PowerLogic P7 Motor and Generator Applications
PowerLogic P7 Motor and Generator Applications
Protection Functions for Motor and Generator Applications
| Protection Functions |
IEC 61850 Logical node |
ANSI code |
Motor application (stages instantiated) |
Generator application (stages instantiated) |
Functional routing support |
||
|---|---|---|---|---|---|---|---|
| Level 0 | Level 1 | Level 0 | Level 1 | ||||
|
Current protection |
|||||||
|
Protection trip conditioning |
PTRC |
86 |
1 | 2 | 1 | 4 |
FALSE |
|
Phase direction |
PHRDIR |
67 |
● |
1 |
● |
1 |
TRUE |
|
Phase overcurrent |
PHPTOC |
50/51 |
2 | 2 | 2 | 4 |
TRUE |
|
Ground direction |
EFRDIR |
67N |
● |
1 |
● |
1 |
TRUE |
|
Ground fault overcurrent |
EFPTOC |
50N/51N |
2 | 2 | 2 | 4 |
TRUE |
|
Sensitive ground fault overcurrent |
VSEFPTOC |
50SG/51SG |
2 | 2 | 2 | 2 |
TRUE |
|
Negative sequence overcurrent |
NPSPTOC |
46 |
2 | 2 | 2 | 2 |
TRUE |
|
Inrush detection |
IDPHAR |
68ID |
2 | 2 |
● |
2 |
TRUE |
|
Selective overcurrent logic (SOL) |
SOLGAPC |
N/A |
1 | 1 | 1 | 1 |
FALSE |
|
Phase undercurrent |
PHPTUC |
37 |
2 | 2 |
— |
— |
TRUE |
|
Voltage dependent overcurrent |
PHPVOC |
51V |
— | — | 1 | 2 |
TRUE |
|
Sensitive directional earthfault |
PSDE |
32N |
● |
2 |
● |
2 |
TRUE |
|
Ground admittance |
EFPADM |
21N |
— | — |
● |
2 |
TRUE |
|
Voltage protection |
|||||||
|
Undervoltage |
PHPTUV |
27 |
2 | 2 | 2 | 2 |
TRUE |
|
Overvoltage |
PHPTOV |
59 |
2 | 2 | 2 | 2 |
TRUE |
|
Positive phase sequence undervoltage |
PPSPTUV |
27D |
1 | 1 | 0 | 2 |
TRUE |
|
Positive phase sequence overvoltage |
PPSPTOV |
N/A |
● |
2 |
● |
2 |
TRUE |
|
Neutral overvoltage |
EFPTOV |
59N |
1 | 3 | 1 | 2 |
TRUE |
|
Negative phase sequence overvoltage |
NPSPTOV |
47 |
1 | 1 | 1 | 1 |
TRUE |
|
Inter-turn overvoltage |
ITPTOV |
59IT |
— | — |
● |
1 |
TRUE |
|
Overfluxing |
PVPH |
24 |
— | — |
● |
1 |
TRUE |
|
Frequency protection |
|||||||
|
Overfrequency |
PTOF |
81O |
● |
2 | 2 | 2 |
FALSE |
|
Underfrequency |
PTUF |
81U |
● |
4 | 4 | 4 |
FALSE |
|
Frequency supervised ROCOF |
PFRC |
81R |
● |
4 |
● |
4 |
FALSE |
|
Differential protection |
|||||||
|
High impedance differential |
HIZPDIF |
87/64REF |
● |
1 |
● |
1 |
TRUE |
|
Biased differential protection |
PHPDIF |
87 |
● |
1 |
● |
1 |
TRUE |
|
Low impedance differential |
RGFPDIF |
64REF |
● |
1 |
● |
1 |
TRUE |
|
Temperature protection |
|||||||
|
Motor thermal overload |
THMPTTR |
49 |
1 | 1 | 1 | 1 |
TRUE |
|
Overtemperature |
STMP |
38/49T |
8 | 8 | 8 | 8 |
FALSE |
|
Negative phase sequence thermal overload |
NPSPTTR |
49N |
1 | 1 | 1 | 1 |
TRUE |
|
Motor protection |
|||||||
|
Motor monitoring |
ZMOT |
