Email Events
Description
The
page allows the selection of the events to notify through email among a list of events.CAUTION |
---|
EQUIPMENT INCOMPATIBILITY OR INOPERABLE EQUIPMENT
Do not rely solely on the notification of the emails for
maintaining your equipment.
Failure to follow these instructions can result in injury or equipment damage.
|
The list of events displayed contain only applicable events related to the MasterPacT MTZ circuit breaker with:
-
with MicroLogic X control unit and EIFE interface
-
with 1 or 2 optional IO modules connected to the ULP port module.
Parameter |
Description |
---|---|
|
List of events for configuration |
|
A check box to enable to add events. |
|
Allows you to choose from a list of email recipients. NOTE: You can choose a maximum
of 12 recipients.
|
|
Allows you to enter a custom text. NOTE: You can enter a maximum of 63 characters in the
custom text area.
|
Events from MasterPacT MTZ Circuit Breaker
Device connected |
Events |
---|---|
MasterPacT MTZ circuit breaker with MicroLogic control units |
Ir trip |
Isd trip |
|
Ii trip |
|
Ig trip |
|
IΔn trip |
|
Ultimate self-protection trip (SELLIM) |
|
Self diagnostic trip |
|
Ultimate self-protection trip (DIN/DINF) |
|
IΔn/Ig test trip |
|
Undervoltage on 1 phase trip |
|
Overvoltage on 1 phase trip |
|
Reverse power trip |
|
Undervoltage on all 3 phases trip |
|
Overvoltage on all 3 phases trip |
|
Optional protection trip |
|
@new D1
IDMTG Ig trip |
|
Ultimate self-protection (DIN/DINF) operate |
|
Ultimate self-protection (SELLIM) operate |
|
Thermal memory reset order |
|
Ir prealarm (I > 90% Ir) |
|
Ir start (I > 105% Ir) |
|
Ir operate |
|
Isd start |
|
Isd operate |
|
Ii operate |
|
Ig alarm |
|
Ig start |
|
Ig operate |
|
IΔn alarm |
|
IΔn start |
|
IΔn operate |
|
Undervoltage on 1 phase start |
|
Undervoltage on 1 phase operate |
|
Undervoltage on all 3 phases start |
|
Undervoltage on all 3 phases operate |
|
Overvoltage on 1 phase start |
|
Overvoltage on 1 phase operate |
|
Overvoltage on all 3 phases start |
|
Overvoltage on all 3 phases operate |
|
Reverse Power start |
|
Reverse Power operate |
|
MasterPacT MTZ circuit breaker with MicroLogic control units |
ERMS engaged |
ERMS engaged for more than 24 hours |
|
ESM (ERMS switch module) self diagnostic alarm |
|
Communication lost with ESM (ERMS switch module) |
|
Request to unlock ERMS by Smartphone |
|
B curve active |
|
Optional protections inhibited by IO |
|
Circuit breaker opened |
|
Circuit breaker closed |
|
Closing order sent to XF |
|
Opening order sent to MX |
|
Circuit Breaker did not open or close |
|
Manual mode enabled |
|
Local mode enabled |
|
Allow control by Digital input is disabled (by EcoStruxure Power Commission ) |
|
Closing inhibited by communication |
|
Closing inhibited through IO module |
|
@new D1
IDMTG Ig start |
|
@new D1
IDMTG Ig operate |
|
Alarm reset |
|
M2C output 1 is forced |
|
M2C output 2 is forced |
|
Protection settings change by display enabled |
|
Remote protection settings change enabled |
|
Protection settings changed by display |
|
Protection settings changed by Bluetooth/USB/IFE |
|
Communication lost with IO#1 module |
|
Communication lost with IO#2 module |
|
Config error IO/CU: dual settings or inhibit cls. |
|
Config error IO/CU: optional protection Inhibit |
|
Config. error IO and CU - Local/Remote mode |
|
Date and time set |
|
Digital module license installed |
|
Digital module license uninstalled |
|
Digital module license expired |
|
Digital module license rejected |
|
Digital module License expires in 30 days |
|
Digital module License expires in 20 days |
|
Digital module License expires in 10 days |
|
Connection on USB port |
|
Injection test in progress |
|
Ig function inhibited for test propose |
|
Test aborted by user |
|
MasterPacT MTZ circuit breaker with MicroLogic control units |
