Time-Stamped Information
General Description
The time-stamped information enables the user to know all the dates related to important information.
The time-stamped information table describes:
-
the current date
-
the last current demand and corresponding dates
-
the last power demand and corresponding dates
-
the last reset and corresponding dates
Current Date
Address |
Register |
RW |
X |
Unit |
Type |
Range |
Description |
---|---|---|---|---|---|---|---|
0x2327–0x232A |
9000–9003 |
R |
– |
– |
XDATE |
– |
Current date of the protection manager |
Last Current Demand
Address |
Register |
RW |
X |
Unit |
Type |
Range |
Description |
---|---|---|---|---|---|---|---|
0x0BBC–0x0BBE |
3005–3007 |
R |
– |
– |
DATE |
– |
Date of last current demand maximum I1 (register 2204) |
0x0BBF–0x0BC1 |
3008–3010 |
R |
– |
– |
DATE |
– |
Date of last current demand maximum I2 (register 2205) |
0x0BC2–0x0BC4 |
3011–3013 |
R |
– |
– |
DATE |
– |
Date of last current demand maximum I3 (register 2206) |
0x0BC5– 0x0BC7 |
3014–3016 |
R |
– |
– |
DATE |
– |
Date of last current demand maximum on the neutral (register 2207)(1) |
(1) Value is not available when the system type in register 3314 is 31 or 40. Refer to System Type. |