N/A |
1 | 1 | — | — |
TRUE |
|
Motor start-up supervision, locked rotor |
PMSS |
48 |
1 | 1 | — | — |
TRUE |
|
Locked rotor |
JAMPTOC |
51LR |
1 | 1 | — | — |
TRUE |
|
Motor restart inhibition |
PMRI |
66 |
1 | 1 | — | — |
FALSE |
|
Voltage check |
VCPTUV |
47 |
1 | 1 | — | — |
TRUE |
|
Generator protection |
|||||||
|
Third harmonic undervoltage |
STPTUV |
27TN |
— | — | 0 | 1 |
TRUE |
|
Inter-turn protection based on split phase |
ITPDIF |
87G |
— | — |
● |
1 |
TRUE |
|
Inadvertent energization |
IEPIOC |
50/27 |
— | — | 1 | 1 |
TRUE |
|
Speed protection |
|||||||
|
Overspeed |
POVS |
12 |
0 | 2 | 0 | 2 |
FALSE |
|
Underspeed |
PZSU |
14 |
0 | 2 | 0 | 2 |
FALSE |
|
Speed detection |
TRTN |
N/A |
0 | 1 | 0 | 1 |
FALSE |
|
Distance/Impedance protection |
|||||||
|
Field failure |
FFPDIS |
40 |
● |
1 |
● |
1 |
TRUE |
|
Underimpedance |
UZPDIS |
21 |
— | — |
● |
1 |
TRUE |
|
Out of step |
OOSPPAM |
78 |
● |
1 |
● |
1 |
TRUE |
|
Power protection |
|||||||
|
Overpower |
PPDOP |
32P |
— | — | 2 | 4 |
FALSE |
|
Reactive overpower |
QPDOP |
32Q |
2 | 2 | 1 | 2 |
FALSE |
|
Underpower |
PPDUP |
37P |
2 | 2 | 1 | 1 |
FALSE |
Control Functions for Motor and Generator Applications
| Control Functions |
IEC 61850 Logical node |
ANSI code |
Motor application (stages instantiated) |
Generator application (stages instantiated) |
Functional routing support |
||
|---|---|---|---|---|---|---|---|
| Level 0 | Level 1 | Level 0 | Level 1 | ||||
|
Circuit breaker proxy |
CBXCBR |
N/A |
1 | 1 | 1 | 1 |
TRUE |
|
Circuit breaker control |
CBCSWI |
N/A |
1 | 1 | 1 | 1 |
FALSE |
|
Circuit breaker interlocking |
CBCILO |
N/A |
1 | 1 | 1 | 1 |
FALSE |
|
Circuit breaker failure |
RBRF |
50BF |
1 | 1 | 1 | 1 |
TRUE |
|
Switch proxy |
SWXSWI |
N/A |
5 | 9 | 5 | 9 |
FALSE |
|
Switch control |
SWCSWI |
N/A |
5 | 9 | 5 | 9 |
FALSE |
|
Switch interlocking |
SWCILO |
N/A |
5 | 9 | 5 | 9 |
FALSE |
|
Synchro-check |
RSYN |
25 |
— | — | 1 | 1 |
TRUE |
Monitoring Functions for Motor and Generator Applications
| Monitoring Functions |
IEC 61850 Logical node |
ANSI code |
Motor application (stages instantiated) |
Generator application (stages instantiated) |
Functional routing support |
||
|---|---|---|---|---|---|---|---|
| Level 0 | Level 1 | Level 0 | Level 1 | ||||
|
CT supervision |
CTSSCTR |
60 |
1 | 2 | 1 | 2 |
FALSE |
|
VT supervision |
VTSSVTR |
60FL |
1 | 1 | 1 | 2 |
FALSE |
|
Circuit breaker supervision |
CBSCBR |
N/A |
1 | 1 | 1 | 1 |
TRUE |
|
Switch monitoring |
SWSSWI |
N/A |
5 | 9 | 5 | 9 |
FALSE |
|
DC battery voltage monitoring |
ZBAT |
N/A |
1 | 1 | 1 | 1 |
FALSE |
|
Bay dead |
PDGAPC |
N/A |
1 | 1 | 1 | 1 |
TRUE |
|
