Input Source
Index |
Input source |
---|---|
0 |
None |
1 |
Fixed 0 |
2 |
Fixed 1 |
3–6 |
Reserved |
7 |
Reset_Key (Main Unit) |
8 |
DI 1 |
9 |
DI 2 |
10 |
DI 3 |
11 |
DI 4 |
12 |
DI 5 |
13 |
DI 6 |
14 |
DI 7 |
15 |
DI 8 |
16 |
DI 9 |
17 |
DI 10 |
18 |
DI 11 |
19 |
DI 12 |
20 |
DI 13 |
21 |
DI 14 |
22 |
DI 15 |
23 |
DI 16 |
24 |
DI 17 |
25 |
DI 18 |
26 |
DI 19 |
27 |
DI 20 |
28 |
DI 21 |
29 |
DI 22 |
30 |
DI 23 |
31 |
DI 24 |
40 |
DO 1 |
41 |
DO 2 |
42 |
DO 3 |
43 |
DO 4 |
44 |
DO 5 |
45 |
DO 6 |
46 |
DO 7 |
47 |
DO 8 |
48 |
DO 9 |
49 |
DO 10 |
50 |
DO 11 |
51 |
DO 12 |
52 |
DO 13 |
53– 231 |
Reserved |
232 |
Pickup Status |
233 |
Alarm Status |
234 |
Trip Status |
235 |
Motor Stop Error Detection |
236 |
Reserved |
237 |
Block Output |
238–247 |
Reserved |
248 |
Motor Stop |
249 |
Motor Start |
250 |
Motor Run |
251 |
Motor Inhibit |
252–263 |
Reserved |
264 |
Thermal Overload Alarm |
265 |
Locked Rotor Alarm |
266 |
Stalled Rotor Alarm |
267 |
Definite Time Overcurrent Alarm |
268 |
Normal Inverse Overcurrent Alarm |
269 |
Short Time Overcurrent Alarm |
270 |
Calculated Ground Current Alarm |
271 |
Measured Ground Current Alarm |
272 |
Under Current Alarm |
273 |
Current Imbalance Alarm |
274 |
Current Phase Loss Alarm |
275 |
Current Phase Reversal Alarm |
276 |
Under Voltage Alarm |
277 |
Over Voltage Alarm |
278 |
Voltage Phase Loss Alarm |
279 |
Voltage Imbalance Alarm |
280 |
Voltage Phase Reversal Alarm |
281 |
Under Frequency Alarm |
282 |
Over Frequency Alarm |
283 |
Reserved |
284 |
Communication Loss Alarm |
285 |
Over Temperature Alarm |
286 |
Under Power Alarm |
287 |
Over Power Alarm |
288 |
Under Power Factor Alarm |
289–295 |
Reserved |
296 |
Thermal Overload Pickup |
297 |
Locked Rotor Pickup |
298 |
Stalled Rotor Pickup |
299 |
Definite Time Overcurrent Pickup |
300 |
Normal Inverse Overcurrent Pickup |
301 |
Short Time Overcurrent Pickup |
302 |
Calculated Ground Current Pickup |
303 |
Measured ground current Pickup |
304 |
Under Current Pickup |
305 |
Current Imbalance Pickup |
306 |
Current Phase Loss Pickup |
307 |
Current Phase Reversal Pickup |
308 |
Under Voltage Pickup |
309 |
Over Voltage Pickup |
310 |
Voltage Phase Loss Pickup |
311 |
Voltage Imbalance Pickup |
312 |
Voltage Phase Reversal Pickup |
313 |
Under Frequency Pickup |
314 |
Over Frequency Pickup |
315 |
Excessive Start Time Pickup |
316 |
Communication Loss Pickup |
317 |
Over Temperature Pickup |
318 |
Under Power Pickup |
319 |
Over Power Pickup |
320 |
Under Power Factor Pickup |
321 |
Reserved |
328 |
Thermal Overload Trip |
329 |
Locked Rotor Trip |
330 |
Stalled Rotor Trip |
331 |
Definite Time Overcurrent Trip |
332 |
Normal Inverse Overcurrent Trip |
333 |
Short Time Overcurrent Trip |
334 |
Calculated Ground Current Trip |
335 |
Measured Ground Current Trip |
336 |
Under Current Trip |
337 |
Current Imbalance Trip |
338 |
Current Phase Loss Trip |
339 |
Current Phase Reversal Trip |
340 |
Under Voltage Trip |
341 |
Over Voltage Trip |
342 |
Voltage Phase Loss Trip |
343 |
Voltage Imbalance Trip |
344 |
Voltage Phase Reversal Trip |
345 |
Under Frequency Trip |
346 |
Over Frequency Trip |
347 |
Excessive Start Time Trip |
348 |
Communication Loss Trip |
349 |
Over Temperature Trip |
350 |
Under Power Trip |
351 |
Over Power Trip |
352 |
Under Power factor Trip |
353–359 |
Reserved |
360 |
Interlock 1 Alarm |
361 |
Interlock 2 Alarm |
362 |
Interlock 3 Alarm |
363 |
Interlock 4 Alarm |
364 |
Interlock 5 Alarm |
365 |
Interlock 6 Alarm |
366 |
Interlock 7 Alarm |
367 |
Interlock 8 Alarm |
368 |
Interlock 9 Alarm |
369 |
Interlock 10 Alarm |
370 |
Interlock 11 Alarm |
371 |
Interlock 12 Alarm |
372–375 |
Reserved |
376 |
