Coupling of Cubicles
| NOTICE |
|---|
|
HAZARD OF INCORRECT INSTALLATION
Before assembly, ensure to remove the lifting brackets
and its associated hardware.
Failure to follow these instructions can result in equipment damage.
|
Follow the below steps to couple the cubicles:
-
Position the second cubicle next to the previous one in accordance with the assignment plan and align it (Figure 30 and Figure 31).
-
Install the 7.2/12/17.5 kV cubicles to one another on the front side with six quantities of M10 x 30 screw, washer, and nut; rear side with seven quantities of M10 x 30 screw, washer, and nut (Figure 30).
-
Install the 24 kV cubicles to one another on the front side with five quantities of M10 x 30 screw, washer, and nut; rear side with four quantities of M10 x 30 screw, washer, and nut (Figure 31).
Figure 30
Screw-Fastening the 7.2/12/17.5
kV Cubicles to One Another (Sheet 1 of 2)
Figure 30
Screw-Fastening the 7.2/12/17.5
kV Cubicles to One Another (Sheet 2 of 2)
|
1 |
Allen screw M10 x 30 |
|
2 |
Washer M10 |
|
3 |
Nut M10 |
Figure 31
Screw-Fastening the 24 kV Cubicles
to One Another (Sheet 1 of 2)
Figure 31
Screw-Fastening the 24 kV Cubicles
to One Another (Sheet 2 of 2)
|
1 |
Allen screw M10 x 30 |
|
2 |
Washer M10 |
|
3 |
Nut M10 |