Ig protection in OFF mode |
Control unit self test major malfunction 1 |
|
Control unit self test major malfunction 2 |
|
Control unit self test major malfunction 3 |
|
Control unit self test major malfunction 4 |
|
Control unit self test major malfunction 5 |
|
Internal current sensor disconnected |
|
External neutral current sensor disconnected |
|
Internal Current Power Supply (CPS) sensors malfunction |
|
Partial internal Current Power Supply (CPS) sensors malfunction |
|
Partial internal Current Power Supply (CPS) sensors major malfunction |
|
Earth leakage (Vigi) sensor disconnected |
|
Protection settings reset to factory values |
|
Protection settings no accessible # 1 |
|
Protection settings no accessible # 2 |
|
Protection settings no accessible # 3 |
|
Protection settings no accessible # 4 |
|
Protection settings no accessible # 5 |
|
Control unit self test # 1 |
|
Control unit self test # 2 |
|
Control unit self test # 3 |
|
Control unit self test # 4 |
|
Control unit self test # 5 |
|
Invalid measurement and optional protection # 1 |
|
Invalid measurement and optional protection # 2 |
|
Invalid measurement and optional protection # 3 |
|
Invalid optional protection self test |
|
NFC invalid communication #1 |
|
NFC invalid communication #2 |
|
NFC invalid communication #3 |
|
Invalid display screen or wireless communication # 1 |
|
Invalid display screen or wireless communication # 2 |
|
Invalid display screen or wireless communication # 3 |
|
Loss of IEEE 802.15.4 communication |
|
Loss of Bluetooth communication |
|
Replace Battery |
|
No battery detected |
|
Control Unit alarm reset |
|
Self diagnostic test - firmware |
|
Unable to read sensor plug |
|
Invalid Control Unit factory config #1 |
|
Invalid Control Unit factory config #2 |
|
Critical hardware modules discrepancy |
|
MasterPacT MTZ circuit breaker with MicroLogic control units |
Critical firmware modules discrepancy |
Non-critical hardware modules discrepancy |
|
Non-critical firmware modules discrepancy |
|
Firmware discrepancy within control unit |
|
IΔn/Ig test - no trip |
|
IΔn/Ig test button pressed |
|
ZSI test in progress |
|
Contact wear is above 60% Check contacts |
|
Contact wear is above 95% Plan for replacement |
|
Contacts 100% worn out CB needs to be replaced |
|
Less than 20% CB operation remaining |
|
CB has reached the max number of operations |
|
Invalid self test - MX1 shunt trip |
|
MX1 shunt trip not detected |
|
MCH charging operations above threshold |
|
MCH has reached the max number of operations |
|
Invalid self test - XF shunt close |
|
XF shunt close not detected |
|
Invalid self test - MN undervoltage release |
|
MN undervoltage release not detected |
|
Voltage loss on MN undervoltage release |
|
Communication loss on MN undervoltage release |
|
Invalid self test - MX2 shunt trip |
|
MX2 shunt trip not detected |
|
Presence of external 24V power supply |
|
Loss of voltage and CB is closed |
|
Events in history log have been erased |
|
Reset Min/Max currents |
|
Reset Min/Max voltages |
|
Reset Min/Max power |
|
Reset Min/Max frequency |
|
Reset Min/Max harmonics |
|
Reset Min/Max power factor |
|
Reset current demand |
|
Reset power demand |
|
Reset energy counters |
|
Bluetooth communication enabled |
|
ZigBee communication enabled |
|
Connection on Bluetooth port |
|
Underfrequency trip |
|
Overfrequency trip |
|
Underfrequency start |
|
Overfrequency start |
|
MasterPacT MTZ circuit breaker with MicroLogic control units |
Underfrequency operate |
Overfrequency operate |
|
Diagnostic data (link) |
|
Last event sequence number |
|
Voltage release operation counter is above alarm threshold |
|
Voltage release has reached the max number of operations |
|
MX2 voltage release operation counter above alarm threshold |
|
MX2 voltage release reached the max number of operations |
