TeSys™ Ultra Combination Motor Controllers
Refer to Catalog MKTED210011EN
TeSys™ Ultra Motor Starter
The TeSys Ultra motor starter is integrated, making it simple to choose and install. It consists of a control unit snapped in a power base. TeSys Ultra can be configured to fit specific applications as well. Optional accessories include a reverser, a current limiter, predictive maintenance options, and communication options. For detailed information about TeSys Ultra, visit our website. |
Selecting TeSys™ Ultra Motor Starters in Three Steps
Step 1. Select Power Base (Only two different bases up to 32 A)
Control |
Max. Current |
Maximum Horsepower Ratings |
Self-Protected |
|||||
---|---|---|---|---|---|---|---|---|
Three-Phase |
Single-Phase |
|||||||
200 V |
230 V |
460 V |
575 V |
115 V |
230 V |
Catalog |
||
With non-removable screw terminations |
12 |
3 |
3 |
7.5 |
10 |
0.5 |
2 |
|
32 |
10 |
10 |
20 |
25 |
2 |
5 |
||
Without screw terminations |
12 |
3 |
3 |
7.5 |
10 |
0.5 |
2 |
|
32 |
10 |
10 |
20 |
25 |
2 |
5 |
Step 2. Select Control Unit [2]
Setting Range |
Standard |
Advanced |
Advanced |
Advanced |
---|---|---|---|---|
0.15–0.6 |
LUCAX6●● |
LUCBX6●● |
LUCCX6●● |
LUCDX6●● |
0.3–1.4 |
LUCA1X●● |
LUCB1X●● |
LUCC1X●● |
LUCD1X●● |
1.25–5.0 |
LUCA05●● |
LUCB05●● |
LUCC05●● |
LUCD05●● |
3–12 |
LUCA12●● |
LUCB12●● |
LUCC12●● |
LUCD12●● |
4.5–18 |
LUCA18●● |
LUCB18●● |
LUCC18●● |
LUCD18●● |
8–32 |
LUCA32●● |
LUCB32●● |
LUCC32●● |
LUCD32●● |
Voltage Codes
Volts |
24 |
110–240 |
---|---|---|
DC |
BL [4] |
— |
AC |
B |
— |
DC or AC |
— |
FU |
Step 3. Select Auxiliary Contacts (optional)
Terminals |
Contact |
Contact Normal |
Contact State for Each Mode [5] |
Catalog |
||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Off |
Ready |
Run |
Short |
Overload Trip |
Overload Trip |
|||||||||||
Auxiliary Contact |
Auxiliary Contact Blocks |
|||||||||||||||
Screw |
Ready condition |
N.O. |
O |
I |
I |
O |
O |
I |
||||||||
Fault condition |
N.C. |
I |
I |
I |
O |
O |
I |
|||||||||
Screw |
Ready condition |
N.O. |
O |
I |
I |
O |
O |
I |
||||||||
Fault condition |
N.O. |
O |
O |
O |
I |
I |
O |
|||||||||
Auxiliary Contact Function Modules |
||||||||||||||||
Screw |
Pole state |
2 N.O. |
O |
O |
I |
O |
O |
|||||||||
Screw |
Pole state |
1 N.O. and 1 N.C. |
O |
I |
O |
I |
I |
O |
O |
I |
O |
I |
||||
Screw |
Pole state |
2 N.C. |
1 |
I |
O |
I |
I |
Accessories
Accessory |
Quick Description |
For details & selection, see: |
---|---|---|
Current limiter |
Increases the breaking capacity to 130 kA @ 460 V and to 65 kA @ 575 V |
|
Reverser |
Stacked or side mounted (LU6MB0●●● only) |
|
Line phase barrier |
Required for use as a self-protected combination starter (UL 508 Type E) |
|
Multifunction control unit |
Has functions for monitoring and predictive maintenance |
|
Function modules |
Fault differentiation, thermal overload, motor load indication |
|
Communication modules |
Integrates into existing networks, major portocols are available |
|
Soft starter + TeSys Ultra |
Use Altistart U01soft starter with TeSys Ultra |
|
Powerbus |
Use TeSys Ultra with a prewired system |
|
Configuration and connection accessories |
SoMove software, bus bar, external handle |
Accessories: Power Base and Plug-in Accessories to Accessories Dimensions: TeSys™ Ultra Starter Dimensions Overload Relays: TeSys™ K Overload Relays Accessories: Aux Contact Blocks Dimensions: TeSys K Contactor Dimensions |
Control Units and Functions
Control Units and Functions
Standard |
Advanced |
Multifunction |
|||
Reference |
LUCA |
LUCB |
LUCC |
LUCD |
LUCM |
Protection type |
|||||
Class 10 |
|||||
Class 20 |
|||||
Class 5–30 |
|||||
Single Phase: LUCC Class 10 only |
|||||
Protection functions |
|||||
Short circuit |
|||||
Over current |
|||||
Thermal overload |
|||||
Phase loss |
|||||
Phase imbalance |
|||||
Ground fault |
|||||
Underload, long start, jam |
|||||
Control functions |
|||||
Manual reset |
|||||
Automatic or local/remote reset |
