Schematics with MasterPacT MTZ Circuit Breakers
Description
The IFE server is connected to the MasterPacT MTZ circuit breaker with:
-
MicroLogic Active control unit through its ULP port module or COM terminal block.
-
MicroLogic X control unit through its ULP port module.
For more information on the ULP system and its components, refer to the DOCA0093•• ULP (Universal Logic Plug) System - User Guide.
ULP Connection
| NOTICE |
|---|
|
HAZARD OF EQUIPMENT DAMAGE
Failure to follow these instructions can result in equipment damage.
|
All the connection configurations require the RJ45 plug/plug ULP cord.
When the second RJ45 ULP port is not used, it must be closed with an ULP line termination.

|
A |
RJ45 plug/plug ULP cord or circuit breaker BCM ULP cord |
|
B |
ULP line termination |
Connection of the IFE Server to a MasterPacT MTZ Circuit Breaker with MicroLogic X Control Unit
Connect the IFE server to the ULP port module on a MasterPacT MTZ circuit breaker with MicroLogic X control unit by using the ULP cord.

|
A |
IFE Ethernet switchboard server |
|
B |
ULP line termination |
|
C |
RJ45 plug/plug ULP cord |
|
D |
ULP port module |
|
E |
MasterPacT MTZ fixed circuit breaker with MicroLogic X control unit |
Connection of the IFE Server to a MasterPacT MTZ Circuit Breaker with MicroLogic Active Control Unit
Connect the IFE server to the MasterPacT MTZ circuit breaker with MicroLogic Active control unit through:
-
ULP port module and RJ45 plug/plug ULP cord.
-
COM terminal block and circuit breaker BCM ULP cord.
|
A |
IFE Ethernet switchboard server |
|
B |
ULP line termination |
|
C |
RJ45 plug/plug ULP cord |
|
D |
Circuit Breaker BCM ULP cord |
|
E |
ULP port module |
|
F |
COM terminal block |
|
G |
BCIM module |
|
H |
MicroLogic Active control unit |
|
I |
MasterPacT MTZ circuit breaker |