Configuring the demand method
- Press and hold
and
at the same time for 2 seconds.
- Use the
or
button to enter the meter Passcode (High) (Default is “0010”) and press
.
- Use the
button to scroll to DMD and press
.
- Use the
or
button to scroll through the options and press
to confirm the new setting.
- Press
to save your changes to the meter.
Setting
Options
Description
Method
Sliding
Int.Val(min)
-
10
-
15
-
20
-
30
-
60
Select an interval from the range 10, 15, 20, 30, 60 minutes. For demand intervals less than 15 minutes, the value is updated every 15 seconds. For demand intervals of 15 minutes and greater, the demand value is updated every 60 seconds. The meter displays the demand value for the last completed interval.
Rolling Int.Val(min)
-
10
-
15
-
20
-
30
-
60
Sub Int.(min)
Int.Val(min)
Sub Int.(min)
10
1, 2, 5, 10
15
1, 3, 5, 15
20
1, 2, 4, 5, 10, 20
30
1, 2, 3, 5, 6, 10, 15, 30
60
1, 2, 3, 4, 5, 6, 10, 12, 15, 20, 30, 60
Select an interval and a subinterval. Demand is updated at the end of each subinterval. The meter displays the demand value for the last completed interval.
NOTE: The subinterval must divide evenly into the interval (for example, three 5-minute (5 x 60 seconds) subintervals for a 15-minute interval).Fixed
Int.Val(min)
-
10
-
15
-
20
-
30
-
60
Select an interval from the range 10, 15, 20, 30, 60 minutes. The meter calculates and updates the demand at the end of each fixed interval.
-