Other Settings
MicroLogic Setup
Settings |
Range |
Factory setting |
Step |
---|---|---|---|
Language |
German English US English UK Italian French Spanish Chinese |
English UK |
– |
Date / time |
– | – |
1 s |
Circuit breaker selection |
– |
Not defined |
– |
Power sign |
P+ P- |
P+ (flow from top to bottom) |
– |
Neutral CT |
– |
None |
– |
VT ratio Primary voltage |
100 to 1150 V |
690 V |
1 V |
Secondary voltage |
100 to 690 V |
690 V |
1 V |
System frequency |
50/60 Hz 400 Hz |
50/60 Hz |
– |
Measurement Setup
Settings |
Range |
Factory setting |
Step |
|
---|---|---|---|---|
System type |
3 Φ, 3 w, 3 CT 3 Φ, 4 w, 3 CT 3 Φ, 4 w, 4 CT |
3 Φ, 4 w, 4 CT |
– | |
Demand current |
Calculation method |
Thermal or block interval |
Block interval |
– |
Window type |
Fixed or sliding |
Sliding |
– | |
Interval |
5 to 60 minutes |
15 minutes |
1 minute |
|
Power demand |
Calculation method |
Thermal or block interval or sync. to comms |
Block interval |
– |
Window type |
Fixed or sliding |
Sliding |
– | |
Interval |
5 to 60 minutes |
15 minutes |
1 minute |
|
Sign convention |
IEEE IEEE alternate IEC |
IEEE |
– |
Communication Setup
Settings |
Range |
Factory setting |
---|---|---|
Com parameter |
Modbus |
– |
Address |
1-47 |
47 |
Baud rate |
9600 to 19200 bauds |
19200 bauds |
Parity |
Even None |
Even |
Connection |
2Wires+ULP or 4Wires |
2Wires+ULP |
Remote settings Access permit |
Yes / no |
Yes |
Access code |
0000 to 9999 |
0000 |
Remote control |
Manual Automatic |
Automatic |
Protection Setup
Settings |
Range |
Factory setting |
---|---|---|
Current protection |
Alarm / trip / OFF |
OFF |
Voltage protection |
||
Other protection |