TeSys™ Giga Series is the newest motor control range for large motor and large load applications. This new offering brings greater performance, panel design optimization, and enhanced ease of installation.
TeSys Giga contactors are available in 115 to 800 amperes in both 3-pole and 4-pole configurations. Designers can choose between the standard version and an advanced version. The advanced version provides additional features such as additional coil voltages, lower coil consumption, PLC input control, and a cable memory feature that permits maintenance without removing cables or busbar connections. For lug options, see Lugs and Mounting for TeSys™ Giga Contactors and Overload Relays.
TeSys Giga Contactors — 3-Pole Standard Version
Motor rating (hp) UL 3–phase |
Continuous current (A) |
Standard
version contactors |
||||
---|---|---|---|---|---|---|
200/208 V |
230/240 V |
460/480V |
575/600 V |
48–130 V |
100–250 V |
|
30 |
40 |
75 |
100 |
210 |
||
40 |
50 |
100 |
125 |
230 |
||
50 |
60 |
125 |
150 |
250 |
||
60 |
75 |
150 |
150 |
290 |
||
75 |
100 |
200 |
200 |
340 |
||
100 |
125 |
250 |
300 |
390 |
||
125 |
150 |
300 |
400 |
490 |
||
150 |
200 |
400 |
450 |
630 |
||
250 |
300 |
600 |
700 |
850 |
||
300 |
350 |
700 |
800 |
900 |
TeSys Giga Contactors — 3-Pole Advanced Version
Motor rating (hp) UL 3–phase |
Continuous current (A) |
Standard
version contactors |
|||||
---|---|---|---|---|---|---|---|
200/208 V |
230/240 V |
460/480 V |
575/600 V |
24–48 V[2] |
48–130 V[2] |
200–500 V |
|
30 |
40 |
75 |
100 |
210 |
|||
40 |
50 |
100 |
125 |
230 |
|||
50 |
60 |
125 |
150 |
250 |
|||
60 |
75 |
150 |
150 |
290 |
|||
75 |
100 |
200 |
200 |
340 |
|||
100 |
125 |
250 |
300 |
390 |
|||
125 |
150 |
300 |
400 |
490 |
|||
150 |
200 |
400 |
450 |
630 |
|||
250 |
300 |
600 |
700 |
850 |
— |
||
300 |
350 |
700 |
800 |
900 |
— |
TeSys™ Giga Overload Relays
TeSys™ Giga electronic overload relays provide wide protection flexibility in a limited number of references that cover up to 630 amperes. Alarm and status LEDs inform users in real time. Ground fault, phase imbalance, trip class (5E, 10E, 20E, 30E), and reset type can easily be configured on the device. Units can be directly mounted to the TeSys Giga contactors or can be individually wired.
TeSys™ Giga Reversing Contactors
Components are available for customer assembly of TeSys™ Giga reversing contactors. For example, the following components must be ordered to build a reversing contactor, 200 hp at 460 V, with a 100–250 V AC/DC coil.
Components Required for Building a Reversing Contactor
Description |
Quantity |
Reference |
---|---|---|
Contactors |
2 |
|
Lugs |
1 |
DZ2FJ6 |
Terminal Mounting |
2 |
LA9G3612 |
Auxiliary Contacts |
(included) |
– |
Power Connections |
1 |
LA9G3761 |
Mechanical Interlock |
1 |
LA9G970 |