Logical Node
System Logical Nodes (L Group)
Physical Device Information (LPHD) Class
Attribute name |
Attribute type |
Description/Value |
M/O/C/E |
See Supported Models |
---|---|---|---|---|
LNName |
Object name |
LPHD |
M |
X |
PhyNam |
DPL |
Physical device name plate |
M |
X |
PhyHealth |
ENS |
Physical device health |
M |
X |
Proxy |
SPS |
Indicates if this LN is a proxy |
M |
X |
Logical Node Zero (LLN0) Class
Attribute name |
Attribute type |
Description/Value |
M/O/C/E |
See Supported Models |
|
---|---|---|---|---|---|
LNName |
Object name |
LLN0 |
M |
X |
|
Common logical node information |
Mod |
ENC |
Mode |
M |
X |
Beh |
ENS |
Behaviour |
M |
X |
|
Health |
ENS |
Health |
M |
X |
|
NamPlt |
LPL |
Name plate |
M |
X |
|
LocKey |
SPS |
Local operation for complete LD |
O |
X |
|
Loc |
SPS |
Local control behaviour |
O |
X |
Metering and Measurement Logical Nodes (M Group)
Harmonics (MHAI) Class
Attribute name |
Attribute type |
Description/Value |
M/O/C/E |
See Supported Models |
|
---|---|---|---|---|---|
LNName |
Object name |
MHAI1 |
M |
X |
|
Common logical node information |
Beh |
ENS |
Behaviour |
M |
X |
Measured or calculated values |
Hz |
MV |
Basic frequency |
C |
X |
ThdA |
WYE |
Current total harmonic or interharmonic distortion |
O |
X |
|
ThdPPV |
DEL |
Phase to phase voltage total harmonic or interharmonic |
O |
X |
Metering (MMTR) Class
Attribute name |
Attribute type |
Description/Value |
M/O/C/E |
See Supported Models |
|
---|---|---|---|---|---|
LNName |
Object name |
MMTR1 |
M |
X |
|
Common logical node information |
Beh |
ENS |
Behaviour |
M |
X |
Measured or calculated values |
TotVAh(1) |
BCR |
Net apparent energy |
O |
X |
TotWh(1) |
BCR |
Net real energy |
O |
X |
|
TotVarh(1) |
BCR |
Net reactive energy |
O |
X |
|
(1) Values accumulated since last reset. |
Measurement (MMXU) Class
Attribute name |
Attribute type |
Description/Value |
M/O/C/E |
See Supported Models |
|
---|---|---|---|---|---|
LNName |
Object name |
MMXU1 |
M |
X |
|
Common logical node information |
Beh |
ENS |
Behaviour |
M |
X |
Measured or calculated values |
TotW |
MV |
Total real power |
O |
X |
TotVAr |
MV |
Total reactive power |
O |
X |
|
TotVA |
MV |
Total apparent power |
O |
X |
|
TotPF |
MV |
Average power factor |
O |
X |
|
Hz |
MV |
Power system frequency |
O |
X |
|
PPV |
DEL |
Phase to phase voltages, ENCluding angles |
O |
X |
|
A |
WYE |
Phase currents |
O |
X |
|
W |
WYE |
Phase active power |
O |
X |
|
VAr |
WYE |
Phase reactive power |
O |
X |
|
VA |
WYE |
Phase apparent power |
O |
X |
|
PF |
WYE |
Phase to ground power factor |
O |
X |
|
ClcMth(1) |
ENG |
Calculation method(1) |
C |
||
(1) The calculation method is unspecified and cannot be changed. |
Generic Reference Logical Nodes (G Group)
Generic Process I/O (GGIO1 – IO Module1)
Attribute name |
Attribute type |
Description/Value |
M/O/C/E |
See Supported Models |
|
---|---|---|---|---|---|
LNName |
Object name |
GGIO1 |
M |
X |
|
Common logical node information |
Mod |
ENC |
Mode |
M |
X |
Beh |
ENS |
Behaviour |
M |
X |
|
Functional attributes |
SPCS01 |
SPC |
Single point controllable status output |
O |
X |
SPCS02 |
SPC |
