Energy, energy by tariff and input metering
The energy and energy by tariff measurements listed below are preserved through power failures.
Energy reset and active tariff information |
||||||
---|---|---|---|---|---|---|
Address |
Register |
Action |
Size |
Type |
Units |
Description |
0x0CB3 |
3252 |
R |
4 |
DATETIME |
— |
Energy Reset Date and Time |
0x0DE1 |
3554 |
R |
4 |
DATETIME |
— |
Input Metering Accumulation Reset Date and Time NOTE: Not applicable
for iEM3150
/ iEM3250
/ iEM3350
|
0x105E |
4191 |
R/WC |
1 |
UInt16 |
— |
Multi Tariffs Energy Active Rate:
NOTE: You can only set the tariff using this method if the Tariff
Mode is set to by Communication.
NOTE: Not applicable for iEM3150
/ iEM3250
/ iEM3350
|
Energy values – 64-bit integer |
||||||
---|---|---|---|---|---|---|
Address |
Register |
Action |
Size |
Type |
Units |
Description |
Total Energy (cannot be reset) |
||||||
0x0C83 |
3204 |
R |
4 |
Int64 |
Wh |
Total Active Energy Import |
0x0C87 |
3208 |
R |
4 |
Int64 |
Wh |
Total Active Energy Export NOTE: Not applicable for iEM3150
/ iEM3250
/ iEM3350
|
0x0C93 |
3220 |
R |
4 |
Int64 |
VARh |
Total Reactive Energy Import NOTE: Not applicable for iEM3150
/ iEM3250
/ iEM3350
|
0x0C97 |
3224 |
R |
4 |
Int64 |
VARh |
Total Reactive Energy Export NOTE: Not applicable for iEM3150
/ iEM3250
/ iEM3350
|
Partial Energy |
||||||
0x0CB7 |
3256 |
R |
4 |
Int64 |
Wh |
Partial Active Energy Import |
0x0CC7 |
3272 |
R |
4 |
Int64 |
VARh |
Partial Reactive Energy Import NOTE: Not applicable for iEM3150
/ iEM3250
/ iEM3350
|
Phase Energy |
||||||
0x0DBD |
3518 |
R |
4 |
Int64 |
Wh |
Active Energy Import Phase 1 |
0x0DC1 |
3522 |
R |
4 |
Int64 |
Wh |
Active Energy Import Phase 2 |
0x0DC5 |
3526 |
R |
4 |
Int64 |
Wh |
Active Energy Import Phase 3 |
Input Metering Counter |
||||||
0x0DE5 |
3558 |
R |
4 |
Int64 |
Unit |
Input Metering Accumulation NOTE: Not applicable for iEM3150
/ iEM3250
/ iEM3350
|
Energy by Tariff (iEM3155 / iEM3255 / iEM3355 only) |
||||||
0x1063 |
4196 |
R |
4 |
Int64 |
Wh |
Rate A Active Energy Import |
0x1067 |
4200 |
R |
4 |
Int64 |
Wh |
Rate B Active Energy Import |
0x106B |
4204 |
R |
4 |
Int64 |
Wh |
Rate C Active Energy Import |
0x106F |
4208 |
R |
4 |
Int64 |
Wh |
Rate D Active Energy Import |
Energy values – 32-bit floating point |
||||||
---|---|---|---|---|---|---|
Address |
Register |
Action |
Size |
Type |
Units |
Description |
Total Energy (cannot be reset) |
||||||
0xB02B |
45100 |
R |
2 |
Float32 |
kWh |
Total Active Energy Import |
0xB02D |
45102 |
R |
2 |
Float32 |
kWh |
Total Active Energy Export NOTE: Not applicable for iEM3150
/ iEM3250
/ iEM3350
|
0xB02F |
45104 |
R |
2 |
Float32 |
kVARh |
Total Reactive Energy Import NOTE: Not applicable for iEM3150
/ iEM3250
/ iEM3350
|
0xB031 |
45106 |
R |
2 |
Float32 |
kVARh |
Total Reactive Energy Export NOTE: Not applicable for iEM3150
/ iEM3250
/ iEM3350
|
Partial Energy |
||||||
0xB033 |
45108 |
R |
2 |
Float32 |
kWh |
Partial Active Energy Import |
0xB035 |
45110 |
R |
2 |
Float32 |
kVARh |
Partial Reactive Energy Import NOTE: Not applicable for iEM3150
/ iEM3250
/ iEM3350
|
Phase Energy |
||||||
0xB037 |
45112 |
R |
2 |
Float32 |
kWh |
Active Energy Import Phase 1 |
0xB039 |
45114 |
R |
2 |
Float32 |
kWh |
Active Energy Import Phase 2 |
0xB03B |
45116 |
R |
2 |
Float32 |
kWh |
Active Energy Import Phase 3 |
Input Metering Counter |
||||||
0xB03D |
45118 |
R |
2 |
Float32 |
Unit |
Input Metering Accumulation NOTE: Not applicable for iEM3150
/ iEM3250
/ iEM3350
|
Energy by Tariff (iEM3155 / iEM3255 / iEM3355 only) |
||||||
0xB03F |
45120 |
R |
2 |
Float32 |
kWh |
Rate A Active Energy Import |
0xB041 |
45122 |
R |
2 |
Float32 |
kWh |
Rate B Active Energy Import |
0xB043 |
45124 |
R |
2 |
Float32 |
kWh |
Rate C Active Energy Import |
0xB045 |
45126 |
R |
2 |
Float32 |
kWh |
Rate D Active Energy Import |