Configuring the meter power system wiring

  1. Press and hold and at the same time for 2 seconds.
  2. Use the or button to enter the meter Passcode (High) (Default is “0010”) and press .
  3. Use the button to scroll to Wire and press .
  4. Use the or button to scroll through the options and press to confirm the new setting.
  5. Press to save your changes to the meter.

    Setting

    Options

    Description

    Type

    • 3PH4W
    • 1PH4W LN
    • 1PH2W LN
    • 1PH2W LL
    • 1PH3W LLN
    • 3PH3W

    Select the power system type the meter is wired to.

    VTCon

    3PH4W

    • Direct Con

    • Wye(3VT)

    1PH4W LN

    • Direct Con

    1PH2W LN

    • Direct Con

    1PH2W LL

    • Direct Con

    1PH3W LLN

    • Direct Con

    3PH3W

    • Direct Con

    • Delta(2VT)

    Select how many voltage transformers (VT) are connected to the electrical power system.

    CTCon

    The titles listed are for the HMI mode in IEEE, with the corresponding titles in IEC mode in square brackets [ ].

    3PH4W

    • Ia [I1]

    • Ia [I1], Ic [I3]

    • Ia [I1], Ib [I2], Ic [I3]

    1PH4W LN

    • Ia [I1], Ib [I2]

    • Ia [I1], Ib [I2], Ic [I3]

    1PH2W LN

    • Ia [I1]

    1PH2W LL

    • Ia [I1]

    1PH3W LLN

    • Ia [I1], Ib [I2]

    3PH3W

    • Ia [I1]

    • Ia [I1], Ic [I3]

    • Ia [I1], Ib [I2], Ic [I3]

    Define how many current transducers (CT) are connected to the meter and which terminals they are connected to.

    A.Sup

    0.1 to 1.0

    Select the values to set the suppression current.