Single point controllable status output |
O |
X |
|
SPCS03 |
SPC |
Single point controllable status output |
O |
X |
|
Ind1 |
SPS |
General indication (binary input) |
O |
X |
|
Ind2 |
SPS |
General indication (binary input) |
O |
X |
|
Ind3 |
SPS |
General indication (binary input) |
O |
X |
|
Ind4 |
SPS |
General indication (binary input) |
O |
X |
|
Ind5 |
SPS |
General indication (binary input) |
O |
X |
|
Ind6 |
SPS |
General indication (binary input) |
O |
X |
|
AnIn1 |
MV |
Analog input |
O |
X |
Generic Process I/O (GGIO2 – IO Module2)
Attribute name |
Attribute type |
Description/Value |
M/O/C/E |
See Supported Models |
|
---|---|---|---|---|---|
LNName |
Object name |
GGIO2 |
M |
X |
|
Common logical node information |
Mod |
ENC |
Mode |
M |
X |
Beh |
ENS |
Behaviour |
M |
X |
|
Functional attributes |
SPCS01 |
SPC |
Single point controllable status output |
O |
X |
SPCS02 |
SPC |
Single point controllable status output |
O |
X |
|
SPCS03 |
SPC |
Single point controllable status output |
O |
X |
|
Ind1 |
SPS |
General indication (binary input) |
O |
X |
|
Ind2 |
SPS |
General indication (binary input) |
O |
X |
|
Ind3 |
SPS |
General indication (binary input) |
O |
X |
|
Ind4 |
SPS |
General indication (binary input) |
O |
X |
|
Ind5 |
SPS |
General indication (binary input) |
O |
X |
|
Ind6 |
SPS |
General indication (binary input) |
O |
X |
|
AnIn1 |
MV |
Analog input |
O |
X |
Generic Process I/O (GGIO3 – M2C Programmable Contact)
Attribute name |
Attribute type |
Description/Value |
M/O/C/E |
See Supported Models |
|
---|---|---|---|---|---|
LNName |
Object name |
GGIO3 |
M |
X |
|
Common logical node information |
Mod |
ENC |
Mode |
M |
X |
Beh |
ENS |
Behaviour |
M |
X |
|
Functional attributes |
SPCS01 |
SPC |
Single point controllable status output |
O |
X |
SPCS02 |
SPC |
Single point controllable status output |
O |
X |
Generic Process I/O (Ext_GGIO1 - External Inputs and Outputs (Chassis Position Status))
Attribute name |
Attribute type |
Description/Value |
M/O/C/E |
See Supported Models |
|
---|---|---|---|---|---|
LNName |
Object name |
Ext_GGIO1 |
M |
X |
|
Common logical node information |
Beh |
ENS |
Behaviour |
M |
X |
Mod |
ENC |
Mode |
C |
X |
|
ChassisPos(1) |
ENS |
Chassis Status Input |
O |
X |
|
(1) For more details on the extended data object, refer ENUM Type Extensions table. |
Supervisory Control Logical Node (C Group)
Attribute name |
Attribute type |
Description/Value |
M/O/C/E |
See Supported Models |
|
---|---|---|---|---|---|
LNName |
Object name |
CSWI1 |
M |
X |
|
Common logical node information |
Beh |
ENS |
Behaviour |
M |
X |
Functional attributes |
Pos |
DPC |
Double point control label status output |
M |
X |
Loc |
SPS |
Single point status |
O |
X |
Switchgear Logical Node (X Group)
Attribute name |
Attribute type |
Description/Value |
M/O/C/E |
See Supported Models |
|
---|---|---|---|---|---|
LNName |
Object name |
XCBR1 |
M |
X |
|
Common logical node information |
Beh |
ENS |
Behaviour |
M |
X |
Functional attributes |
Pos |
DPC |
Double point control label status output |
M |
X |
Loc |
SPS |
Single point status |
O |
X |
|
OpCnt |
INS |
Operation counter |
M |
X |
|
RTC(1) |
SPS |
