Configuring the demand setup parameters
- Double-click on Demand Setup to open the dialog showing the list of parameters.
- Select the Power Demand and click Edit to open its setup dialog.
- Choose values from the drop down lists for Mode and Interval period/ Periods x
Sub-Interval (in minutes).
Parameters
Options
Description
Mode
Timed Interval Sliding Block
Interval period (minutes)
-
10, 15, 20, 30, 60
Select an interval from the range 10, 15, 20, 30, 60 minutes. For demand intervals less than 15 minutes, the value is updated every 15 seconds. For demand intervals with 15 minutes and greater, the demand value is updated every 60 seconds. The meter displays the demand value for the last completed interval.
Timed Interval Fixed Block (Default)
Interval period (minutes)
-
10, 15, 20, 30, 60
Select an interval from the range 10, 15, 20, 30, 60 minutes. The meter calculates and updates the demand at the end of each fixed interval.
Timed Interval Rolling Block
Periods x Sub-Interval
Periods
Sub-Interval (minutes)
1
(Default)10, 15, 20, 30, 60
(Default: 15)2
5, 10, 15, 30
3
5, 10, 20
4
5, 15
5
2, 3, 4, 6, 12
6
5, 10
10
1, 2, 3, 6
12
5
15
1, 2, 4
20
1, 3
30
1, 2
60
1
Select period and a subinterval. The demand is updated at the end of each subinterval. The meter displays the demand value for the last completed interval.
-
- Click OK, and then click Send to save your changes to the meter.NOTE: When changes are not saved to the meter, the status bar on the bottom left screen shows Download Incomplete.