|||||
Fault differentiation |
|||||
Thermal alarm |
|||||
Motor load display |
|||||
Fault history |
|||||
Alarm threshold adjustment |
|||||
Tripping test |
|||||
= built-in the control unit |
|||||
= works with the related function modules (see Line Phase Barrier, Reverser) |
Power Base and Plug-in Accessories
TeSys™ Reversing Starters
Power Base with Reversing Unit assembled under the base
Control Connection |
Max. Current |
Maximum Horsepower Ratings |
Self-Protected Catalog |
|||||
---|---|---|---|---|---|---|---|---|
Three-Phase |
Single-Phase |
|||||||
200 V |
230 V |
460 V |
575 V |
115 V |
230 V |
|||
With screw terminations |
12 |
3 |
3 |
7.5 |
10 |
1.5 |
2 |
LU2B12[7] |
32 |
10 |
10 |
20 |
25 |
2 |
5 |
LU2B32[7] |
Select Control Unit Options[8][9]
Setting Range |
Standard |
Advanced |
Advanced |
Advanced |
---|---|---|---|---|
0.15–0.6 |
LUCAX6●● |
LUCBX6●● |
LUCCX6●● |
LUCDX6●● |
0.3–1.4 |
LUCA1X●● |
LUCB1X●● |
LUCC1X●● |
LUCD1X●● |
1.25–5.0 |
LUCA05●● |
LUCB05●● |
LUCC05●● |
LUCD05●● |
3–12 |
LUCA12●● |
LUCB12●● |
LUCC12●● |
LUCD12●● |
4.5–18 |
LUCA18●● |
LUCB18●● |
LUCC18●● |
LUCD18●● |
8–32 |
LUCA32●● |
LUCB32●● |
LUCC32●● |
LUCD32●● |
TeSys™ Ultra Accessories
Current Limiter [12][13]
Function Modules [12][14]
Module |
Description |
For use with: |
Operation |
Catalog |
---|---|---|---|---|
Fault differentiation: |
Provides indication between an overload trip and a short circuit trip. |
Advanced control units only |
24–250 Vac/Vdc |
|
Thermal overload |
Signals when the motor current reaches 1.05 of the full load setting on the control unit. |
Advanced control units only |
24–250 Vac/Vdc |
|
Motor load indication |
Provides a signal proportional to the average currents in the three phases divided by the full load current setting of the control unit. The output corresponds to a load status of 0–2 times the full load setting of the control unit. |
Advanced or multi-function control units |
4–20 mA |
|
Parallel wiring |
Provides a convenient way to reduce control wiring and allow for connecting starters to a communications network by providing 24 Vdc for the starters. |
Advanced or multi-function control units (24 Vdc only) and LU9BN11C or LU9MRC prewired connector |
LU9G02 |
Accessories
Communication Modules [12][15]
Communication modules
allow the TeSys Ultra starter to be connected directly to the network.
They are for use with advanced or multi-function control units (24
Vdc only) and require a separate 24 Vdc power supply.
Module |
Prewired Connector |
Catalog Number |
---|---|---|
Modbus™ Communication |
LU9BN11C or LU9MRC |
|
CANopen Communication |
LU9BN11L or LU9MRL |
|
Profibus Communication |
LU9BN11L or LU9MRL |
|
DeviceNet™ Communication |
LU9BN11L or LU9MRL |
TeSys™ Ultra Cabling Accessories—Power Bus Bars
Description |
Application |
Pitch |
Standard Pack |
Catalog Number |
---|---|---|---|---|
3-Pole, 63 A Bus Bar |
For feeding 2 TeSys Ultra controllers |
45 |
1 |
|
54 |
1 |
|||
72 |
1 |
|||
For feeding 3 TeSys Ultra controllers |
45 |
1 |
||
54 |
1 |
|||
For feeding 4 TeSys Ultra controllers |
45 |
1 |
||
54 |
1 |
|||
72 |
1 |
|||
For feeding 5 TeSys Ultra controllers |
54 |
1 |
||
Terminal blocks | Top feed for use with bus bars | — | 1 |
Control Circuit Accessories [16] for placement on power base.
Accessory |
Application |
Technical Data |
Mounting |
Catalog |
|
---|---|---|---|---|---|
Control circuit contact block |
Switches control circuit power via LUB● handle (NEC430-74 compliance) |
5 A at 600 Vac |
Side mounting to LUB● |
||
Through-the-door |
Use to enclose TeSys LUB● only. |
NEMA 1, 12, 3R, 4, 4X |
Kit |
||
Control circuit filters |
Use with electronic or triac output controllers |
Up to 150 Vac max. |
Directly to coil terminals |
Non-reversing |
|
Reversing |
|||||
Pre-wired connector |
Central control when using communication modules |
See Communication Modules for usage. |
Lower power terminals to communication module. |
Non-reversing |
|
Reversing |