Single point status/Ready to close |
E |
X |
|
BlkOpn |
SPC |
Single point controllable status output |
M |
X |
|
BlkCls |
SPC |
Single point controllable status output |
M |
X |
|
(1) Extended data object. |
Protection Function Logical Node (P Group)
Attribute name |
Attribute type |
Description/Value |
M/O/C/E |
See Supported Models |
|
---|---|---|---|---|---|
LNName |
Object name |
A51L_PTOC1/Long time overcurrent protection |
M |
X |
|
Common logical node information |
Beh |
ENS |
Behaviour |
M |
X |
Functional attributes |
Op |
ACT |
Operate/Protection activation information |
M |
X |
Str |
ACD |
Start/Direction protection activation information |
M |
X |
Attribute name |
Attribute type |
Description/Value |
M/O/C/E |
See Supported Models |
|
---|---|---|---|---|---|
LNName |
Object name |
A51S_PTOC1/Short time overcurrent protection |
M |
X |
|
Common logical node information |
Beh |
ENS |
Behaviour |
M |
X |
Functional attributes |
Op |
ACT |
Operate/Protection activation information |
M |
X |
Str |
ACD |
Start/Direction protection activation information |
M |
X |
Attribute name |
Attribute type |
Description/Value |
M/O/C/E |
See Supported Models |
|
---|---|---|---|---|---|
LNName |
Object name |
A51G_PTOC1/Ground fault protection |
M |
X |
|
Common logical node information |
Beh |
ENS |
Behaviour |
M |
X |
Functional attributes |
Op |
ACT |
Operate/Protection activation information |
M |
X |
Str |
ACD |
Start/Direction protection activation information |
M |
X |
Attribute name |
Attribute type |
Description/Value |
M/O/C/E |
See Supported Models |
|
---|---|---|---|---|---|
LNName |
Object name |
A51G_PTOC2/Earth leakage protection |
M |
X |
|
Common logical node information |
Beh |
ENS |
Behaviour |
M |
X |
Functional attributes |
Op |
ACT |
Operate/Protection activation information |
M |
X |
Str |
ACD |
Start/Direction protection activation information |
M |
X |
Attribute name |
Attribute type |
Description/Value |
M/O/C/E |
See Supported Models |
|
---|---|---|---|---|---|
LNName |
Object name |
A67_PTOC1/Directional time overCurrent protection |
M |
X |
|
Common logical node information |
Beh |
ENS |
Behaviour |
M |
X |
Functional attributes |
Op |
ACT |
Operate/Protection activation information |
M |
X |
Str |
ACD |
Start/Direction protection activation information |
M |
X |
Attribute name |
Attribute type |
Description/Value |
M/O/C/E |
See Supported Models |
|
---|---|---|---|---|---|
LNName |
Object name |
A50_PIOC1/Instantaneous protection |
M |
X |
|
Common logical node information |
Beh |
ENS |
Behaviour |
M |
X |
Functional attributes |
Op |
ACT |
Operate/Protection activation information |
M |
X |
Attribute name |
Attribute type |
Description/Value |
M/O/C/E |
See Supported Models |
|
---|---|---|---|---|---|
LNName |
Object name |
A32_PDOP1/Directional Overpower Protection |
M |
X |
|
Common logical node information |
Beh |
ENS |
Behaviour |
M |
X |
Functional attributes |
Op |
ACT |
Operate/Protection Activation Information |
M |
X |
Str |
ACD |
Start/Direction Protection Activation Information |
M |
X |
Attribute name |
Attribute type |
Description/Value |
M/O/C/E |
See Supported Models |
|
---|---|---|---|---|---|
