
– |
– |
– |
✔ |
– |
适用于所有脱扣单元类型和控制类型(拨动手柄、旋转手柄或电动机构)。 |
MX |
– |
– |
– |
– |
✔ |
– |
|
经由通讯网络进行的远程指示 |
|||||||
BSCM |
– |
– |
✔ |
✔ |
– |
– |
用于将 BSCM 模块连接到通讯网络。 |
NSX 线缆 |
– |
✔ |
– |
– |
– |
– |
|
NSX 线缆 |
– |
– |
– |
✔ |
– |
– |
用于在没有安装 BSCM 的情况下将 MicroLogic 5、6 和 7 脱扣单元连接到通讯网络。 |
利用 MicroLogic 脱扣单元进行的特定远程指示 |
|||||||
SDx |
✔ |
– |
– |
– |
✔ |
– |
包括供 MicroLogic 4 和 7 脱扣单元使用的 SDV。 |
SDTAM |
✔ |
– |
– |
– |
✔ |
– |
仅适用于带 MicroLogic 2 M 或 6 E-M 电机保护专用型脱扣单元的断路器 |
24 Vdc 电源连接器 |
– |
– |
– |
✔ |
– |
– |
用于将外部电源连接到 MicroLogic 5、6 和 7 脱扣单元。 |
ComPact NSX400-630 3P/4P 断路器上电气辅助装置的插槽
只有 ComPact NSX400-630 断路器才配备有 MicroLogic 脱扣单元。
下图显示了电气辅助装置安装在盒体中时可使用的插槽。有关更多信息,请参阅 LVPED217032EN ComPact NSX & NSXm 目录。
名称 |
插槽 |
备注 |
||||||||
---|---|---|---|---|---|---|---|---|---|---|
A |
B |
C |
D |
E |
F |
G |
H |
I |
||
标准远程指示和控制辅件 |
||||||||||
OF1(有线或无线) |
– |
– |
✔ |
– |
– |
– |
– |
– |
– |
适用于所有脱扣单元类型和控制类型(拨动手柄、旋转手柄或电动机构)。 |
OF2(有线或无线) |
– |
✔ |
– |
– |
– |
– |
– |
– |
– |
|
OF3(有线或无线) |
✔ |
– |
– |
– |
– |
– |
– |
– |
– |
|
OF4(有线或无线) |
– |
– |
– |
– |
– |
– |
✔ |
– |
– |
|
SD(有线或无线) |
– |
– |
– |
– |
– |
– |
– |
– |
✔ |
|
SDE(有线或无线) |
– |
– |
– |
– |
– |
– |
– |
✔ |
– |
|
SDV(仅有线) |
– |
– |
– |
– |
– |
✔ |
– |
– |
– |
VigiPacT Add-on 中的指示触点 |
MN |
– |
– |
– |
– |
✔ |
– |
– |
– |
– |
适用于所有脱扣单元类型和控制类型(拨动手柄、旋转手柄或电动机构)。 |
MX |
– |
– |
– |
– |
✔ |
– |
– |
– |
– |
|
经由通讯网络进行的远程指示 |
||||||||||
BSCM |
– |
– |
– |
– |
– |
– |
✔ |
✔ |
– |
用于将 BSCM 模块连接到通讯网络。 |
NSX 线缆 |
– |
– |
– |
– |
– |
– |
✔ |
– |
– |
|
NSX 线缆 |
– |
– |
– |
– |
– |
– |
– |
– |
✔ |
用于在没有安装 BSCM 的情况下将 MicroLogic 5、6 和 7 脱扣单元连接到通讯网络。 |
利用 MicroLogic 脱扣单元进行的特定远程指示 |
||||||||||
SDx |
– |
– |
– |
✔ |
✔ |
– |
– |
– |
– |
包括供 MicroLogic 4 和 7 脱扣单元使用的 SDV。 |
SDTAM |
– |
– |
– |
✔ |
✔ |
– |
– |
– |
– |
仅适用于带 MicroLogic 2 M 或 6 E-M 电机保护专用型脱扣单元的断路器 |
24 Vdc 电源连接器 |
– |
– |
– |
– |
– |
– |
✔ |
– |
– |
用于将外部电源连接到 MicroLogic 5、6 和 7 脱扣单元。 |
指示触点的操作
下表列出了指示触点(或输出)与执行器和主触点的相关位置。
执行器和主触点位置 |
|||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
ON |
通过以下方式脱扣: |
OFF |
|||||||||
MN/MX |
PT(1) |
脱扣单元(2) |
|||||||||
L |
S 或 So |
I |
R |
G |
|||||||
名称 |
指示触点位置 |
||||||||||
OF |
✔ |
– |
– |
– |
– |
– |
– |
– |
– |
||
SD |
– |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
✔ |
– |
||
SDE |
– |
– |
– |
✔ |
✔ |
✔ |
✔ |
✔ |
– |
||
SDV |
– |
– |
– |
– |
– |
– |
✔ |
– |
– |
||
SDx 输出(3) |
|||||||||||
SD2 |
SDT |
– |
– |
– |
✔ |
– |
– |
– |
– |
– |
|
SD4 |
PAL |
– |
– |
– |
✔ |
– |
– |
– |
– |
– |
|
SDG |
– |
– |
– |
– |
– |
– |
– |
✔ |
– |
||
SDV |
– |
– |
– |
– |
– |
– |
✔ |
– |
– |
||
SDTAM 输出 |
|||||||||||
SD2 |
预合/预分SDT |
– |
– |
– |
✔✔ |
– |
– |
– |
– |
– |
|
SD4 |
接触器控制 |
||||||||||
✔:触点闭合,✔✔:预合输出 (400 ms) |
|||||||||||
(1) PT:脱扣按钮 (2) L:长延时保护 S 或 So:短延时保护 I:瞬时保护 R:VigiPacT Add-on 保护(接地漏电) G:接地故障保护 (3) 可以使用 EcoStruxure Power Commission 软件为 MicroLogic 5、6 和 7 脱扣单元自定义 SDx 输出分配。 |
NO 触点的状态对于以下装置在以下情况下为断开:
-
OF 触点,当断路器处于 O (OFF) 位置时。
-
SD、SDE 和 SDV 触点,当相关功能没有激活时。
无线指示辅助装置的操作
无线指示辅助装置提供的信息与 OF、SD 或 SDE 位置的标准有线辅助触点所提供的信息相同。这些信息远程发送到网关或 Panel Server。
在调试无线指示辅助装置时,用户定义所发送的信息的类型:分闸/合闸或脱扣。