DOCA0005EN-14

Energy and energy by tariff measurements (INT64 and FLOAT32)

The energy and energy by tariff measurements listed below are preserved through power failures. An addition of energy values in FLOAT32 format have been provided with the existing 64-bit registers.

NOTE: E denotes the extension bit; the hex value assumes E = 0.

Data format

DIFE

Primary VIF

Primary VIFE

Manufacturer-specific VIFE

Description

bin

hex

bin

hex

INT64

07

03

Total active energy import

07

83

E000 1001

09

Total active energy export

87

40

03

Total reactive energy import

87

40

83

E000 1001

09

Total reactive energy export

07

83

E000 1101

0D

Partial active energy import

87

40

83

E000 1101

0D

Partial reactive energy import

07

83

E000 0001

01

Active energy import phase 1

07

83

E000 0010

02

Active energy import phase 2

07

83

E000 0011

03

Active energy import phase 3

03

E001 0000

10

Active tariff

  • 0 = Multi Tariff feature is disabled
  • 1 = rate A (tariff 1) active
  • 2 = rate B (tariff 2) active
  • 3 = rate C (tariff 3) active
  • 4 = rate D (tariff 4) active

87

10

03

Rate A (tariff 1) active energy import

87

20

03

Rate B (tariff 2) active energy import

87

30

03

Rate C (tariff 3) active energy import

87

80 10

03

Rate D (tariff 4) active energy import

07

E110 0001

61

Input metering accumulation

04

ED

E000 1100

0C

Date and time of last partial energy reset

04

ED

E000 1110

0E

Date and time of last input metering reset

FLOAT32

05

03

Total active energy import

05

83

E000 1001

09

Total active energy export

85

40

83

Total reactive energy import

85

40

83

E000 1001

09

Total reactive energy export

05

83

E000 1101

0D

Partial active energy import

85

40

83

E000 1101

0D

Partial reactive energy import

05

83

E000 0001

01

Active energy import phase 1

05

83

E000 0010

02

Active energy import phase 2

05

83

E000 0011

03

Active energy import phase 3

85

10

03

Rate A (tariff 1) active energy import

85

20

03

Rate B (tariff 2) active energy import

85

30

03

Rate C (tariff 3) active energy import

85

80 10

03

Rate D (tariff 4) active energy import

05

E110 0001

61

Input metering accumulation

NOTE: The unit of FLOAT32 energy value is kWh/kVARh.

QR Code is a registered trademark of DENSO WAVE INCORPORATED in Japan and other countries.