LNName |
Object name |
A81_PTUF1/Underfrequency protection |
M |
X |
|
Common logical node information |
Beh |
ENS |
Behaviour |
M |
X |
Functional attributes |
Op |
ACT |
Operate/Protection activation information |
M |
X |
Str |
ACD |
Start/Direction protection activation information |
M |
X |
Attribute name |
Attribute type |
Description/Value |
M/O/C/E |
See Supported Models |
|
---|---|---|---|---|---|
LNName |
Object name |
A81_PTOF1/Overfrequency protection |
M |
X |
|
Common logical node information |
Beh |
ENS |
Behaviour |
M |
X |
Functional attributes |
Op |
ACT |
Operate/Protection activation information |
M |
X |
Str |
ACD |
Start/Direction protection activation information |
M |
X |
Attribute name |
Attribute type |
Description/Value |
M/O/C/E |
See Supported Models |
|
---|---|---|---|---|---|
LNName |
Object name |
A27_PTUV1/Undervoltage-1 Protection |
M |
X |
|
Common logical node information |
Beh |
ENS |
Behaviour |
M |
X |
Functional attributes |
Op |
ACT |
Operate/Protection activation information |
O |
X |
Str |
ACD |
Start/Direction protection activation information |
M |
X |
Attribute name |
Attribute type |
Description/Value |
M/O/C/E |
See Supported Models |
|
---|---|---|---|---|---|
LNName |
Object name |
A27_PTUV2/Undervoltage-2 protection |
M |
X |
|
Common logical node information |
Beh |
ENS |
Behaviour |
M |
X |
Functional attributes |
Op |
ACT |
Operate/Protection activation information |
O |
X |
Str |
ACD |
Start/Direction protection activation information |
M |
X |
Attribute name |
Attribute type |
Description/Value |
M/O/C/E |
See Supported Models |
|
---|---|---|---|---|---|
LNName |
Object name |
A59_PTOV1/Overvoltage-1 Protection |
M |
X |
|
Common logical node information |
Beh |
ENS |
Behaviour |
M |
X |
Functional attributes |
Op |
ACT |
Operate/Protection activation information |
O |
X |
Str |
ACD |
Start/Direction protection activation information |
M |
X |
Attribute name |
Attribute type |
Description/Value |
M/O/C/E |
See Supported Models |
|
---|---|---|---|---|---|
LNName |
Object name |
A59_PTOV2/Overvoltage-2 protection |
M |
X |
|
Common logical node information |
Beh |
ENS |
Behaviour |
M |
X |
Functional attributes |
Op |
ACT |
Operate/Protection activation information |
O |
X |
Str |
ACD |
Start/Direction protection activation information |
M |
X |
Attribute name |
Attribute type |
Description/Value |
M/O/C/E |
See Supported Models |
|
---|---|---|---|---|---|
LNName |
Object name |
PTRC1–Protection Trip Conditioning |
M |
X |
|
Common logical node information |
Beh |
ENS |
Behaviour |
M |
X |
Functional attributes |
Op |
ACT |
Operate/Protection activation information |
C |
X |
Tr |
ACT |
Protection trip conditioning for PTRC |
C |
X |
Common Data Attributes Classes
The following tables list the fields found in each common data attribute class. The field descriptions are as follows:
-
M: Mandatory fields
-
O: Optional fields
-
C: Conditional fields
Timestamp
Attribute name |
Attribute type |
Value/Rrange |
M/O/C |
Comments |
---|---|---|---|---|
SecondsSinceEpoch |
INT32 |
(0...MAX) |
M |
- |
FractionOfSecond |
INT24U |
Default: 0 |
M |
Default |
TimeQuality |
TimeQuality |
