Two-Component Motor Circuit Solutions to 520 amps
Refer to Catalog MKTED210011EN
Two-Component Motor Circuit Solutions to 520 Amps
Simplify design, panel space and installation with TeSys™ high SCCR solution that use only two components that make up an entire branch circuit up to 520 amps. These two-component solutions are UL compliant using either a Type F combination motor controller rating or a UL 489 rating. For additional solutions and ratings, see Motor Control Solutions for North America data bulletin 8536DB0901.
Quick selection table for TeSys™ two–component motor circuit solutions
200 V 3P |
230 V 3P |
460 V 3P |
GV Ref |
Overload Dial Range (A) |
Contactor Ref [1] |
SCCR 480Y as applied with specified protection |
|||
---|---|---|---|---|---|---|---|---|---|
HP |
FLA[2] |
HP |
FLA[2] |
HP |
FLA[2] |
||||
— | — | — | — | 1/2 | 1.1 | 1 to 1.6 | 65 kA[3] | ||
— | — | — | — | 3/4 | 1.6 | 1 to 1.6 | 65 kA[3] | ||
1/2 | 2.5 | 1/2 | 2.2 | 1 | 2.1 | 1.6 to 2.5 | 65 kA[3] | ||
— | — | — | — | 1 1/2 | 3 | 2.5 to 4 | 65 kA[3] | ||
3/4 | 3.7 | 3/4 | 3.2 | 2 | 3.4 | 2.5 to 4 | 65 kA[3] | ||
1 | 4.6 | 1 | 4.2 | 3 | 4.8 | 4 to 6.3 | 65 kA[3] | ||
— | — | 1 1/2 | 6 | — | — | 4 to 6.3 | 65 kA[3] | ||
1 1/2 | 6.9 | 2 | 6.8 | — | — | 6 to 10 | 65 kA[3] | ||
2 | 7.8 | — | — | 5 | 7.6 | 6 to 10 | 65 kA[3] | ||
— | — | 3 | 9.6 | — | — | 9 to 14 | 50 kA[4] | ||
3 | 11 | — | — | 7 1/2 | 11 | 9 to 14 | 50 kA[4] | ||
— | — | — | — | 10 | 14 | 9 to 14 | 50 kA[4] | ||
5 | 17.5 | 5 | 15.2 | — | — | 13 to 18 | 50 kA[4] | ||
— | — | 7 1/2 | 22 | 15 | 21 | 17 to 23 | 50 kA[4] | ||
7 1/2 | 25.3 | — | — | — | — | 20 to 25 | 50 kA[4] | ||
— | — | 10 | 28 | 20 | 27 | 23 to 32 | 65 kA[5] | ||
10 | 32.2 | — | — | 25 | 34 | 30 to 40 | 65 kA[5] | ||
— | — | 15 | 42 | 30 | 40 | 37 to 50 | 65 kA[5] | ||
15 | 48 | 20 | 54 | 40 | 52 | 48 to 65 | 65 kA[5] | ||
20 | 62.1 | 25 | 68 | 50 | 65 | 65 to 115 | 65 kA | ||
25 | 78.2 | 30 | 80 | 60 | 77 | 65 to 115 | 65 kA | ||
30 | 92 | — | — | — | — | 65 to 115 | 65 kA | ||
— | — | 40 | 104 | 75 | 96 | 58 to 130 | 65 kA | ||
40 | 120 | — | — | — | — | 58 to 130 | 65 kA | ||
— | — | 50 | 130 | 100 | 124 | 114 to 217 | 65 kA | ||
50 | 150 | 60 | 154 | 125 | 156 | 114 to 217 | 100 kA | ||
60 | 177 | 75 | 192 | 150 | 180 | 114 to 217 | 100 kA | ||
75 | 221 | 100 | 248 | 200 | 240 | 190 to 348 | 100 kA | ||
100 | 285 | 125 | 312 | 250 | 302 | 190 to 348 | 100 kA | ||
125 | 359 | 150 | 360 | 300 | 361 | 312 to 520 | 65 kA | ||
150 | 414 | 200 | 480 | 400 | 477 | 312 to 520 | 65 kA | ||
200 | 552 | — | — | 500 | 590 | 312 to 520 | 100 kA |