Safety Inspection
DANGER |
|---|
|
HAZARD OF ELECTRIC SHOCK, explosion and arc flash
Do a high voltage test to detect any equipment degradation.
Failure to follow these instructions will result in death or serious injury.
|
The integrated EMC filter has Y capacitors.
The tripping current is exceeded when AC testing voltage is applied.
-
Test the forced cooling fan with DC voltage while performing the legally required high-voltage test. The voltage to be used corresponds to the peak value of the AC voltage required by the standard.
|
What to check |
How to check |
How often |
What action |
|---|---|---|---|
|
Contact protection cover for intactness or damage |
Visual inspection |
At least every 6 months |
Repair or replace the forced cooling fan. |
|
Forced cooling fan for damage to blades and housing |
Visual inspection |
At least every 6 months |
Replace the forced cooling fan. |
|
Fastening the cables |
Visual inspection |
At least every 6 months |
Tighten the cables. |
|
Fastening the earthing terminal |
Visual inspection |
At least every 6 months |
Tighten the earthing terminal. |
|
Insulation of cables for damage |
Visual inspection |
At least every 6 months |
Replace the cables. |
|
Impeller for wear/deposits/corrosion and damage |
Visual inspection |
At least every 6 months |
Clean the impeller or replace the forced cooling fan. |
|
Abnormal bearing noise |
Acoustic |
At least every 6 months |
Replace the forced cooling fan. |
DANGER