See TimeQuality table below |
M |
Default |
TimeQuality
Attribute name |
Attribute type |
Value/Range |
M/O/C |
Comments |
---|---|---|---|---|
LeapSecondsKnown |
Boolean |
Default: false |
M |
Supported |
ClockFailure |
Boolean |
Default: false |
M |
Default |
ClockNotSynchronized |
Boolean |
Default: false |
M |
Supported |
TimeAccuracy |
Coded Enum |
1ms-T1 |
M |
Default |
Quality
Attribute name |
Attribute type |
Value/Range |
M/O/C |
Comments |
---|---|---|---|---|
validity |
Packed list Coded enum |
Good/Invalid/Questionable |
M |
Supported |
detailQual |
Packed list |
- |
M |
Supported |
- overflow |
Boolean |
Default: False |
M |
Default: False |
- outOfRange |
Boolean |
True/False |
M |
Default: False |
- badReference |
Boolean |
True/False |
M |
Default: False |
- oscillatory |
Boolean |
True/False |
M |
Default: False |
- failure |
Boolean |
True/False |
M |
Default: False |
- oldData |
Boolean |
True/False |
M |
Default: False |
- inconsistent |
Boolean |
True/False |
M |
Default: False |
- inaccurate |
Boolean |
True/False |
M |
Default: False |
source |
Coded enum |
Process/Substituted Default: False |
M |
Default: Process |
test |
Boolean |
True/false |
M |
Default: False |
operatorBlocked |
Boolean |
True/false |
M |
Default: False |
Vector
Attribute name |
Attribute type |
Value/Range |
M/O/C |
Comments |
---|---|---|---|---|
mag |
AnalogValue |
Analog value |
M |
- |
Operate Configuration
Attribute name |
Attribute type |
Value/Range |
M/O/C |
Comments |
---|---|---|---|---|
ctlVal |
Boolean |
- |
M |
- |
origin |
Originator |
- |
M |
- |
ctlNum |
INT8U |
- |
M |
- |
T |
Timestamp |
- |
O |
- |
Test |
Boolean |
- |
O |
- |
Check |
Check |
- |
O |
- |
Operate Configuration 2
Attribute name |
Attribute type |
Value/Range |
M/O/C |
Comments |
---|---|---|---|---|
ctlVal |
INT32 |
- |
M |
- |
origin |
Originator |
- |
M |
- |
ctlNum |
INT8U |
- |
M |
- |
T |
Timestamp |
- |
O |
- |
Test |
Boolean |
- |
O |
- |
Check |
Check |
- |
O |
- |
Analog Value
Attribute name |
Attribute type |
Value/Range |
M/O/C |
Comments |
---|---|---|---|---|
f |
Float32 |
Floating point value |
C |
- |
Originator
Attribute name |
Attribute type |
Value/Range |
M/O/C |
Comments |
---|---|---|---|---|
orCat |
ENUM |
Refer to IEC 61850-7-3 standard |
M |
- |
orIdent |
Octet String64 |
M |
- |
Unit
Attribute name |
Attribute type |
Value/Range |
M/O/C |
Comments |
---|---|---|---|---|
SIUnit |
Enum |
Refer to IEC 61850-7-3 standard |
M |
- |
multiplier |
Enum |
Refer to IEC 61850-7-3 standard |
O |
Default :1 |
Sub-Data Attributes
CtlModel Value
Attribute name |
Supported/Not Supported |
---|---|
status-only |
Supported |
direct-with-normal-security |
Supported |
sbo-with-normal-security |
Supported |
direct-with-enhanced-security |
Not Supported |
sbo-with-enhanced-security |
Supported |
Common Data Classes
The following tables list the fields found in each common data attribute class. The field descriptions are as follows:
-
M: Mandatory fields
-
O: Optional fields
-
C: Conditional fields
Single Point Status (SPS)
Attribute name |
Attribute type |
FC |
M/O/C |
Comments |
---|---|---|---|---|
stVal |
Boolean |
ST |
M |
- |
q |
Quality |
