Overload alarm setup and acknowledgment
SND_UD code |
Data format |
Manufacturer specific VIFE |
Range/Options |
Description |
|
---|---|---|---|---|---|
bin |
hex |
||||
00 |
05 |
E011 0101 |
35 |
0 – 9999999 |
The pickup setpoint in kW for the overload alarm |
00 |
02 |
E011 0100 |
34 |
0, 1 |
Overload alarm setup:
|
Use the information in the table below to acknowledge the overload alarm.
SND_UD code |
Data format |
Manufacturer specific VIFE |
Range/Options |
Description |
|
---|---|---|---|---|---|
bin |
hex |
||||
07 |
00 |
E011 1000 |
B8 |
— |
Acknowledge alarm |