Interlock 1 Pickup |
377 |
Interlock 2 Pickup |
378 |
Interlock 3 Pickup |
379 |
Interlock 4 Pickup |
380 |
Interlock 5 Pickup |
381 |
Interlock 6 Pickup |
382 |
Interlock 7 Pickup |
383 |
Interlock 8 Pickup |
384 |
Interlock 9 Pickup |
385 |
Interlock 10 Pickup |
386 |
Interlock 11 Pickup |
387 |
Interlock 12 Pickup |
388–391 |
Reserved |
392 |
Interlock 1 Trip |
393 |
Interlock 2 Trip |
394 |
Interlock 3 Trip |
395 |
Interlock 4 Trip |
396 |
Interlock 5 Trip |
397 |
Interlock 6 Trip |
398 |
Interlock 7 Trip |
399 |
Interlock 8 Trip |
400 |
Interlock 9 Trip |
401 |
Interlock 10 Trip |
402 |
Interlock 11 Trip |
403 |
Interlock 12 Trip |
404–503 |
Reserved |
504 |
Contactor Output 1 |
505 |
Contactor Output 2 |
506 |
Contactor Output 3 |
507 |
Contactor Output 4 |
508 |
Contactor Output 5 |
509–535 |
Reserved |
536 |
Motor Forward Running |
537 |
Motor Reverse Running |
538 |
Motor Fast Forward Running |
539 |
Motor Fast Reverse Running |
540 |
Motor Running in Star (Forward) |
541 |
Motor Running in Delta (Forward) |
542 |
Motor Running in Star (Reverse) |
543 |
Motor Running in Delta (Reverse) |
544 |
Motor in Star-Delta Changeover (Forward) |
545 |
Motor in Star-Delta Changeover (Reverse) |
546 |
Interlocking Time Active |
547 |
Change-Over Pause Active |
548–551 |
Reserved |
552 |
Status - Permissive Command 1 |
553 |
Status - Permissive Command 2 |
554 |
Status - Permissive Command 3 |
555 |
Status - Permissive Command 4 |
556 |
Status - Permissive Command 5 |
557 |
Status - Permissive Command 6 |
558 |
Status - Permissive Command 7 |
559 |
Status - Permissive Command 8 |
560–583 |
Reserved |
584 |
No Voltage Inhibit |
585 |
Under Voltage Inhibit |
586 |
Trip Inhibit |
587 |
Thermal Inhibit |
588 |
Max Starts Inhibit |
589 |
Interlock 1 Inhibit |
590 |
Interlock 2 Inhibit |
591 |
Interlock 3 Inhibit |
592 |
Interlock 4 Inhibit |
593 |
Interlock 5 Inhibit |
594 |
Interlock 6 Inhibit |
595 |
Interlock 7 Inhibit |
596 |
Interlock 8 Inhibit |
597 |
Interlock 9 Inhibit |
598 |
Interlock 10 Inhibit |
599 |
Interlock 11 Inhibit |
600 |
Interlock 12 Inhibit |
601 |
Local DI Stop Inhibit |
602 |
Remote DI Stop Inhibit |
603 |
Communication Stop Inhibit |
604 |
Forced Stop Inhibit |
605 |
Antibackspin Inhibit |
606 |
Reserved |
607 |
Direction Change Inhibit |
608 |
Speed Change Inhibit |
609 |
Custom Stop Inhibit |
610–615 |
Reserved |
616 |
Sensor Module Communication Error Detected |
617 |
Expansion Module Communication Error Detected |
618 |
HMI Communication Error Detected |
619 |
EEPROM Interface Error Detected |
620 |
EEPROM Checksum Error Detected |
621 |
Configuration Error Detected |
622 |
PROFIBUS DP Interface Error Detected |
623 |
Internal Temperature Error Detected |
624 |
Watchdog Timeout Detected |
625 |
Low Battery Detected |
626 |
Reserved |
627 |
Reserved |
628 |
Energy Register Overflow |
629 |
Error Detected During Expansion Module Initialization |
630 |
RTC Initialization Error Detected |
631 |
Internal Temperature Minor Error Detected |
632–647 |
Reserved |
648 |
Watchdog Timeout Detected |
649 |
ADC Conversion Error Detected |
650 |
Flash Error Detected |
651 |
Reserved |
652 |
Voltage Configuration Not Detected |
653 |
Reserved |
654 |
Calibration Error Detected |
655 |
VL1 Measurement Error Detected |
656 |
VL2 Measurement Error Detected |
657 |
VL3 Measurement Error Detected |
658 |
IL1 Low Gain Measurement Error Detected |
659 |
IL1 High Gain Measurement Error Detected |
660 |
IL2 Low Gain Measurement Error Detected |
661 |
IL2 High Gain Measurement Error Detected |
662 |
IL3 Low Gain Measurement Error Detected |
663 |
IL3 High Gain Measurement Error Detected |
664–65534 |
Reserved |
65535 |
Custom Logic |