ST |
M |
- |
t |
Timestamp |
ST |
M |
- |
d |
Visible string 255 |
DC |
O |
- |
Integer Status (INS)
Attribute name |
Attribute type |
FC |
M/O/C |
Comments |
---|---|---|---|---|
stVal |
INT32 |
ST |
M |
- |
q |
Quality |
ST |
M |
- |
t |
Timestamp |
ST |
M |
- |
Enumerated Status (ENS)
Attribute name |
Attribute type |
FC |
M/O/C |
Comments |
---|---|---|---|---|
stVal |
Enumerated |
ST |
M |
- |
q |
Quality |
ST |
M |
- |
t |
Timestamp |
ST |
M |
- |
Binary Counter Reading (BCR)
Attribute name |
Attribute type |
FC |
M/O/C |
Comments |
---|---|---|---|---|
actVal |
Int64 |
ST |
M |
- |
q |
Quality |
ST |
M |
- |
t |
Timestamp |
ST |
M |
- |
units |
Unit |
CF |
O |
- |
pulsQty |
Float32 |
CF |
M |
Default:1 |
Measured Value (MV)
Attribute name |
Attribute type |
FC |
M/O/C |
Comments |
---|---|---|---|---|
mag |
AnalogVal |
MX |
M |
- |
q |
Quality |
MX |
M |
- |
t |
Timestamp |
MX |
M |
- |
units |
Unit |
CF |
O |
Read only |
db |
Int32U |
CF |
O |
Supported range 1 to 100 (Integer) If the db value is configured to a value > 100, then it will be considered as 0. |
d |
Visible string 255 |
DC |
O |
- |
Complex Measured Value (CMV)
Attribute name |
Attribute type |
FC |
M/O/C |
Comments |
---|---|---|---|---|
cVal |
Vector |
MX |
M |
- |
q |
Quality |
MX |
M |
- |
t |
Timestamp |
MX |
M |
- |
units |
Unit |
CF |
O |
- |
db |
Int32U |
CF |
O |
- |
WYE (WYE)
Attribute name |
Attribute type |
FC |
M/O/C |
Comments |
---|---|---|---|---|
phsA |
CMV |
- |
C |
- |
phsB |
CMV |
- |
C |
- |
phsC |
CMV |
- |
C |
- |
neut |
CMV |
- |
C |
- |
net |
CMV |
- |
C |
- |
Delta (DEL)
Attribute name |
Attribute type |
FC |
M/O/C |
Comments |
---|---|---|---|---|
phsAB |
CMV |
- |
C |
- |
phsBC |
CMV |
- |
C |
- |
phsCA |
CMV |
- |
C |
- |
Controllable Single Point (SPC)
Attribute name |
Attribute type |
FC |
M/O/C |
Comments |
---|---|---|---|---|
stVal |
Boolean |
ST |
M |
- |
q |
Quality |
ST |
M |
- |
t |
Timestamp |
ST |
M |
- |
Oper |
Operate |
CO |
M |
- |
ctlVal |
Boolean |
CO |
M |
- |
ctlModel |
CtlModel |
CF |
M |
Default: Direct with normal security |
cancel |
Boolean |
CO |
M |
- |
Controllable Enumerated Status (ENC)
Attribute name |
Attribute type |
FC |
M/O/C |
Comments |
---|---|---|---|---|
stVal |
Int8 |
ST |
M |
- |
q |
Quality |
ST |
M |
- |
t |
Timestamp |
ST |
M |
- |
ctlModel |
CtlModels |
CF |
M |
Default: Read only |
Logical Node Name Plate (LPL)
Attribute name |
Attribute type |
FC |
M/O/C |
Comments |
---|---|---|---|---|
vendor |
Visible string 255 |
DC |
M |
- |
serNum |
Visible string 255 |
DC |
O |
- |
model |
Visible string 255 |
DC |
O |
- |
location |
Visible string 255 |
DC |
C |
- |
Directional Protection Activation Information (ACD)
Attribute name |
Attribute type |
FC |
M/O/C |
Comments |
---|---|---|---|---|
general |
Boolean |
ST |
M |
- |
dirGeneral |
Enumerated (Int8) |
ST |
M |
- |
q |
Quality |
ST |
M |
- |
t |
Timestamp |
ST |
M |
- |
Protection Activation Information (ACT)
Attribute name |
Attribute type |
FC |
M/O/C |
Comments |
---|---|---|---|---|
general |
Boolean |
ST |
M |
- |
q |
Quality |
ST |
M |
- |
t |
Timestamp |
ST |
M |
- |
Logical Node Name Plate (LPL)
Attribute name |
Attribute type |