|
MX1 voltage release operation counter above alarm threshold |
|
MX1 voltage release reached the max number of operations |
|
MN undervoltage release operation counter is above alarm threshold |
|
MN undervoltage voltage release reached the max number of operations |
|
Schedule basic maintenance within one month |
|
Schedule standard maintenance within one month |
|
Schedule manufacturer maintenance within three months |
|
After 6 months of commissioning protection settings still set to factory default |
|
Remaining service life of MicroLogic below alarm threshold |
|
MicroLogic control unit reached the max service life |
|
Last modification of protection settings not completely applied |
|
Frequency based protection |
|
IDMTL long time trip |
|
IDMTL long time start |
|
IDMTL long time operate |
|
Forward directional overcurrent trip |
|
Reverse directional overcurrent trip |
|
Forward directional overcurrent start |
|
Reverse directional overcurrent start |
|
Forward directional overcurrent operate |
|
Reverse directional overcurrent operate |
|
Forward directional overcurrent received |
|
Reverse directional overcurrent received |
|
Forward directional overcurrent sent |
|
Reverse directional overcurrent sent |
Events from IO Modules
Device connected |
Events |
---|---|
IO module 1 |
Threshold overrun on Input 1 counter (#1) |
Threshold overrun on Input 2 counter (#1) |
|
Threshold overrun on Input 3 counter (#1) |
|
Threshold overrun on Input 4 counter (#1) |
|
Threshold overrun on Input 5 counter (#1) |
|
Threshold overrun on Input 6 counter (#1) |
|
Switchboard Temperature threshold 1(#1) |
|
Switchboard Temperature threshold 2 (#1) |
|
Switchboard Temperature threshold 3 (#1) |
|
IO module Failure (STOP mode) (#1) |
|
IO module Failure (ERROR mode) (#1) |
|
IO module 2 |
Threshold overrun on Input 1 counter (#2) |
Threshold overrun on Input 2 counter (#2) |
|
Threshold overrun on Input 3 counter (#2) |
|
Threshold overrun on Input 4 counter (#2) |
|
Threshold overrun on Input 5 counter (#2) |
|
Threshold overrun on Input 6 counter (#2) |
|
Switchboard Temperature threshold 1(#2) |
|
Switchboard Temperature threshold 2 (#2) |
|
Switchboard Temperature threshold 3 (#2) |
|
IO module Failure (STOP mode) (#2) |
|
IO module Failure (ERROR mode) (#2) |
|
IO module 1 or IO module 2 |
Discrepancy with ERMS orders |
Earth leakage trip signal contact (SDV) alarm |
|
Control voltage presence contact alarm |
|
Surge protection status contact alarm |
|
Surge failure contact alarm |
|
Switch disconnector ON/OFF indication alarm contact (OF) |
|
Fuse blown indication contact alarm |
|
Emergency Stop alarm |
|
Switchboard temperature contact alarm |
|
Switchboard ventilation contact alarm |
|
Switchboard door contact alarm |
Events from EIFE Interface
Device connected |
Events |
---|---|
EIFE interface |
Disconnection of the circuit breaker from cradle is overdue |
Remaining service life of cradle is below alarm threshold |
|
Cradle has reached its maximum number of operations |
|
New MicroLogic unit has been detected |
|
Cradle Position Discrepancy |
|
Cradle connected position status (CE) |
|
Cradle disconnected position status (CD) |
|
Cradle test position status (CT) |
|
Cradle replacement within 6 month |
|
Regrease cradle to be performed |
|
New MicroLogic unit has been detected |
|
Drawer Position Discrepancy |
|
Cradle Connected Contact Change |
|
Cradle Disconnected Contact Change |
|
Cradle Test Contact Change |
|
@new D1
Password of service user profile for EIFE interface was changed |
|
@new D1
Password of engineer user profile for EIFE interface was changed |
|
@new D1
Password of operator user profile for EIFE interface was changed |
|
@new D1
Password of administrator user profile for EIFE interface was changed |
|
@new D1
All the passwords for EIFE interface were changed |