DOCA0005EN-14

Alarm status information

NOTE: E denotes the extension bit; the hex value assumes E = 0.

Data format

Primary VIF

Manufacturer specific VIFE

Description

bin

hex

02

E011 0111

37

Alarm status:

  • 0x0000 = Alarm is inactive
  • 0x0100 = Alarm is active

02

E011 1000

38

Acknowledgement status:

  • 0x0000 = historic alarm is acknowledged by the user
  • 0x0100 = historic alarm is unacknowledged by the user

04

ED

E011 1001

39

Timestamp of last alarm (DD/MM/YYYY hh:mm:ss)

05

E011 1010

3A

Value at last alarm

02

E011 0100

34

Overload alarm configuration:

  • 0x0000 = disabled
  • 0x0100 = enabled

05

E011 0101

35

The pickup setpoint in kW for the overload alarm

QR Code is a registered trademark of DENSO WAVE INCORPORATED in Japan and other countries.