FC |
M/O/C |
Comments |
---|---|---|---|---|
vendor |
Visible string 255 |
DC |
M |
- |
swRev |
Visible string 255 |
DC |
M |
- |
configRev |
Visible string 255 |
DC |
C |
- |
ldNs |
Visible string 255 |
EX |
C |
- |
Device Name Plate (DPL)
Attribute name |
Attribute type |
FC |
M/O/C |
Comments |
---|---|---|---|---|
vendor |
Visible string 255 |
DC |
M |
- |
swRev |
Visible string 255 |
DC |
O |
- |
model |
Visible string 255 |
DC |
O |
- |
location |
Visible string 255 |
EX |
O |
- |
Double Point Status Contact (DPC)
Attribute name |
Attribute type |
FC |
M/O/C |
Comments |
---|---|---|---|---|
stVal |
Coded Enum |
ST |
M |
- |
q |
Quality |
ST |
M |
- |
t |
Timestamp |
ST |
M |
- |
Oper |
Operate |
CO |
M |
- |
ctlVal |
Boolean |
CO |
M |
- |
ctlModel |
CtlModel |
CF |
M |
- |
cancel |
Boolean |
CO |
M |
- |
sboClass |
sboclassess |
CF |
C |
- |
Timeout |
Int32U |
CF |
M |
Default: 120000 |
orgin |
orginator |
ST |
C |
- |
ctlNum |
Int8U |
ST |
C |
- |
Logical Nodes Per Device Type
Logical node |
IFE interface |
EIFE interface |
IFE server with firmware version ≥ V005.001.000 |
---|---|---|---|
LLN0 |
X |
X |
X |
LPHD1 |
X |
X |
X |
CSWI1 |
X |
X |
X |
GGIO1 |
X |
X |
X |
GGIO2 |
X |
X |
X |
GGIO3 |
X |
X |
X |
Ext_GGIO1 |
X |
X |
X |
A51L_PTOC1 |
X |
X |
X |
A51S_PTOC1 |
X |
X |
X |
A51G_PTOC1 |
X |
X |
X |
A51G_PTOC2 |
X |
X |
X |
A67_PTOC1 |
X |
X |
X |
A32_PDOP1 |
X |
X |
X |
A81_PTUF1 |
X |
X |
X |
A81_PTOF1 |
X |
X |
X |
A27_PTUV1 |
X |
X |
X |
A27_PTUV2 |
X |
X |
X |
A59_PTOV1 |
X |
X |
X |
A59_PTOV2 |
X |
X |
X |
A50_PIOC1 |
X |
X |
X |
PTRC1 |
X |
X |
X |
MMXU1 |
X |
X |
X |
MMTR1 |
X |
X |
X |
MHAI1 |
X |
X |
X |
XCBR1 |
X |
X |
X |
ENUM Type Extensions
Enumerated Type: New ENUM
Description: For Ext_GGIO1,
ChassisPos data object
Value |
Description |
Remarks |
---|---|---|
0 |
Position Discrepancy |
- |
1 |
Connected |
- |
2 |
Test |
- |
3 |
Disconnected |
- |
Enumerated Types
The following subsections specify the enumerations that are associated with some common data class attributes. The definition of the enumerations are according to IEC 61850-7-3 and IEC 61850-7-4 unless otherwise stated.
Enumerated Type: AddCause
Description: Cause
of the rejected command
Value |
Description |
Remarks |
---|---|---|
0 |
Unknown |
- |
1 |
Not-supported |
- |
2 |
Blocked-by-switching-hierarchy |
- |
3 |
Select-failed |
- |
4 |
Invalid-position |
- |
5 |
Position-reached |
- |
6 |
Parameter-change-in-execution |
- |
7 |
Step-limit |
- |
8 |
Blocked-by-Mode |
- |
9 |
Blocked-by-process |
- |
10 |
Blocked-by-interlocking |
- |
11 |
Blocked-by-synchrocheck |
- |
12 |
Command-already-in-execution |
- |
13 |
Blocked-by-health |
- |
14 |
1-of-n-control |
- |
15 |
Abortion-by-cancel |
- |
16 |
Time-limit-over |
- |
17 |
Abortion-by-trip |
- |
18 |
Object-not-selected |
- |
19 |
Object-already-selected |
- |
20 |
No-access-authority |
- |
21 |
Ended-with-overshoot |
- |
22 |
Abortion-due-to-deviation |
- |
23 |
Abortion-by-communication-loss |
- |
24 |
Blocked-by-command |
- |
25 |
None |
- |
26 |
Inconsistent-parameters |
- |
27 |
Locked-by-other-client |
- |
Enumerated Type: BehKind
Description : Behaviour
Value |
Description |
Remarks |