Voltage variation |
QVVR |
N/A |
● |
1 |
● |
1 |
TRUE |
Logs and Records for Motor and Generator Applications
| Logs and Records |
IEC 61850 Logical node |
ANSI code |
Motor application (stages instantiated) |
Generator application (stages instantiated) |
Functional routing support |
||
|---|---|---|---|---|---|---|---|
| Level 0 | Level 1 | Level 0 | Level 1 | ||||
|
Sequence of event record |
GENGLOG |
N/A |
1 | 1 | 1 | 1 |
FALSE |
|
Disturbance record |
DRRDRE |
N/A |
1 | 1 | 1 | 1 |
FALSE |
|
Fault record |
TCRGLOG |
N/A |
1 | 1 | 1 | 1 |
FALSE |
|
Operation log |
GENGLOG |
N/A |
1 | 1 | 1 | 1 |
FALSE |
|
Power quality record |
PQGLOG |
N/A |
● |
1 |
● |
1 |
FALSE |
Measurement Functions for Motor and Generator Applications
| Measurement functions |
IEC 61850 Logical node |
ANSI code |
Motor application (stages instantiated) |
Generator application (stages instantiated) |
Functional routing support |
||
|---|---|---|---|---|---|---|---|
| Level 0 | Level 1 | Level 0 | Level 1 | ||||
|
CT group measurement |
|||||||
|
3ph current |
VECAMMXU |
N/A |
1 | 2 | 1 | 2 |
FALSE |
|
3ph RMS current |
RMSAMMXU |
N/A |
1 | 2 | 1 | 2 |
FALSE |
|
Sequence current |
AMSQI |
N/A |
1 | 2 | 1 | 2 |
FALSE |
|
1ph current |
VECAXMMXU |
N/A |
1 | 2 | 1 | 2 |
FALSE |
|
1ph RMS current |
RMSAXMMXU |
N/A |
1 |
2 |
1 |
2 |
FALSE |
|
VT group measurement |
|||||||
|
3ph voltage |
VECVMMXU |
N/A |
1 | 1 | 1 | 2 |
FALSE |
|
3ph RMS voltage |
RMSVMMXU |
N/A |
1 | 1 | 1 | 2 |
FALSE |
|
Sequence voltage |
VMSQI |
N/A |
1 | 1 | 1 | 2 |
FALSE |
|
1ph voltage |
VECVXMMXU |
N/A |
● |
2 | 1 | 2 |
FALSE |
|
1ph RMS voltage |
RMSVXMMXU |
N/A |
● |
2 | 1 | 2 |
FALSE |
|
Bay measurement |
|||||||
|
Fundamental frequency active, reactive and apparent power values, power factor |
BAYMMXU |
N/A |
1 | 1 | 1 | 1 |
FALSE |
|
RMS active, reactive and apparent power |
BAYMMXU |
N/A |
1 | 1 | 1 | 1 |
FALSE |
|
Minimum and maximum demand values: RMS phase currents |
DVALMMXU |
N/A |
1 | 1 | 1 | 1 |
FALSE |
|
Minimum and maximum demand values: active, reactive, apparent power and power factor |
DVALMMXU |
N/A |
1 | 1 | 1 | 1 |
FALSE |
|
Active and reactive of energy values |
EMMTR |
N/A |
1 | 1 | 1 | 1 |
FALSE |
|
Bay Fourier current |
BAYMMXU |
N/A |
1 | 1 | 1 | 1 |
FALSE |
|
Bay RMS current |
BAYMMXU |
N/A |
1 | 1 | 1 | 1 |
FALSE |
|
Bay sequence current |
BAYMMXU |
N/A |
1 | 1 | 1 | 1 |
FALSE |
|
Bay Fourier voltage |
BAYMMXU |
N/A |
1 | 1 | 1 | 1 |
FALSE |
|
Bay RMS voltage |
BAYMMXU |
N/A |
1 | 1 | 1 | 1 |
FALSE |
|
Bay sequence voltage |
BAYMMXU |
N/A |
1 | 1 | 1 | 1 |
FALSE |
|
Bay harmonics current and voltage |
MHAI |
N/A |
● |
1 |
● |
1 |
FALSE |