4th telegram information
Byte No |
Size |
Value |
Description |
---|---|---|---|
1 |
1 |
68 |
Start character |
2 |
1 |
X |
L-field, calculated from C field to last user data |
3 |
1 |
X |
L-field, repeated |
4 |
1 |
68 |
Start character |
5 |
1 |
08 |
C-field, RSP_UD |
6 |
1 |
X |
A-field, address |
7 |
1 |
72 |
CI-field, variable data respond, LSB first |
8 – 11 |
4 |
XXXX |
Identification number, 8 BCD digits |
12 – 13 |
2 |
4CA3 |
Manufacturer: SCH |
14 |
1 |
00 |
Version |
15 |
1 |
02 |
Medium, 02 = Electricity |
16 |
1 |
X |
Number of accesses |
17 |
1 |
X |
Status |
18 – 19 |
2 |
0000 |
Signature (0000 = no encryption) |
20 |
1 |
07 |
DIF size, 64 Bit Integer |
21 |
1 |
03 |
Energy |
22 – 29 |
8 |
XXXXXXXX |
Total Active Energy Import |
30 |
1 |
07 |
DIF size, 64 Bit Integer |
31 |
1 |
83 |
Energy |
32 |
1 |
FF |
VIF next byte is manufacturer specific |
33 |
1 |
FF |
Export energy |
34 – 41 |
8 |
09 |
Total Active Energy Export |
42 |
1 |
XXXXXXXX |
DIF size, 32 Bit Real |
43 |
1 |
05 |
Power |
44 – 47 |
4 |
2E |
Total Power |
48 |
1 |
XXXX |
DIF indicating that this is the last telegram |
49 |
1 |
0F |
CS checksum, calculated from C field to last data |
50 |
1 |
X |
Stop character |