---|---|---|
1 |
on |
- |
2 |
blocked |
Not Supported |
3 |
test |
Not Supported |
4 |
test/blocked |
Not Supported |
5 |
off |
- |
Enumerated Type: CtlModelKind
Description :
Control Model
Value |
Description |
Remarks |
---|---|---|
0 |
status-only |
- |
1 |
direct-with-normal-security |
- |
2 |
sbo-with-normal-security |
- |
3 |
direct-with-enhanced-security |
Not Supported |
4 |
sbo-with-enhanced-security |
- |
Enumerated Type: FaultDirectionKind
Description:
Direction
Value |
Description |
Remarks |
---|---|---|
0 |
unknown |
- |
1 |
forward |
- |
2 |
backward |
- |
3 |
both |
- |
Enumerated Type: HealthKind
Description : Health
Value |
Description |
Remarks |
---|---|---|
1 |
Ok |
- |
2 |
Warning |
- |
3 |
Alarm |
- |
Enumerated Type: ModKind
Description: Mode
Value |
Description |
Remarks |
---|---|---|
1 |
on |
- |
2 |
blocked |
Not Supported |
3 |
test |
Not Supported |
4 |
test/blocked |
Not Supported |
5 |
off |
- |
Enumerated Type: MultiplierKind
Description
: Exponents of the multiplier value in base 10
Value |
Description |
Remarks |
---|---|---|
-24 |
y |
- |
-21 |
z |
- |
-18 |
a |
- |
-15 |
f |
- |
-12 |
p |
- |
-9 |
n |
- |
-6 |
µ |
- |
-3 |
m |
- |
-2 |
c |
- |
-1 |
d |
- |
0 |
- |
- |
1 |
da |
- |
2 |
h |
- |
3 |
k |
- |
6 |
M |
- |
9 |
G |
- |
12 |
T |
- |
15 |
P |
- |
18 |
E |
- |
21 |
Z |
- |
24 |
Y |
- |
Enumerated Type: OriginatorCategoryKind
Description
: Ed2 IEC61850-7-2 defined
Value |
Description |
Remarks |
---|---|---|
0 |
not-supported |
- |
1 |
bay-control |
- |
2 |
station-control |
- |
3 |
remote-control |
- |
4 |
automatic-bay |
- |
5 |
automatic-station |
- |
6 |
automatic-remote |
- |
7 |
maintenance |
- |
8 |
process |
Control commands with OrCat as process will be rejected. |
Enumerated Type: SIUnitKind
Description: SI
Units derived from ISO/IEC 1000
Value |
Description |
Remarks |
---|---|---|
-16 |
years |
- |
-15 |
months |
- |
-14 |
weeks |
- |
-13 |
V/s |
- |
-12 |
mins |
- |
-11 |
hours |
- |
-10 |
days |
- |
-9 |
°F |
- |
-8 |
ratio |
- |
–7 |
miles |
- |
-6 |
inches |
- |
-5 |
feet |
- |
-4 |
df/dt |
- |
-2 |
% |
- |
-1 |
pu |
- |
1 |
- |
- |
2 |
m |
- |
3 |
kg |
- |
4 |
s |
- |
5 |
A |
- |
6 |
K |
- |
7 |
mol |
- |
8 |
cd |
- |
9 |
deg |
- |
10 |
rad |
- |
11 |
sr |
- |
21 |
Gy |
- |
22 |
Bq |
- |
23 |
°C |
- |
24 |
Sv |
- |
25 |
F |
- |
26 |
C |
- |
27 |
S |
- |
28 |
H |
- |
29 |
V |
- |
30 |
ohm |
- |
31 |
J |
- |
32 |
N |
- |
33 |
Hz |
- |
34 |
Ix |
- |
35 |
Lm |
- |
36 |
Wb |
- |
37 |
T |
- |
38 |
W |
- |
39 |
Pa |
- |
41 |
m2 |
- |
42 |
m3 |
- |
43 |
m/s |
- |
44 |
m/s2 |
- |
45 |
m3/s |
- |
46 |
m/m3 |
- |
47 |
M |
- |
48 |
kg/m3 |
- |
49 |
m2/s |
- |
50 |
W/m K |
- |
51 |
J/K |
- |
52 |
ppm |
- |
53 |
1/s |
- |
54 |
rad/s |
- |
55 |
W/m2 |
- |
56 |
J/m2 |
- |
57 |
S/m |
- |
58 |
K/s |
- |
59 |
Pa/s |
- |
60 |
J/kg K |
- |
61 |
VA |
- |
62 |
Watts |
- |
63 |
VAr |
- |
64 |
phi |
- |
65 |
cos(phi) |
- |
66 |
Vs |
- |
67 |
V2 |
- |
68 |
As |
- |
69 |
A2 |
- |
70 |
A2t |
- |
71 |
VAh |
- |
72 |
Wh |
- |
73 |
VArh |
- |
74 |
V/Hz |
- |
75 |
Hz/s |
- |
76 |
char |
- |
77 |
char/s |
- |
78 |
kgm2 |
- |
79 |
dB |
- |
80 |
J/Wh |
- |
81 |
W/s |
- |
82 |
l/s |
- |
83 |
dBm |
- |