7EN02-0443-00

Configuring the CT and VT ratio

  1. Press and hold and at the same time for 2 seconds.
  2. Use the or button to enter the meter Passcode (High) (Default is “0010”) and press .
  3. Use the button to scroll to Ratio and press .
  4. Use the or button to scroll through the options and press to confirm the new setting.
  5. Press to save your changes to the meter.

    Setting

    Options

    Description

    EM3570X

    CT Sec

    • 1000
    • 333

    Select the size of the CT secondary, in millivolts.

    CT Pri

    1 to 32767

    Enter the size of the CT primary, in Amps.

    EM3570AX

    CT Sec

    Rcoil

    CT ratio secondary

    NOTE: The CT ratio secondary is read-only.

    CT Pri

    5000

    CT ratio primary

    NOTE: The CT ratio primary is read-only.

    VT Sec

    • 100
    • 110
    • 115
    • 120

    Select the size of the VT secondary, in Volts.

    VT Pri

    1 to 1000000

    Enter the size of the VT primary, in Volts.